NDAC 33.1-24-08-30
General release detection requirements for all underground storage tank systems
Cite as N.D. Admin. Code ยง 33.1-24-08-30
1.
Owners and operators of underground storage tank systems must provide a method, or
combination of methods, of release detection that:
a.
Can detect a release from any portion of the tank and the connected underground piping
that routinely contains product;
b.
Is installed and calibrated in accordance with the manufacturer's instructions;
c.
Beginning on April 1, 2021, is operated and maintained, and electronic and mechanical
components are tested for proper operation, in accordance with one of the following:
manufacturer's instructions, a code of practice developed by a nationally recognized
association or independent testing laboratory, or requirements determined by the
department to be no less protective of human health and the environment than the two
options listed above. A test of the proper operation must be performed at least annually
and, at a minimum, as applicable to the facility, cover the following components and
criteria:
(1)
Automatic tank gauge and other controllers: test alarm, verify system configuration,
and test battery backup;
(2)
Probes and sensors: inspect for residual buildup, ensure floats move freely, ensure
shaft is not damaged, ensure cables are free of kinks and breaks, and test alarm
operability and communication with controller;
(3)
Automatic line leak detector: test operation to meet criteria in subsection 1 of
section 33.1-24-08-34 by simulating a leak;
(4)
Vacuum pumps and pressure gauges: ensure proper communication with sensors
and controller; and
(5)
Hand-held electronic sampling equipment associated with groundwater and vapor
monitoring: ensure proper operation.
NOTE: The following code of practice may be used to comply with subdivision c of
subsection 1: Petroleum Equipment Institute Publication RP1200, "Recommended
Practices for the Testing and Verification of Spill, Overfill, Leak Detection and Secondary
Containment Equipment at UST Facilities".
d.
Meets the performance requirements in sections 33.1-24-08-33, 33.1-24-08-34,
33.1-24-08-70, 33.1-24-08-71, or 33.1-24-08-72, as applicable, with any performance
claims and their manner of determination described in writing by the equipment
manufacturer or installer. In addition, the methods listed in subsections 2, 3, and 4 of
section 33.1-24-08-33; subsections 1 and 2 of section 33.1-24-08-34; and sections
33.1-24-08-70, 33.1-24-08-71, or 33.1-24-08-72, must be capable of detecting the leak
rate or quantity specified for that method in the corresponding section of the rule with a
probability of detection of ninety-five hundredths and a probability of false alarm of five
hundredths.
2.
When a release detection method operated in accordance with the performance standards in
sections 33.1-24-08-33 and 33.1-24-08-34; and either 33.1-24-08-70, 33.1-24-08-71, or
33.1-24-08-72 indicates a release may have occurred, owners and operators must notify the
department in accordance with sections 33.1-24-08-40 through 33.1-24-08-43.
3.
Any underground storage tank system that cannot apply a method of release detection that
complies with the requirements of this section must complete the closure procedures in
sections 33.1-24-08-60 through 33.1-24-08-64. For previously deferred underground storage
tank systems described in sections 33.1-24-08-01, 33.1-24-08-02, or 33.1-24-08-03; and
33.1-24-08-70, 33.1-24-08-71, or 33.1-24-08-72, this requirement applies after the effective
dates described in paragraphs 2 and 3 of subdivision a of subsection 1 of section
33.1-24-08-01 and subsection 1 of section 33.1-24-08-71.