510-RICR-00-00-5. RISBC-5 Rhode Island Electrical Code (version Periodic Refile, 12/19/2001 to 07/23/2002)
RHODE ISLAND
STATE BUILDING CODE
Electrical Code
Regulation SBC-5
APRIL 1, 1998
Re-enactment of SBC-5
Dated May 1, 1997
Replaces Regulation SBC-5-94
Revised April 5, 1994
STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS
Department of Administration
BUILDING CODE STANDARDS COMMITTEE
One Capitol Hill
Providence, Rhode Island 02908-5859
(401) 222-3033
Fax No. (401) 222-2599
7th EDITION
STATEMENT OF NEED
Pursuant to the State Building Code Chapter 23, Title 27.3, the Building
Code Standards Committee has promulgated Regulation SBC-5, as
amended, dated April 1, 1998. In accordance with section 23-27.3-l09.1
paragraphs 1-4 of the Code, the Committee has the authority to adopt
appropriate rules and regulations when necessary to maintain the State
Building Code current with national model codes and standards.
STATE OF RHODE ISLAND
BUILDING CODE STANDARDS COMMITTEE
CHAIRMAN
VICE CHAIRMAN
J. Robert Wahlberg
Gordon Preiss, P.E.
Builder Heavy Construction Registered Prof. Engineer
(Mechanical)
EXECUTIVE COMMITTEE
Russell Brown
Building Official
Daniel Paquette
Builder
Donald Gagnon
Minimum Housing Inspector
Members
Frank Canario
Mark Lowenstein
Public Health Official
Representative of the Disabled
James Carlson
Frank Montanaro
Public Member
State Representative
John Cronin
Dana Newbrook
Plumber
Architect
Steve Durkee
Ronald Travers
Architect
Building Official
Thomas Lynch
Joseph Walsh
Builders Trades Council
Electrical Inspector
John Gaskell
William Lepore
Electrical Engineer
Electrical Contractor
Randall Collins
Donald Jacques
Landscape Architect
Representative of the Disabled
William Howe
Thomas Coffey
Fire Official
Legal Counsel
Richard Hanson
Joseph A. Cirillo
Public Member
State Building Commissioner
Executive Secretary
Electrical Code
Regulation SBC-5
April 1, 1998
The Building Code Standards Committee, in accordance with the rule making authority
in Title 23, Chapter 27.3, Section 109.1, paragraphs 1 through 4 inclusive of the General
Laws of Rhode Island, have formally adopted and promulgated the provisions of the
National Electrical Code, 1996 Edition, N.F.P.A. No. 70, 1996 as published by the
National Fire Protection Association, as the Code for the design and installation of all
electrical systems and data, telecommunications, video and sound installations, with
amendments thereto hereinafter set forth to the chapters and sections of said Code.
ARTICLE 90 INTRODUCTION:
The following Rhode Island amendments are made to the Sections of Article 90:
Amend Section 90-1 Purpose by adding the following paragraphs. Delete the existing
Rhode Island amendments to Sections 90-1.1, 90-4 and 90-5.
90-1.1 Purpose:
The installation of all work shall be accomplished by persons licensed by the
State of Rhode Island, Department of Labor, Division of Professional Regulation
of Electricians, Title 5, Chapter 6, and Telecommunications, Chapter 5-70 of the
General Laws of Rhode Island.
Amend section 90-4 Enforcement, to read as follows:
90.4 Enforcement:
This code is intended to be suitable for mandatory application by governmental
bodies exercising legal jurisdiction over electrical installations and for use by
insurance inspectors. The Committee and the State Building Commissioner shall
have responsibility for making interpretations of the rules and for deciding upon
the approval of equipment and materials. The authority having jurisdiction shall
have the responsibility for granting special permission contemplated in a number
of the rules. The State Building Code Standards Committee acting as the State
Board of Appeals, may waive specific requirements in this code or permit
alternative methods, where it is assured that equivalent objectives can be achieved
by establishing and maintaining effective safety.
Amend Section 90-6, Interpretations, to read as follows:
90-6
Formal Interpretations:
To promote uniformity of interpretations and application of the provisions of this
Code, the State Building Code Standards Committee has established interpretation
procedures and regulations to be implemented by the State Building
Commissioner. Part D of this Appendix is for reference purposes only and the
procedures outlined herein may be used by the Commissioner in an advisory
manner. See SBC-10, Rules and Regulations for code interpretations.
90-1
ARTICLE 110 – REQUIREMENTS FOR ELECTRICAL
INSTALLATIONS:
The following Rhode Island amendments are made to the Sections of Article 110:
Amend Section 110-16(c) Working clearance by adding a new paragraph:
110-16(c) Access and Entrance to Working space:
At least one entrance of sufficient area shall be provided to give access to
the working space about electric equipment. There shall be one entrance
not less than 24 inches (610mm) wide and 6-1/2 feet (1.98m) high.
Add a new Section 110-16(f), Working Clearance to read as follows:
110-16.(f) Door Locks
Doors on all rooms that contain electrical equipment rated over 800 amps
shall be equipped with locks. Personnel doors shall swing out and be
equipped with panic bars, pressure plates, or other devices that are
normally latched but open under simple pressure.
110-1
ARTICLE 200 – USE AND IDENTIFICATION OF GROUNDED
CONDUCTORS:
The following Rhode Island amendments are made to the Sections of Article 200:
Amend Section 200-6 (d) Grounded Conductors of Different Systems to read as
follows:
200-6 (d) Grounded Conductors of Different systems:
Where conductors of different systems are installed in the same raceway,
box, auxiliary gutter, or other types of enclosures, each grounded
conductor shall have an outer covering similar to (a) or (b) above and shall
be identified by system. Where the identification is by color, white shall
be used on systems not exceeding 150 volts to ground, and gray shall be
used for systems exceeding 150 volts to ground. When additional systems
are present, each other system grounded conductor, if required, shall have
an outer covering of white with identifiable colored stripe (not green)
running along the insulation, or other and different means of identification
as allowed by (a) or (b).
200-1
ARTICLE 210 – BRANCH CIRCUITS:
The following Rhode Island amendments are added to the Sections of Article 210:
Amend Section 210-8 (a) Ground Fault Circuit Interrupter Protection for Personnel by
adding the following exception and fine print note:
210-8. Ground-Fault Circuit-Interrupter Protection for Personnel.
(FPN): See Section 215-9 for ground-fault circuit-interrupter protection for
personnel on feeders.
(a) Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles
installed in the locations specified below shall have ground-fault circuit-
interrupter protection for personnel.
(1) Bathrooms
Exception: A single receptacle located within a dedicated space for a laundry
appliance or a duplex receptacle for two appliances which in normal use are not
easily moved from one place to another.
(FPN): See definition of receptacle in Article 100.
Amend Section 210-8(a) (3) Outdoors: by designating the existing exception as
Exception No. 1 and add a second exception as follows:
(3) Outdoors.
Exception No. 1: Receptacles that are not readily accessible and are supplied from
a dedicated branch circuit for electric snow-melting or deicing equipment as
covered in Article 426 shall be permitted to be installed without ground-fault
circuit-interrupter protection for personnel.
Exception No. 2: Ground-fault circuit-interrupter protection for personnel shall
not be required for a 125 volt. 15 or 20-ampere outdoor receptacle where the sole
purpose of the receptacle is for a wheelchair lift and the receptacle is a NEMA
L5-15R or 20R receptacle and is in addition to the receptacles required by Section
210-52(e) and is in accordance with the provisions of Section 410-57.
Retain Rhode Island section 210-52 (h), Hallways, to read as follows:
210-1
210-52(h) Hallways:
For hallways of 4 feet (1.22 m) or more in length at least one receptacle outlet shall be
required.
As used in this subsection the hall length shall be considered the length along the
centerline of the hall without passing through a doorway.
210-2
ARTICLE 220 – BRANCH-CIRCUIT, FEEDER, AND SERVICE
CALCULATIONS:
The following Rhode Island amendments are made to the sections of Article 220:
Add a new section 220-37 Optional Calculation-New Laundromats to read as follows:
220-37 Optional Calculation: New Laundromats:
Calculations of a service load or feeder, where the service or feeder serves the
total load for laundromat machines, shall be allowed to be reduced by 20% in lieu
of the requirements of Part B of this article.
The overload protection of the service-entrance conductors shall be in accordance
with Sections 230-90 and 240-3.
Feeder conductors shall not be required to be of greater ampacity than the service-
entrance conductors.
Service-entrance or feeder conductors whose demand load is determined by this
optional calculation shall be permitted to have the neutral load determined by
Section 220-22.
220-1
ARTICLE 230 – SERVICES
The following Rhode Island amendment is made to the sections of Article 230:
Amend section 230-32 by adding a last sentence to read as follows:
230-32. Protection Against Damage:
Service laterals that are not encased in concrete and that are buried 18 inches
(457mm) or more below grade shall have their location identified by a warning
ribbon placed in the trench at least 12 inches (305 mm) above the underground
installation.
230-1
ARTICLE 240 – OVERCURRENT PROTECTION
The following Rhode Island amendments are made to the sections of Article 240:
Amend section 240-21(j) Transformer Secondary Conductors of Separately Derived
Systems for Industrial Installations to read as follows:
240-21(j) Transformer Secondary Conductors of Separately Derived Systems
Conductors shall be permitted to be connected to a transformer secondary of a
separately derived system, without overcurrent protection at the connection,
where all the following conditions are met:
(1) The length of the secondary conductors does not exceed 25 ft (7.62m).
(2) The ampacity of the secondary conductors is not less than the secondary
current rating of the transformer, and the sum of the ratings of the overcurrent
devices does not exceed the ampacity of the secondary conductors. The sum of
the ratings of the overcurrent devices does not exceed 125% of the ampacity of
the transformer.
(3) All overcurrent devices are grouped.
(4) The secondary conductors are suitably protected from physical damage.
240-1
ARTICLE 250 – GROUNDING
The following Rhode Island amendments are made to the sections of Article 250:
Amend section 250-91 (a), Grounding Electrode Conductor: to read as follows:
Retain exceptions 1, 2 and 3.
250-91(a) Grounding Electrode Conductor
The material for grounding electrode conductor shall be copper only. The material
selected shall be resistant to any corrosive condition existing at the installation or shall be
suitably protected against corrosion. The conductor shall be solid or stranded, insulated,
covered or bare and shall be installed in one continuous length without a splice or joint.
Amend section 250-94 Size of Alternating-Current Grounding Electrode Conductor: by
adding a last sentence to read as follows:
250-94. Size of Alternating-Current Grounding Electrode Conductor.
The size of the grounding electrode conductor of a grounded or ungrounded ac system
shall not be less than given in Table 250-94.
Exception:
a. Where connected to made electrodes as in Section 250-83(c) or (d), that portion of
the grounding electrode conductor that is the sole connection to the grounding electrode
shall not be required to be larger than No. 6 copper wire or No. 4 aluminum wire.
b. Where connected to a concrete-encased electrode as in Section 250-81(c), that
portion of the grounding electrode conductor that is the sole connection to the grounding
electrode shall not be required to be larger than No. 4 copper wire.
c. Where connected to a ground ring as in Section 250-81(d), that portion of the
grounding electrode conductor that is the sole connection to the grounding electrode shall
not be required to be larger than the conductor used for the ground ring.
The size of the grounding electrode conductor of a grounded or ungrounded AC system
shall not be less than given in Table 250-94. In no case shall it be required to be larger
than the largest size listed in Table 250-94.
250-1
ARTICLE 300 – WIRING METHODS
Delete NEC section 300-4 Protection Against Physical Damage in its entirety:
Amend NEC section 300-4(d) Cables and Raceways Parallel to Framing Members to read
as follows:
300-4(d) Cables and Raceways Parallel to Framing Members:
In both exposed and concealed locations, where a cable or raceway type wiring
method is installed parallel to framing members, such as joists, rafters, or studs,
the cable or raceway shall be installed and supported so that the nearest outside
surface of the cable or raceway is not less than ¾ inches (31.8 mm) from the
nearest edge of the framing member where nails or screws are likely to penetrate.
Where this distance cannot be maintained, the cable or raceway shall be protected
from penetration by nails or screws by a steel plate, sleeve, or equivalent at least
1/16 inch (1.59 mm) thick.
Delete NEC section 300-7(c) in its entirety:
Amend section 300-5(j) Ground Movement by adding a new last sentence to the
paragraph and the FPN:
300-5(j) Ground Movement:
Where direct buried conductors, raceways, or cables are subject to movement by
settlement or frost, direct buried conductors, raceways or cables shall be arranged to
prevent damage to the enclosed conductors or to equipment connected to the raceways.
This section only applies to raceways that are on buildings or large permanent structures.
(FPN): This section recognizes “S” loops in underground direct burial to raceway
transitions, expansion joints in pipe risers to fixed equipment, and generally the provision
of flexible connections to equipment subject to settlement or frost heaves.
It is the intent of this article to require expansion fittings in all conduit risers
including rigid metal conduit, intermediate metal conduit and rigid nonmetallic
conduit.
Delete section 300-15(b) exception 4 and renumber exception 5, 6, 7, 8, and 9 to 4, 5, 6, 7
and 8:
300-1
ARTICLE 310 – CONDUCTORS FOR GENERAL WIRING
The following Rhode Island amendments are made to the sections of Article 310:
Amend: “Notes to Ampacity Tables of 0 to 2000 Volts” Table 310-19 by adding a sixth
exception to note 8:
NOTES TO AMPACITY TABLES OF 0 TO 2000 VOLTS:
8 Adjustment Factors:
Exception No. 6:
Derating factors shall not apply where 30 or fewer current carrying conductors occupy no
more than 20 percent of the interior cross sectional area of Underfloor Raceways, Article
354; Cellular Metal Floor Raceways, Article 356; and Cellular Concrete Floor Raceways,
Article 358.
310-1
ARTICLE 336 – NONMETALLIC – SHEATHED CABLE
The following Rhode Island amendments are made to the sections of Article 336:
Amend Section 336-18, Supports, by adding a second paragraph: Delete Rhode Island
section 336-15:
336-18 Supports:
336-18 Supports. Nonmetallic-sheathed cable shall be secured by staples,
cable ties, straps, or similar fittings so designed and installed as not to
damage the cable. Cable shall be secured in place at intervals not
exceeding 4 ½ ft (1.37m) and within 12 in. (305 mm) from every
cabinet, box, or fitting. Two conductor cables shall not be stapled on
edge. Cables run through holes in wood or metal joists, rafters, or studs
shall be considered to be supported and secured.
Where staples are used for cable sized smaller than three No. 8 AWG
conductors, they shall be of the insulated type.
Exception:
Listed non-insulated staple installed by the use of a hand operated staple
gun shall be permitted.
(FPN): See Section 370-17(c) for support where nonmetallic boxes are
used.
Delete section 336-25. In its entirety:
336-1
ARTICLE 370 – OUTLET, DEVICE, PULL AND JUNCTION BOXES,
CONDUIT BODIES AND FITTINGS:
The following Rhode Island amendment is made to the section of Article 370:
Amend section 370-27(c), Boxes at Fan Outlets, by adding a second paragraph:
(c) Boxes at Fan Outlets. Outlet boxes shall not be used as the sole
support for ceiling (paddle) fans.
In addition, in dwelling units, ceiling outlet boxes in habitable rooms,
stairways, foyers, and bathroom areas where such fans are not excluded by
Section 410-4(d), that are not used to support fans, shall be considered as
likely to support a fan. These boxes shall be listed as being suitable for
the sole support of a fan not exceeding 35 pounds (15.88kg) in weight,
with or without accessories, when all of the following conditions are met:
(1) Interior use.
The box is located in the
interior of a dwelling unit.
(2) Distance from Walls.
The box is located more than 3
feet (914mm) from any wall.
(3) Height
The box is not less than 7-1/2
feet (2.29m) above the floor.
(4) Circuits.
The box is supplied by a
general-purpose branch circuit.
Exception: Boxes listed for the application shall be permitted as the sole means
of support.
370-1
ARTICLE 384 – SWITCHBOARDS AND PANELBOARDS:
The following Rhode Island amendment is made to the section of Article 384:
Amend section 384-16 Overcurrent Protection by adding a new section 384-16(g) Field
Installed Breakers:
384-16(g) Field Installed Breakers:
Field installed circuit breakers shall only be installed in panelboards that are listed
to accept that specific breaker.
Exception:
Except as modified by the authority having jurisdiction for panelboards that are
out of manufacture.
384-1
ARTICLE 410-LIGHTING FIXTURES, LAMPHOLDERS, LAMPS, AND
RECEPTACLES:
The following Rhode Island amendments are added to the sections of Article 410:
Amend section 410-4(d) to read as follows:
410-4(d) Above Bathtubs:
No parts of cord-connected fixtures, hanging fixtures, lighting track, pendants, or
ceiling paddle fans shall be located within a zone measured 3 ft. (914mm)
horizontally and 8ft (2.44m) vertically from the top of the bathtub rim. This zone
is all encompassing and includes the zone directly over the tub.
Amend section and 410-16(c), suspended Ceilings, to read as follows and add a new
exception:
410-16(c) Means of Support:
Framing members of suspended ceiling systems used to support fixtures shall be
securely fastened to each other and shall be securely attached to the building
structure at appropriate intervals. Lay-in type lighting fixtures and surface
mounted fluorescent lighting fixtures shall be supported from the roof structure or
ceiling above and shall not depend on the suspended ceiling grid system for
support.
Exception:
Excluding fluorescent down lights.
410-1
ARTICLE 450 – TRANSFORMERS AND TRANSFORMER VAULTS:
The following Rhode Island amendment is added to the sections of Article 450:
Renumber Rhode Island 29 Section 450, Clearances for Flammable Oil Equipment
Installed Outdoors, to read as follows:
450-27 FLAMMABLE OIL EQUIPMENT INSTALLED OUTDOORS:
(1) Electrical equipment containing liquid that will burn in air, in quantities more
than 10 gallons, and installed outdoors including pad mounted transformers
shall not, except as permitted below, be located within 10 feet of:
(a) Any combustible surfaces or material on a building; or
(b) Any door or window; or
(c) Any ventilation inlet or outlet
Exception No. 1 Such new equipment installed, owned and maintained by the
public utility shall be exempt from these provisions, except when installed on
private property.
Exception No. 2 By special permission smaller spaces may be permitted where it
is judged that the particular arrangement of the installation will provide adequate
safety and there is a fire wall separation.
450-1
ARTICLE 525 CARNIVALS, CIRCUSES, FAIRS, AND SIMILAR
EVENTS:
The following Rhode Island amendment is made to the section of Article 525:
Amend section 525-18 to read as follows:
525-18 Ground-Fault Circuit-Interrupters Protection:
All 125 volt, single-phase, 15 and 20 ampere receptacle outlets shall have
ground-fault circuit-interrupter protection for personnel. For the purposes
of this section, cord sets incorporating listed ground-fault circuit-
interrupter protection for personnel shall be permitted.
525-1
ARTICLE 680 SWIMMING POOLS, FOUNTAINS, AND SIMILAR
INSTALLATIONS:
The following Rhode Island amendments are made to the sections of Article 680:
680-22(a). Bonding:
Add the following as a fifth exception to Section 680-22(a).
Exception No. 5:
Where reinforcing steel is effectively insulated by an encapsulating non-
conductive compound at the time of manufacture, it shall be permitted to
be unbounded provided No. 8 or larger bare solid copper conductors are
run in the pour around the perimeter of the pool below the normal water
line, and through the pour at other locations such that no point in the pour,
measured through the pour, is more than 15 feet (4.58m) from a bonding
conductor.
Amend section 680-22(b) common Bonding Grid by adding new item 4:
(4) A solid No. 8 or larger copper conductor installed as per 680-22(a)
680-1
ARTICLE 695 – FIRE PUMPS:
The following Rhode Island amendment is made to the section of Article 695:
Section 695-8 Exception No. 1 Amend the exception to read as follows:
695-8 Power Wiring:
Exception No. 1 Fire pump supply conductors on the load side of the
disconnecting means as permitted by Section 695-3(c). Exception No. 1,
shall be permitted to be routed through buildings using listed type MI
cable with a minimum of 2-hour fire resistance. The installation shall
comply with the restrictions provided for in the listing of such systems.
695-1
ARTICLE 700 – EMERGENCY SYSTEMS:
The following Rhode Island amendments are made to the section of Article 700:
700-9.(c) Fire Protection:
Emergency systems other than storage battery systems shall meet the following
additional requirements in hospitals, buildings exceeding three stories above
grade, buildings exceeding 75 ft (23m) in height or in any building exceeding
assembly occupancies greater than 1000 persons.
(1) Feeder-circuit wiring shall be installed either in spaces fully protected by
approved automatic fire suppression systems (sprinklers, carbon dioxide
systems, etc.) or shall be
(a) installed as per article 230-6 and terminate in a 2 hour rated room or
(b) shall be a listed electrical circuit protective system with a 2-hour fire rating
(2) Equipment for feeder circuits (including transfer switches, transformers,
panelboards, etc.) shall be either located in spaces fully protected by approved
automatic fire suppression systems (sprinklers, carbon dioxide systems, etc.)
or in spaces with a 2-hour fire resistance rating.
700-12(e) Unit Equipment:
Unit equipment shall be permanently fixed in place (i.e. not portable) and shall
have all wiring to each unit installed in accordance with the requirements of any
of the wiring methods in Chapter 3. The branch circuit feeding the unit
equipment shall be the same branch circuit as that serving the normal lighting in
the area and connected ahead of any local switches. The branch circuit feeding
unit equipment shall be clearly identified at the distribution panel. Emergency
illumination fixtures that obtain power from a unit equipment and are not part of
the unit equipment shall be wired to the unit equipment as required by Section
700-9 and by one of the wiring methods of Chapter 3.
FPN: The provision for cord and plug connection has been removed from this section.
700-1
STATE BUILDING CODE REGULATION – 1998
The following list includes all regulations promulgated by the State Building Code Standards Committee.
All regulations are available for a fee at the State Building Commission.
1.
Building Code…………………………………………SBC-1
2.
One and Two Dwelling Family
Dwelling Code………………………………………...SBC-2
3.
Plumbing Code………………………………………..SBC-3
4.
Mechanical Code……………………………………...SBC-4
5.
Electrical Code………………………………………..SBC-5
6.
Manufactured Buildings and Building Components….SBC-6
7.
ANSI A225.1
Manufactured Home
Installation Standard…………………………………..SBC-7
8.
State Energy Code…………………………………….SBC-8
9.
Enforcement and Implementation
Procedures for Projects Under
the Jurisdiction of the State
of Rhode Island……………………………………….SBC-9
10.
Code Interpretations…………………………………..SBC-10
11.
Certification of Building Officials,
Building, Electrical, Plumbing and
Mechanical Inspectors………………………………..SBC-11
12.
New Materials and Methods
of Construction……………………………………….SBC-12
13.
State Building Code
For Existing Schools………………………………….SBC-13
14.
Accessibility for Individuals with
Disabilities for Residential Use
Groups R-2 and R-3…………………………………..SBC-14
15.
Accessibility for Individuals with
Disabilities in State and Local
Government Facilities………………………………...SBC-15
16.
Accessibility for Individuals with
Disabilities…………………………………………….SBC-16
17.
Public Buildings Accessibility
Meeting Standards…………………………………….SBC-17
18.
Native Lumber………………………………………...SBC-18