NDAC 33.1-24-08-34
Methods of release detection for piping
Cite as N.D. Admin. Code ยง 33.1-24-08-34
Each method of release detection for piping used to meet the requirements of subsection 2 of
section 33.1-24-08-10 and section 33.1-24-08-31 must be conducted in accordance with the following:
1.
Automatic line leak detectors. Methods which alert the operator to the presence of a leak by
restricting or shutting off the flow of regulated substances through piping or triggering an
audible or visual alarm may be used only if they detect leaks of three gallons [11.36 liters] per
hour at ten pounds per square inch line pressure within one hour. An annual test of the
operation of the leak detector must be conducted in accordance with subdivision c of
subsection 1 of section 33-24-08-30.
2.
Line tightness testing. A periodic test of piping may be conducted only if it can detect a
one-tenth gallon [.38 liter] per hour leak rate at one and one-half times the operating pressure.
3.
Applicable tank methods. Except as described in subsection 1 of section 33.1-24-08-31, any
of the methods in subsections 5 through 9 of section 33.1-24-08-33 may be used if they are
designed to detect a release from any portion of the underground piping that routinely
contains regulated substances.