NDAC 33.1-18-01-07
Pump installation for water wells
Cite as N.D. Admin. Code ยง 33.1-18-01-07
1.
Pumphouse appurtenances. The installation of necessary appurtenances for public wells
shall be as illustrated in pump installation details contained in the diagrams attached to this
chapter.
a.
Floor drain. The pumproom floor shall be watertight and shall slope away from the pump
base. The pumproom floor shall be provided with a floor drain discharging to a sump at
least twenty-five feet [7.62 meters] from the well.
b.
Vents. Provisions shall be made for venting the well casing to the atmosphere. There
shall be no holes in the pump base which might allow wastewater or other material to
enter the well. A breather tube shall be installed of sufficient size to permit air to enter
and leave the well freely with the changing of water elevation caused by starting and
stopping the pump. The breather tube shall terminate in a full one-hundred-eighty-degree
bend at least eighteen inches [45.72 centimeters] above the floor, securely screened with
sixteen mesh wire screen. If the breather tube or a depth gauge line passes through the
base of the pump or through the seal connection into the well, the hole about the tube
shall be sealed.
c.
Water level measurement. An access plug for a measuring tape or an air line and
drawdown gauge for determining location of the water level shall be installed during the
installation of the pump on all public wells. Installation of permanent water level
measuring equipment shall be made using corrosion-resistant materials firmly attached,
in a vertical position, to the drop pipe or pump column in such a manner as to prevent
entrance of foreign materials. The air line shall extend from the top of the well to several
feet [meters] below the lowest anticipated water level. The length of the air line shall be
accurately measured and the length recorded.
2.
Cutting of well casing. No casing shall be cut off or cut into below ground level except to
install a pitless unit or adapter.
3.
Pitless unit and adapter.
a.
Pitless unit. Pitless units designed to replace a section of well casing must meet the
standards of the national sanitation foundation or the water systems council and must:
(1)
Be factory fabricated from point of connection with the well casing to the unit cap or
cover. The materials used must be durable, at least equal in quality to the well
casing, to prevent excessive corrosion.
(2)
Form an unbroken extension of the well casing from the point of discharge to a point
above ground level as specified for upper well terminals.
(3)
Have an inside diameter equal to or greater than the inside diameter of the well
casing to facilitate work and repair on the well, pump, or well screen. Any deviation
from this paragraph must be approved in writing by the department.
(4)
Conduct water from a well casing without exposing the well to contamination
through openings in the casing.
(5)
Have access to the casing for disinfection of the well.
(6)
Be capped with a cover having a downward flange which will overlap the edge of
the unit. The cover must be securely fastened to the unit and must be sufficiently
snug to the unit to be verminproof or watertight if required.
The cover must provide for watertight entrance of electrical cables, vent piping, and
an air line or a tap for wetted tape measurements of depth to water level of a well.
(7)
Be installed by threaded, welded, or compression flange gasketed connection to the
cutoff casing. The threaded, welded, or compression flange gasketed connection to
the cutoff casing must be watertight. If the connection to the casing is to be a field
weld, the factory-assembled unit must be designed specifically for field welding.
(8)
Have all field connections between the pitless unit and the water service pipe
threaded, flanged, or mechanical joint.
b.
Pitless adapter. Commercially manufactured clamp-on or weld-on pitless adapters for
attachment to the exterior of a well casing may be installed when approved by the
department. Pitless adapters must be installed according to manufacturer's specifications
and meet the standards of the national sanitation foundation. A list of approved pitless
adapters is available from the department.
(1)
Pitless adapters must be constructed and installed so as to prevent the
entrance of contaminants into the well or water supply through openings in the
well casing.
(2)
The pitless adapter must provide adequate clearance within the well to permit
insertion and withdrawal of the pump and system components through the
upper terminal of the well casing.
(3)
The pitless adapter must be connected to the well casing with
clamps-and-gasket or by welding and must be watertight. To assure a
watertight connection between the pitless adapter and the well casing, care
must be used in cutting the hole in the well casing, preferably with a
hole-cutting saw. All burrs from the cutting process must be removed. Both the
outside and the inside surfaces of well casing surrounding the hole must be
smooth.
(4)
A pitless cap or cover must enclose the upper terminal of the well casing. The
cap, entrance of electrical cables, vent piping, air lines, etc., must be as
specified for pitless units.
(5)
All field connections between the pitless adapter and the water service pipe
must be threaded, flanged, or mechanical joint.
(6)
All other aspects of pitless adapter requirements must be as specified for
pitless units.
c.
Freezing. Water service piping must be installed below recorded frost penetration. A
minimum depth of seven feet [2.28 meters] below grade is recommended to prevent
freezing.
4.
Over-the-well pumps. Power-driven pumps located over a well shall be installed on a
concrete base of sufficient height to permit the outside casing to extend one inch
[2.54 centimeters] above the concrete base. On all public water wells, the annular opening
between the drill hole and casing shall be filled with cement grout before the pump base and
pumphouse floor are constructed. If the well is of the gravel wall type, the outer casing shall
extend at least twelve inches [30.48 centimeters] above the pumproom floor with suitable
provisions made for adding gravel. The inner casing shall extend one inch [2.54 centimeters]
above the pump base. Note diagrams no. 1 and no. 2, pump installation details, in the
diagrams attached to this chapter.
A sanitary well seal shall be installed at the top of the well casing to prevent the entrance of
contaminated water or objectionable material.
5.
Pump column. A separate pump column, suction or discharge pipe shall be installed inside
the well casing in all instances, whether the well is to be pumped by suction, airlift, or deep
well pump.
6.
Submersible pumps. The discharge line installed inside of the well casing must meet the
standards for ferrous or nonferrous well casing in subsections 2 and 3 of section
33.1-18-01-06. The discharge line shall leave the well at the top of the casing. The opening
between the discharge line and casing or pipe sleeve shall be sealed watertight with an
expanding rubber seal or equivalent device. When an underground discharge is desired, a
properly installed pitless unit or, when approved by the department, a pitless adapter shall be
used.
The electrical cable shall be firmly attached to the pump riser at intervals of twenty feet
[6.10 meters] or less.
When a check valve is not part of the pump, a check valve shall be installed on the pump
discharge line within the well.
A check valve on the pump discharge line is not required on nonpressurized wells for livestock
use that would be damaged by freezing, when an airgap or other cross-connection control
protection is provided.
7.
Offset pumps. Pumps offset from public wells shall be located in an aboveground
pumphouse or other building. All portions of suction lines buried below the ground surface
between the well and the pump shall be enclosed in a protective pipe of standard thickness
and be sealed watertight at both ends.
This requirement shall be considered satisfied if the suction line lies within a pressure
discharge line.
Offset pumps for private wells may be located in a basement provided that the pumps and all
suction pipes are elevated at least twelve inches [30.48 centimeters] above the floor.
8.
Hand pumps. Hand pumps shall be of the force type equipped with a packing gland around
the pump rod, a delivery spout which is closed and downward directed, and a one-piece
bell-type base which is part of the pump stand or is attached to the pump column in a
watertight manner.
The bell base of the pump shall be bolted with a gasket to a flange which is securely attached
to the casing or pipe sleeve.
9.
Pump controls.
a.
Public water wells. Pump controls for public water wells must be installed in accordance
with the manufacturer's recommendations as shown on approved plans and
specifications.
b.
Private water wells. Pump controls for private water wells should be installed in
accordance with manufacturer's recommendations and must include:
(1)
A pressure-activated pump switch.
(2)
A thermal overload switch.
(3)
A flow control orifice or a low water level cutoff switch on all pumps having an output
in excess of the well capacity.
(4)
A pressure relief valve on positive displacement pumps.
(5)
The installation of necessary appurtenances for private water wells should be as
illustrated in diagram no. 4 - pitless unit and appurtenances for private wells.