NDAC 33.1-14-09-19
Modular hot water heating boilers
Cite as N.D. Admin. Code ยง 33.1-14-09-19
1.
Individual modules must be limited to a maximum input of four hundred thousand British
thermal units [4.22 x 10 to the eighth power joules] per hour (gas), three gallons [11.36 liters]
per hour (oil), or one hundred fifteen kilowatt-hours (electricity).
2.
Each module of a modular hot water heating boiler must be equipped with the following:
a.
Pressure/altitude gauge (see section 33.1-14-09-12).
b.
Thermometer (see section 33.1-14-09-13).
c.
Operating temperature control (see subsection 2 of section 33.1-14-09-14).
d.
Safety relief valve (see section 33.1-14-09-07).
e.
Drain valve (see section 33.1-14-09-20).
3.
The assembled modular hot water heating boiler must be equipped with the following:
a.
High-limit temperature control (see subsection 1 of section 33.1-14-09-14).
b.
Low-water fuel cutoff (see section 33.1-14-09-18).
c.
Makeup feedwater connection (see section 33.1-14-09-11).
d.
Expansion tank provisions (see section 33.1-14-09-15).
e.
Stop valves (see section 33.1-14-09-10).