NDAC 33.1-18-01-05
Protection of ground water sources
Cite as N.D. Admin. Code ยง 33.1-18-01-05
1.
Minimum protective depths of wells. All wells shall be watertight to exclude contamination.
Wells shall be designed to seal off formations that are or may be contaminated or undesirable.
Unless approved otherwise by the department, the annular space between a well hole
excavation and the outside of the well casing shall be filled with neat cement grout, high-solids
bentonite clay grout, bentonite chips, or bentonite tablets at least one and one-half inches
[3.81 centimeters] in thickness from a depth of not less than thirty feet [9.1 meters] to the
ground surface or the upper end of the well casing if a pitless unit or adapter is installed. Wells
with a depth of thirty feet [9.1 meters] or less shall be grouted from within two feet [60.96
centimeters] of the top of the well screen to the ground surface or the upper end of the well
casing if a pitless unit or adapter is installed. Greater depths are preferable and may be
required for specific installations as determined by review of the plans and specifications.
The annular space of wells constructed in unconsolidated formations without overlying
confining beds and static water levels less than thirty feet [9.1 meters] below the ground
surface shall be filled with neat cement grout, high-solids bentonite clay grout, bentonite chips,
or bentonite tablets at least one and one-half inches [3.81 centimeters] in thickness from the
static water level or a depth of not less than ten feet [3.0 meters], whichever is greater, to the
ground surface or the upper end of the well casing if a pitless unit or adapter is installed.
Driven well casing may, when conditions warrant, be installed without grouting.
2.
Required protection for various sources.
a.
Radial collector wells. The location of all caisson construction joints and porthole
assemblies shall be indicated. The caisson wall shall be substantially reinforced. Radial
collectors shall be in areas and at depths approved by the department. Provisions shall
be made to assure minimum vertical rise. The top of the caisson shall be covered with a
watertight floor. All openings in the floor shall be curbed and protected from entrance of
foreign material. Pump discharge piping shall not be placed through caisson walls.
b.
Dug or bored wells. Dug or bored wells greater than two feet [60.96 centimeters] in
diameter shall be developed only where geological conditions preclude the development
of a satisfactory drilled well.
Every dug or bored well shall have a continuous watertight casing. The section of casing
in the producing zone serving as the well screen shall readily admit water and be
structurally sound to withstand external pressures.
The open space between the excavation and the installed casing shall be sealed with
neat cement grout, high-solids bentonite clay grout, bentonite chips, or bentonite tablets.
The watertight casing shall extend at least twelve inches [30.48 centimeters] above
finished ground surface. A cover slab at least four inches [10.16 centimeters] thick,
adequately reinforced and having a diameter sufficient to overlap the lining by two inches
[5.08 centimeters] shall be provided. The slab shall be constructed without joints.
The top of the slab shall be sloped to drain to all sides and a watertight joint made where
the slab rests on the well casing using cement mortar or a mastic compound.
A manhole, if installed, shall be provided with a curb cast in the slab and extending at
least four to six inches [10.16 to 15.24 centimeters] above the slab. The manhole shall
have a watertight overlapping cover extending down around the curb by at least two
inches [5.08 centimeters].
Adequate sized pipe sleeve or sleeves shall be cast in place in the slab to accommodate
the type of pump or pump piping proposed for the well.
c.
Infiltration wells. Infiltration wells may be considered where geological conditions
preclude possibility of developing an acceptable drilled well. The area around the well
shall be under the control of the water purveyor for a distance acceptable to or required
by the department. The flow in the lines shall be by gravity to a collecting well. The water
shall be continuously chlorinated to assure bacterial purity.
d.
Flowing wells. The construction of flowing wells shall be in compliance with North Dakota
Century Code chapter 61-20.
The construction of flowing wells shall be such that the flow from them can be controlled.
Well casing shall be installed, and the annular space grouted with neat cement to form a
tight seal. The neat cement grout shall extend upward from within twenty feet
[6.1 meters] of the top of the aquifer to the ground surface or the upper end of the well
casing if a pitless unit or adapter is installed.
Well casings shall be joined in a watertight manner. Flow control should consist of valved
pipe connections, watertight pump connections, or receiving reservoirs set at an
elevation corresponding to the artesian head.
e.
Existing wells. The department shall be consulted for requirements concerning the
reconstruction of existing wells.