NDAC 33.1-24-08-33
Methods of release detection for tanks
Cite as N.D. Admin. Code ยง 33.1-24-08-33
Each method of release detection for tanks used to meet the requirements of section 33.1-24-08-31
must be conducted in accordance with the following:
1.
Inventory control. Product inventory control (for another test of equivalent performance) must
be conducted monthly to detect a release of at least one percent of flowthrough plus one
hundred thirty gallons [492.10 liters] on a monthly basis in the following manner:
a.
Inventory volume measurements for regulated substance inputs, withdrawals, and the
amount still remaining in the tank are recorded each operating day;
b.
The equipment used is capable of measuring the level of product over the full range of
the tank's height to the nearest one-eighth of an inch [3.05 millimeters];
c.
The regulated substance inputs are reconciled with delivery receipts by measurement of
the tank inventory volume before and after delivery;
d.
Deliveries are made through a drop tube that extends to within one foot [0.30 meters] of
the tank bottom;
e.
Product dispensing is metered and recorded within the local standards for meter
calibration or an accuracy of six cubic inches [98.32 milliliters] for every five gallons
[18.93 liters] of product withdrawn; and
f.
The measurement of any water level in the bottom of the tank is made to the nearest
one-eighth of an inch [3.05 millimeters] at least once a month.
NOTE: Practices described in the American Petroleum Institute, Recommended Practice
RP 1621, "Bulk Liquid Stock Control at Retail Outlets", may be used, where applicable, as
guidance in meeting the requirements.
2.
Manual tank gauging. Manual tank gauging must meet the following requirements:
a.
Tank liquid level measurements are taken at the beginning and ending of a period using
the appropriate minimum duration of test value in the table below during which no liquid
is added to or removed from the tank;
b.
Level measurements are based on an average of two consecutive stick readings at both
the beginning and ending of the period;
c.
The equipment used is capable of measuring the level of product over the full range of
the tank's height to the nearest one-eighth of an inch [3.05 millimeters];
d.
A release is suspected and subject to the requirements of sections 33.1-24-08-40
through 33.1-24-08-43 if the variation between beginning and ending measurements
exceeds the weekly or monthly standards in the following table:
Nominal Tank
Capacity
Minimum Duration
of Test
Weekly Standard
(One Test)
Monthly Standard
(Average of Four
Tests)
550 gallons or less
36 hours
10 gallons
5 gallons
551-1,000 gallons
(when tank diameter
is 64 inches)
44 hours
9 gallons
4 gallons
551-1,000 gallons
(when tank diameter
is 48 inches)
58 hours
12 gallons
6 gallons
551-1,000 gallons
(also requires
periodic tank
tightness testing)
36 hours
13 gallons
7 gallons
1,001-2,000 gallons
(also requires
periodic tank
tightness testing)
36 hours
26 gallons
13 gallons
e.
Tanks of five hundred fifty gallons [2,081.98 liters] or less nominal capacity and tanks
with a nominal capacity of five hundred fifty-one to one thousand gallons [2,085.76 to
3,785.41 liters] which meet the tank diameter criteria in the table in subdivision d may
use this as the sole method of release detection. All other tanks with a nominal capacity
of five hundred fifty-one to two thousand gallons [2,085.76 to 7,570.80 liters] may use
this method in place of inventory control in subsection 1. Tanks of greater than
two thousand gallons [7,570.80 liters] nominal capacity may not use this method to meet
the requirements of sections 33.1-24-08-30 through 33.1-24-08-35.
3.
Tank tightness testing. Tank tightness testing (or another test of equivalent performance)
must be capable of detecting a one-tenth gallon [.38 liter] per hour leak rate from any portion
of the tank that routinely contains product while accounting for the effects of thermal
expansion or contraction of the product, vapor pockets, tank deformation, evaporation or
condensation, and the location of the water table.
4.
Automatic tank gauging. Equipment for automatic tank gauging that tests for the loss of
product and conducts inventory control must meet the following requirements:
a.
The automatic product level monitor test can detect a two-tenths gallon [.76 liter] per hour
leak rate from any portion of the tank that routinely contains product;
b.
The automatic tank gauging equipment must meet the inventory control (or other test of
equivalent performance) requirements of subsection 1; and
c.
The test must be performed with the system operating in one of the following modes:
(1)
In-tank static testing conducted at least once every thirty days; or
(2)
Continuous in-tank leak detection operating on an uninterrupted basis or operating
within a process that allows the system to gather incremental measurements to
determine the leak status of the tank at least once every thirty days.
5.
Vapor monitoring. Testing or monitoring for vapors within the soil gas of the excavation zone
must meet the following requirements:
a.
The materials used as backfill are sufficiently porous (for example, gravel, sand, crushed
rock) to readily allow diffusion of vapors from releases into the excavation area;
b.
The stored regulated substance, or a tracer compound placed in the tank system, is
sufficiently volatile (for example, gasoline) to result in a vapor level that is detectable by
the monitoring devices located in the excavation zone in the event of a release from the
tank;
c.
The measurement of vapors by the monitoring device is not rendered inoperative by the
ground water, rainfall, or soil moisture or other known interferences so that a release
could go undetected for more than thirty days;
d.
The level of background contamination in the excavation zone will not interfere with the
method used to detect releases from the tank;
e.
The vapor monitors are designed and operated to detect any significant increase in
concentration above background of the regulated substance stored in the tank system, a
component or components of that substance, or a tracer compound placed in the tank
system;
f.
In the underground storage tank excavation zone, the site is assessed to ensure
compliance with the requirements in subdivisions a through d and to establish the
number and positioning of monitoring wells that will detect releases within the excavation
zone from any portion of the tank that routinely contains product; and
g.
Monitoring wells are clearly marked and secured to avoid unauthorized access and
tampering.
6.
Ground water monitoring. Testing or monitoring for liquids on the ground water must meet
the following requirements:
a.
The regulated substance stored is immiscible in water and has a specific gravity of less
than one;
b.
Ground water is never more than twenty feet [6.07 meters] from the ground surface and
the hydraulic conductivity of the soils between the underground storage tank system and
the monitoring wells or devices is not less than one one-hundredths centimeter per
second (for example, the soil should consist of gravels, coarse-to-medium sands, coarse
silts or other permeable materials);
c.
The slotted portion of the monitoring well casing must be designed to prevent migration
of natural soils or filter pack into the well and to allow entry of regulated substance on the
water table into the well under both high and low ground water conditions;
d.
Monitoring wells must be sealed from the ground surface to the top of the filter pack;
e.
Monitoring wells or devices intercept the excavation zone or are as close to it as is
technically feasible;
f.
The continuous monitoring devices or manual methods used can detect the presence of
at least one-eighth of an inch [3.05 millimeters] of free product on top of the ground water
in the monitoring wells;
g.
Within and immediately below the underground storage tank system excavation zone,
the site is assessed to ensure compliance with the requirements in subdivisions a
through e and to establish the number and positioning of monitoring wells or devices that
will detect releases from any portion of the tank that routinely contains product; and
h.
Monitoring wells are clearly marked and secured to avoid unauthorized access and
tampering.
7.
Interstitial monitoring. Interstitial monitoring between the underground storage tank system
and a secondary barrier immediately around or beneath it may be used, but only if the system
is designed, constructed, and installed to detect a leak from any portion of the tank that
routinely contains product and also meets one of the following requirements:
a.
For double-walled underground storage tank systems, the sampling or testing method
can detect a leak through the inner wall in any portion of the tank that routinely contains
product;
b.
For underground storage tank systems with a secondary barrier within the excavation
zone, the sampling or testing method used can detect a leak between the underground
storage tank system and the secondary barrier;
(1)
The secondary barrier around or beneath the underground storage tank system
consists of artificially constructed material that is sufficiently thick and impermeable
(at least 10-6 centimeter per second for the regulated substance stored) to direct a
leak to the monitoring point and permit its detection;
(2)
The barrier is compatible with the regulated substance stored so that a release from
the underground storage tank system will not cause a deterioration of the barrier
allowing a release to pass through undetected;
(3)
For cathodically protected tanks, the secondary barrier must be installed so that it
does not interfere with the proper operation of the cathodic protection system;
(4)
The ground water, soil moisture, or rainfall will not render the testing or sampling
method used inoperative so that a release could go undetected for more than thirty
days;
(5)
The site is assessed to ensure the secondary barrier is always above the ground
water and not in a twenty-five-year floodplain, unless the barrier and monitoring
designs are for use under such conditions; and
(6)
Monitoring wells are clearly marked and secured to avoid unauthorized access and
tampering.
c.
For tanks with an internally fitted liner, an automated device can detect a leak between
the inner wall of the tank and the liner, and the liner is compatible with the substance
stored.
8.
Statistical inventory reconciliation. Release detection methods based on the application of
statistical principles to inventory data similar to those described in subsection 1 must meet the
following requirements:
a.
Report a quantitative result with a calculated leak rate;
b.
Be capable of detecting a leak rate of two-tenths gallon per hour or a release of one
hundred fifty gallons within thirty days; and
c.
Use a threshold that does not exceed one-half the minimum detectible leak rate.
9.
Other methods. Any other type of release detection method, or combination of methods, can
be used if:
a.
It can detect a two-tenths gallon [.76 liter] per hour leak rate or a release of one hundred
fifty gallons [567.81 liters] within a month with a probability of detection of ninety-five
hundredths and a probability of false alarm of five one-hundredths; or
b.
The department may approve another method if the owner and operator can
demonstrate that the method can detect a release as effectively as any of the methods
allowed in subsections 3 through 8. In comparing methods, the department shall consider
the size of release the method can detect and the frequency and reliability with which it
can be detected. If the method is approved, the owner and operator must comply with
any conditions imposed by the department on its use to ensure the protection of human
health and the environment.