NDAC 33.1-18-01-08
Storage tanks
Cite as N.D. Admin. Code ยง 33.1-18-01-08
1.
Public water systems. Storage equipment for public water systems must be as shown on
approved plans and specifications.
2.
Private water systems. Storage equipment must be as follows:
a.
All tanks must be certified under water system council standards for size and pressure.
b.
Hydropneumatic tanks must have a working pressure rating in excess of the maximum
system pressure but not less than seventy-five pounds per square inch [34.02 kilograms
per 6.45 square centimeters].
c.
All tanks must be coated or made of materials resistant to corrosion.
d.
All tanks must be constructed of materials or coatings which are nontoxic.
e.
All tanks must be provided with a means of draining.
f.
Atmospheric storage tanks must be provided with a cover to prevent the entrance of
unauthorized persons, dirt, or vermin. The cover must be vented with a return bend vent
pipe having an area not less than the area of the downfeed riser pipe and the vent must
be screened with corrosion-resistant screen having not less than fourteen and not more
than twenty openings per linear inch [2.54 centimeters].