OAR 918-311-0050
OAR 918-311-0050. Standards for Electrical Plans Review
A person performing electrical plan review shall do the following as a minimum:
(1) Load Calculations. Check load calculations for appropriateness, completeness and accuracy.
(2) Equipment. Check and determine if the equipment is:
(a) Suitable for the environment; and
(b) Properly sized and rated to meet the minimum code requirements.
(3) Service and Feeder. Check service and feeder installations for code compliance related to:
(a) Wiring method;
(b) Conduit and box fill;
(c) Conductor size and ampacity rating;
(d) Clearances;
(e) Locations;
(f) Accessibility; and
(g) Service grounding conductor size.