510-RICR-00-00-8. RISBC-8 Rhode Island Energy Conservation Code (version Amendment, 01/01/2009 to 07/01/2010)
RHODE ISLAND
STATE BUILDING CODE
SBC-8 State Energy Conservation Code
Effective January 1, 2009
Replaces Regulation SBC-8
Dated August 1, 2008
STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS
Department of Administration
BUILDING CODE STANDARDS COMMITTEE
One Capitol Hill
Providence, Rhode Island 02908-5859
(401) 222-3033
FAX No. (401) 222-2599
10th EDITION
RISBC-8
RISBC-8
THIS PAGE LEFT INTENTIONALLY BLANK
RISBC-8
Regulation SBC-8
State Energy Conservation Code
January 1, 2009
The Building Code Standards Committee, in accordance with the rule making authority of
Title 23, Chapter 23-27.3, Section 109.1, paragraphs a through c inclusive, has formally
adopted and promulgated as the Rhode Island State Building Code, the provisions of the
International Energy Conservation Code, 2006 edition, as published by the International
Code Council, Inc. (I.C.C.), together with amendments thereto hereinafter set forth to the
articles and sections of this code:
The provisions of Title 23, Chapter 27.3 of the General Laws of Rhode Island establishing
administration and enforcement are hereby incorporated by reference. Regulatory
Administration Chapter 1 immediately follows and is supplemental to the General Laws.
Editorial Note: Code users please note:
When purchasing or using the State Energy Conservation Code 2006 code, please take note of
the particular printing edition. Errata to that printing edition is available on-line directly at no
charge at www.iccsafe.org/cs/codes/errata.html or call the office of the State Building Code
Commissioner at 401-222-3033 for further information.
Printed copies of the administrative and enforcement provisions of Title 23, Chapter 27.3 are
available at the Office of the State Building Code Commission or on-line at
www.rilim.state.ri.us/statutes/title23/23 27.3/index.htm.
The State Energy Conservation Code, 2006 Edition, is protected by the copyright that has been
issued to the ICC. As a result, the State Building Code is not available in complete form to the
public in an electronic format. The State Energy Conservation Code 2006 edition that is
referred to within is contained in a printed volume and is also in an electronic format that have
been published by the ICC under an exclusive license.
The Office of the State Building Code Commissioner has purchased volumes of these codes and
they shall be distributed to Rhode Island cities and towns during the month of June 2008 so that
local officials will have access to the code prior to the implementation of these rules on January
1, 2009.
In order to assure public access to this code the Office of the State Building Code Commissioner
shall provide a copy of this code to the Rhode Island State Library, which is located on the
second floor of the State House. In addition, all codes may be viewed during business hours at
the Department of Administration’s Library which is located on the fourth floor of the William
E. Powers Building, One Capitol Hill, Providence.
The Legislative Regulation Committee approved adoption of this code on June 19, 2008.
By:
John P. Leyden
Executive Secretary
Rhode Island Building Code Standards Committee
i
RISBC-8
THIS PAGE LEFT INTENTIONALLY BLANK
RISBC-8
STATE OF RHODE ISLAND
BUILDING CODE STANDARDS COMMITTEE
CHAIRMAN
VICE CHAIRMAN
Stephen C. Turner, PE
Public Member
Allen P. Durand
Builders Trades Council
EXECUTIVE
COMMITTEE
Robert M. Stillings
Architect
Bruce Davey, PE
Structural Engineer
John Pagliaro
Building Official
Doris Aschman
Public Health Official
William Howe
Fire Official
Bernard J. Bernard, III
Electrical Inspector
William J. Nash, Jr.
Building Official
Russell Brown
Building Official
Dana Newbrook
Architect
James R. Carlson, RA
Public Member
Michael A. Newman
Master Plumber
G. Thomas Chabot
Electrical Contractor
David F. Palmisciano
Building Trades Council
Randy Collins, Jr., RLA
Landscape Architect
Gordon W. Preiss, PE
Mechanical Engineer
Robert E. DeBlois, Jr.
Builder
Vacant
Builder
Paul DePace, PE
Representative for the Disabled
Vacant
Representative for the Disabled
James Fink, PE
Electrical Engineer
John P. Leyden, CBO
State Building Commissioner
Executive Secretary
Donald Gagnon
Minimum Housing Inspector
Thomas Coffey
Legal Counsel
ii
RISBC-8
THIS PAGE LEFT INTENTIONALLY BLANK
STATE BUILDING CODE REGULATIONS – 2007
The following list includes all regulations promulgated by the State Building Code
Standards Committee. All regulations are available for a fee at the State Building
Commission.
1.
Building Code
SBC-1-2007
2..
One and Two Family Dwelling Code
SBC-2-2007
3.
Plumbing Code
SBC-3-2007
4.
Mechanical Code
SBC-4-2007
5.
Electrical Code
SBC-5-2008
6.
Reserved
7.
Reserved
8.
Energy Conservation Code
SBC-8-2008
9
Enforcement and Implementation Procedures for
Projects Under the Jurisdiction of
The State of Rhode Island
SBC-9
10.
Code Interpretations
SBC-10
11.
Certification of Building Officials,
Building, Electrical, Plumbing and Mechanical
Inspectors
SBC-11-2002
12.
New Materials and Methods of Construction
SBC-12
13.
State Building Code for Existing Schools
SBC-13
14.
Reserved
15.
Reserved
16.
Reserved
17.
Public Buildings Accessibility Meeting Standards
SBC-17
18.
Native Lumber
SBC-18
19.
Fuel Gas Code
SBC-19-2007
iii
RISBC-8
THIS PAGE LEFT INTENTIONALLY BLANK
RISBC-8
Format: These code changes follow numbering sequence and topics of the
INTERNATIONAL ENERGY CONSERVATION CODE 2006 (first printing). All
Provisions of IECC 2006 are retained unless indicated as deleted or revised. Published
errata is available from the ICC website dependent on the printing issue number and date.
Chapter 1
ADMINISTRATION
Revise IECC section 101.1, Title, to read as follows:
101.1 Title: These regulations shall be known as the State Energy Conservation Code
Regulation SBC-8 - 2007 hereafter referred to as " this code”.
Add the following new section 101.1.1 referenced codes.
101.1.1 Referenced Codes. The other codes listed in Sections 101.4.1 through 101.4.7
and referenced elsewhere in this code shall be considered part of the requirements of this
code to the prescribed extent of each such reference.
1.
Electrical. The provisions of Rhode Island State Electrical Code SBC-5-2008
shall apply wherever referenced in this code as the ICC Electrical Code, and shall
apply to the installation of electrical systems, including alterations, repairs,
replacement, equipment, appliances, fixtures, fittings, and appurtenances thereto.
2.
Gas. The provisions of the Rhode Island State Fuel Gas Code SBC-19-2007 shall
apply wherever referenced in this code as the International Fuel Gas Code, and
shall apply to the installation of gas piping from the point of delivery, gas
appliances and related accessories as covered in this code. These requirements
apply to gas piping systems extending from the point of delivery to the inlet
connections of appliances and the installation and operation of residential and
commercial gas appliances and related accessories.
3.
Mechanical. The provisions of the Rhode Island State Mechanical Code SBC-4-
2007 shall apply wherever referenced in this code as the International Mechanical
Code and shall apply to the installation, alterations, repairs and replacement of the
mechanical systems, including equipment, appliances, fixtures, fittings and/or
appurtenances, including ventilating, heating, cooling, air-conditioning and
refrigeration systems, incinerators and other energy-related systems.
1
RISBC-8-2008
4.
Plumbing. The provisions of Rhode Island State Plumbing Code SBC-3-2007
shall apply wherever referenced in this code as the International Plumbing Code,
and shall apply to the installation, alteration, repair and replacement of plumbing
systems, including equipment, appliances, fixtures, fittings and appurtenances,
and where connected to a water or sewage system and all aspects of a medical gas
system.
5.
Property Maintenance. Refer to state or local codes.
6.
Fire Prevention Code. Wherever and whenever provisions of the Internatinal
Fire Code 2003 editions are referenced, the appropriate Rhode Island Fire Safety
Code requirements shall apply.
7.
Building Code. The provisions of the Rhode Island State Building Code SBC-1-
2007 shall apply wherever referenced in this code as the International Building
Code, and shall apply to all matters governing the design and construction of
buildings.
8.
Existing Building Code. The provisions of the State Building Codes SBC-1-
2007 in conjunction with the State Rehabilitation Code SRC-1 and the Rhode
Island Fire Safety Code shall apply wherever referenced in this code as the
International Existing Building Code.
Any and all such references to the various International Code Council family of
code shall be substituted for the appropriate state code as indicated above.
2
RISBC-8-2008
Chapter 3
Climate Zones
Delete section 301 in its entirety and substitute the following.
Section 301
Climate Zones
301.1 General Rhode Island shall be considered as climate zone 5A with the following
design conditions.
Add the following Table
Table 301.1
Exterior Design Conditions.
Value
Value
Climate zone
Providence County
All others
Winter, design dry-bulb (degree F)
0
5
Summer, design dry-bulb
87
89
Summer design wet-bulb
71
73
Degree days heating
6831
5950
Degree days cooling
371
811
3
RISBC-8-2008
Add the Following Figure
301.1
4
RISBC-8-2008
Chapter 4
401.2 Delete and substitute the following:
401.2 Compliance shall be demonstrated by either;
1. Meeting the requirements of this chapter using the criteria for climate zone
5 from figure 301.1 or.
2. Meeting the following prescriptive requirements listed as table 402.1.1 or
3. Compliance submission of Res-Check for Zone5 and Chapter4
401.3 Certificate: Add the following
A certificate similar to this shall be attached to or near the electrical panel board.
ENERGY CERTIFICATE
STREET ADDRESS: _____________________________________________
CITY/TOWN: _____________________________________________
PREDOMINANT VALUES:
R VALUE CEILING/ROOF _____________
R VALUE WALLS _____________
R VALUE FOUNDATION _____________
R VALUE DUCTS _____________
U FACTOR FENESTRATION _____________
U FACTOR SKYLIGHT _____________
AFUE VALUE BOILER/FURNACE _____________
CERTIFICATE COMPLETED BY BUILDER/REGISTERED DESIGN PROFESSIONAL
___________________________________
SIGNATURE
5
RISBC-8-2008
Delete Table 402.1.1 and substitute the following
TABLE 402.1.1
INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENT
Windowd
Area
Percentage
of Exterior
Wall Area
Fenestration
U-Factor
Skylight
U-Factor
Ceiling
R-Value
Frame
Wall
R-Value
Mass
Wall
R-Value
Floor
R-Value
Basement
Wall
R-Value
Crawl
Space
R-Value
0> 17.5
0..35
0.60
R-38
R-15 or
R13 +5a
R-13
R-19/30 b
R-10
R10/13 c
17.51>25
0.35
0.60
R-38
R-19 or
R13 +5a
R-13
R-30
R-13
R10/13 c
Footnote:
a.
“13 +5” means R-13 cavity insulation plus R-5 insulated sheathing.
b.
R-19 / 30 means R-19 at floors above occupiable ( unheated basements) areas; and R-30 above open
crawl space and garage areas.
c.
R 10 / 13 means R-10 continuous or R-13 at cavity
d. Window area is calculated using rough opening
Notes: 1.
If window area exceeds 25% of gross exterior conditioned space wall area, the
provisions of Chapter 4 prevail.
2.
R-Value 10.0 insulation shall be installed for unheated slab on grade structures
from grade to 2’ (two feet) below grade and shall be protected against physical
damage in accordance with Section R403.3.2. of Residential Code SBC-2
3.
Sliding glass doors and fully glazed patio doors shall be considered windows for
the purpose of this table
4.
Roof/ceiling assemblies in which the finished interior surface is the underside of
the roof sheathing, or where the finished ceiling surface is attached to the
underside of the roof framing member (i.e. cathedral ceilings), shall have a
minimum R-value of 30. Additionally insulation provided the exterior walls of the
structure or portion containing such conditions shall have an accompanying wall
insulation value of R-19 or better, and a glass U-factor with a maximum of 0.35.
5.
Mass walls shall meet the R-value requirements of Section 402.2.3
6.
Skylights and roof windows shall have a maximum U factor of 0.60.
401.3 Add the following 401.3.1 Certificate:
A certificate similar to this shall be attached to or near the electrical panel board.
402.1.4 Delete and substitute the following:
402.1.4 Total UA Alternative.
If the total building thermal envelope UA (sum of U-factor times the assembly area) is
less than or equal to the total UA resulting from using the U-factors in table 402.1.3
(multiplied by the same assembly area as in the proposed building) the building shall be
considered in compliance with the Table 402.1.1. The UA calculations shall be done
using an approved methodology.
Add the following section:
403.7 Minimum equipment performance. Heating and cooling equipment shall have minimum
equipment performance as indicated in Table 403.1.
6
RISBC-8-2008
TABLE 403.1
MINIMUM EQUIPMENT PERFORMANCE
EQUIPMENT
CATEGORY
SUBCATEGORY
REFERENCED
STANDARD
MINIMUM
PERFORMANCE
Air-cooled heat pumps, Heating
mode<65,000 Btu/h cooling
capacity
Split systems
Single package
ARI 210/240
8 HSPFa,b
7.6 HSPFa,b
Gas-fired or oil-fired furnace
<225,000 Btu/h
_____
DOE 10 CFR Part 430,
Subpart B, Appendix N
AFUE 85%b
Gas-fired or oil fired steam and
hot-water boilers <300,000 Btu/h
____
DOE 10 CFR Part 430,
Subpart B, Appendix N
AFUE 80%b, c
Air-cooled air conditioners and
heat pumps, Cooling mode
<65,000 Btu/h cooling capacity
Split systems
Single package
ARI 210/240
13.0 SEERb
12.0 SEERb
For SI: 1 British thermal unit per hour = 0.2931 W.
a.
For multi-capacity equipment, the minimum performance shall apply to each capacity step
provided. Multi-capacity refers to manufacturer-published ratings for more than one capacity
mode allowed by the product’s controls.
b.
This is used to be consistent with the National Appliance Energy Conservation Act (NAECA)
of 1987 (Public Law 100-12).
c.
Except for gas-fired steam boilers for which the minimum AFUE shall be 75 percent.
d.
Seasonal rating.
Delete footnotes e and f of Table 404.5.2(1) and substitute the following
e.
Tested envelope leakage shall be determined and documented by an
independent party approved by the code official.
f.
The combined air exchange rate for infiltration and mechanical ventilation
shall be determined and documented by an independent party approved by
the code official.
Add the following sections.
405
Pools. All pools shall be provided with energy conserving
measures in accordance with sections 405.1 through 405.3
Pool heaters. All pool heaters shall be equipped with a readily accessible on-off
switch to allow shutting off the heater without adjusting the thermostat setting, Pool
heaters fire by natural gas shall not have continuously burning pilot lights.
Time Switches. Time switches that can automatically turn off and on heaters and
pumps according to a preset schedule shall be installed on swimming pool heaters and
pumps.
Exception:
1. Where pumps are required to operate solar-and waste-heat- recovery pool
heating systems.
Pool covers. Heated pools shall be equipped with a vapor retardant pool covers on or
at water surface. Pools heated more than 90F (32C) shall have a pool cover with a
minimum insulation value of R-12.
Exception:
7
RISBC-8-2008
Pools deriving over 60 percent of the energy for heating from site-recovered
energy or solar energy source.
8
RISBC-8-2008
Chapter 5
501.2 Delete and substitute.
501.2 Applications. There are two independent methods of satisfying the requirements
of this Chapter. If the Prescriptive Method in Section 501.2.1 is being used, the
requirements of the Total Building Performance Method in Section 501.2.2 do not apply.
If the Performance Method in Section 501.2.2 is being used, the requirements of the
Prescriptive Method in Section 501.2.1 do not apply.
501.2.1 (Prescriptive Method) The requirements in sections 502 (Building envelope),
503 (Building mechanical systems), 504 (Service water heating), and 505 (Lighting) shall
each be satisfied.
OR
501.2.2 (Total Building Performance Method) The requirements in accordance with
Section 506 and Section 502.6 shall be satisfied.
Table 502.2 (1) Revise as shown.
Below Grade Wall
R-5 Continuous
R-7.5 Noncontinuous
Unheated Slabs
R-3 Thermal break at wall to floor joint
R-7.5 for 24 inches below
502.4.6 Revise the following exception.
2. Doors not intended to be used as building entrance doors.
Add the following exception:
7. Doors other than main entrance doors in building four stories or less.
502.6 Air Barrier
502.6.1 Air Barriers: The building envelope shall be designed and constructed
with a continuous air barrier to control air leakage into, and out of the conditioned space.
An air barrier shall also be provided for interior partitions between conditioned space and
space designed to maintain temperature or humidity levels which differ from those in the
conditioned space by more than 50% of the difference between the conditioned space and
design ambient conditions. The air barrier shall have the following characteristics:
1. It must be continuous, with all joints made air-tight.
2. It shall have an air permeability not to exceed 0.004 cfm/ft2 under a pressure
differential of 0.3 in. water.
3. It shall be capable of withstanding positive and negative combined design wind, fan
and stack pressure on the envelope without damage or displacement and shall transfer the
load to the structure. It shall not displace adjacent materials under full load.
9
RISBC-8-2008
4. The air barrier shall be joined in an air-tight and flexible manner to the air barrier
material of adjacent systems, allowing for the relative movement of systems due to
thermal and moisture variations and creep. Connection shall be made between:
a. Foundation and walls.
b. Walls and windows or doors.
c. Different wall systems
d. Wall and roof.
e. Wall and roof over unconditioned space.
f. Walls, floor and roof across construction, control and expansion joints.
g. Walls, floors and roof to utility, pipe and duct penetrations.
502.6.2 Air barrier penetrations: All penetrations of the air barrier and paths of air
infiltration/exfiltration shall be made air-tight.
503.2.1 Delete and substitute
503.2.1 Calculation of heating loads. Documented design load calculations shall
be provided by the design professional upon request of the A.H.J. Heating and
cooling loads shall be adjusted to account for load reductions that are achieved when
energy recovery systems are utilized in the HVAC system. Design loads shall be
determined by an approved equivalent computation procedure, using the design
parameters specified in chapter 3. Acceptable methods include energy modeling
software, spreadsheet calculations, or hand written calculations certified by the
design professional.
503.2.4.2 Add the following exception .
Exception: A building equipped with a DDC system may follow manufacturers
installation instructions.
503.2.4.4 Delete and substitute the following exceptions.
1.
Gravity exhaust dampers shall be permitted in buildings less than
three stories in height.
2.
Gravity dampers shall be permitted for exhaust airflows of 300 CFM
(.14 m3/s) when serving a single space.
503.2.7 Duct and plenum insulation and sealing.
Delete /and substitute.
10
RISBC-8-2008
….. a minimum of R-8 insulation when located in unconditioned spaces and with a
minimum of R-12 when located outside of the building. Exterior installations shall be
protected from the weather…….
503.2.9 Delete and substitute the following
503.2.9 HVAC System completion.
Prior to the issuance of a certificate of occupancy upon the request of the AHJ
evidence of system completion in accordance with sections 503.2.9.1 through
503.2.9.3 shall be provided.
Delete Table 503.3.1(1) and substitute the following table:
Table 503.3.1(1)
Climate Zone 5-A
Economizers on all individual cooling units
> 54,000 Btu/h
Climate Zone 5-A
On 75% of all Cooling systems when the Total
Building Load is > 12 million Btu/h
Except Use Group R
506
Delete and Substitute.
Section 506 Total Building Performance
506.1 General The proposed design complies with this section provided that the design
is in compliance with section 11 Energy Cost Budget of ASHRE 90.1 including
meeting the prescriptive requirements of Sections 5.4, 6.4, 7.4, 8.4, 9.4, and 10.4
as referenced in Chapter 11.
11
RISBC-8-2008