510-RICR-00-00-8
510-RICR-00-00-8. RISBC-8 Rhode Island Energy Conservation Code (version Amendment, 08/01/2019 to 01/04/2022)
8.1 Authority
The Building Code Standards
Committee, in accordance with the rule making authority of R.I. Gen.
Laws §§ 23-27.3-109.1(a) through (c) inclusive, has
formally adopted and promulgated as the Rhode Island State Building
Code, the provisions of the International Energy Conservation Code,
2015 edition, as published by the International Code Council, Inc.
(I.C.C.), together with amendments thereto hereinafter set forth to
the articles and sections of this code.
8.2 Incorporated Materials
A. The provisions of R.I. Gen.
Laws Chapter 23-27.3 establishing administration and enforcement are
hereby incorporated by reference. § 8.3 of this Part (Chapter 1)
immediately follows and is supplemental to the General Laws.
Editorial Note: Code users please note:
1. When
purchasing or using the International Energy Conservation Code 2015
code, please take note of the particular printing edition. Errata to
that printing edition is available on-line directly at no charge at
www.iccsafe.org/cs/codes/pages/errata.aspx
or call the office of the State Building Code Commissioner at
401-889-5550 for further information.
2. Printed
copies of the administrative and enforcement provisions of R.I. Gen.
Laws Chapter 23-27.3 are available at the Office of the State
Building Code Commission or on-line at
http://www.rilin.state.ri.us/Statutes/TITLE23/23-27.3/INDEX.HTM .
3. The
International Energy Conservation Code, 2015 Edition, is protected by
the copyright that has been issued to the ICC. As a result, the State
Building Code is not available in complete form to the public in an
electronic format. The State Energy Conservation Code 2019 edition
that is referred to within is contained in a printed volume and is
also in an electronic format that have been published by the ICC
under an exclusive license.
B. Format: These code changes
follow numbering sequence and topics of the INTERNATIONAL ENERGY
CONSERVATION CODE 2015 (first printing). All Provisions of IECC 2015
are retained unless indicated as deleted or revised. Published errata
are available from the ICC website dependent on the printing issue
number and date.
8.3 Chapter
1[CE] ADMINISTRATION
Revise IECC section C101.1,
Title, to read as follows:
C101.1 Title: This part shall
be known as the State Energy Conservation Code SBC-8-2019 hereafter
referred to as "this code”.
Add
the following new section C101.1.1 referenced codes.
C101.1.1
Referenced Codes. The other codes listed in Sections C101.4.1 through
C101.4.6 and referenced elsewhere in this code shall be considered
part of the requirements of this code to the prescribed extent of
each such reference.
(1) Electrical. The provisions
of Rhode Island State Electrical Code SBC-5-2019 ( Part
5 of this Subchapter ) shall apply wherever referenced in this
code as the ICC Electrical Code, and shall apply to the installation
of electrical systems, including alterations, repairs, replacement,
equipment, appliances, fixtures, fittings, and appurtenances thereto.
(2) Gas. The provisions of the
Rhode Island State Fuel Gas Code SBC-19-2019 ( Part
19 of this Subchapter ) shall apply wherever referenced in this
code as the International Fuel Gas Code, and shall apply to the
installation of gas piping from the point of delivery, gas appliances
and related accessories as covered in this code. These requirements
apply to gas piping systems extending from the point of delivery to
the inlet connections of appliances and the installation and
operation of residential and commercial gas appliances and related
accessories.
(3) Mechanical. The provisions
of the Rhode Island State Mechanical Code SBC-4-2019 ( Part
4 of this Subchapter ) shall apply wherever referenced in this
code as the International Mechanical Code and shall apply to the
installation, alterations, repairs and replacement of the mechanical
systems, including equipment, appliances, fixtures, fittings and/or
appurtenances, including ventilating, heating, cooling,
air-conditioning and refrigeration systems, incinerators and other
energy-related systems.
(4) Plumbing. The provisions
of Rhode Island State Plumbing Code SBC-3-2019 ( Part
3 of this Subchapter ) shall apply wherever referenced in this
code as the International Plumbing Code, and shall apply to the
installation, alteration, repair and replacement of plumbing systems,
including equipment, appliances, fixtures, fittings and
appurtenances, and where connected to a water or sewage system and
all aspects of a medical gas system.
(5) Property Maintenance. The
provisions of the Rhode Island State Property Maintenance Code
SBC-6-2019 ( Part
6 of this Subchapter ) Provides requirements for continued use and
maintenance buildings and property, and of related plumbing,
mechanical, electrical and fire protection systems in existing
residential nonresidential structures.
(6) Fire Prevention Code.
Wherever and whenever provisions of the International Fire Code 2019
editions are referenced, the appropriate Rhode Island Fire Safety
Code ( 450-RICR-00-00-1
through 10 ) requirements shall apply.
(7) Building Code. The
provisions of the Rhode Island State Building Code SBC-1-2019 ( Part
1 of this Subchapter ) shall apply wherever referenced in this
code as the International Building Code, and shall apply to all
matters governing the design and construction of buildings.
(8) Existing Building Code.
The provisions of the State Building Codes SBC-1-2019 ( Part
1 of this Subchapter ) in conjunction with the State
Rehabilitation Code SRC-1 ( Part
20 of this Subchapter ) and the Rhode Island Fire Safety Code
( 450-RICR-00-00-1
through 10 ) shall apply wherever referenced in this code as the
International Existing Building Code.
(9) Any and all such
references to the various International Code Council family of code
shall be substituted for the appropriate state code as indicated
above.
8.4 Chapter
3[CE] Climate Zones
Delete section C301 in its
entirety and substitute the following.
Section C301 Climate Zones
C301.1 General Rhode Island
shall be considered as climate zone 5 with the following design
conditions.
Table C301.1 Delete and
substitute the following:
Table 301.1
Exterior Design
Conditions.
Value
Value
Climate zone
Providence County
All others
Winter, design dry-bulb
(degree F)
0
5
Summer, design dry-bulb
87
89
Summer design wet-bulb
71
73
Degree days heating
6831
5950
Degree days cooling
371
811
Delete Figure C301.1 and
Substitute the following: Figure C301.1
Delete without substitution
section C301.2 and C301.3
Delete without substitution
Table C301.3(1)
Delete table C301.3(2) and
substitute the following
TABLE
C301.3(2)
RHODE
ISLAND CLIMATE ZONE DEFINITION
Zone Number
THERMAL CRITERIA
IP UNITS
SI UNITS
5
5400, HDD650F≤ 7200
3000 < HDD180C ≤
4000
Delete C302.1 and substitute
the following:
C302.1 Interior design
conditions. The interior design temperature used for energy load
calculations shall be a maximum of 72°F (22°C) for heating
and minimum of 75°F (24°C) for cooling.
8.5 Chapter 4[CE]
Delete C401.2 Application.
And add the following:
C401.2 Application.
Commercial buildings projects shall comply with the requirements in
sections C403 (Building Envelope Requirements), C403 (Building
Mechanical Systems), C404 (Service Water Heating), C405 (Electrical
Power and Lighting Systems) and C406 (Tenant Spaces, including
C406.1.1) in its entirety. As an alternative, commercial buildings
projects shall comply with the energy cost budget method in
ASHRAE/IESNA 90.1.
Delete without substitute
C401.2.1 Application to existing building.
Delete Table C402.1.4 and
substitute the following
TABLE
C402.1.4
OPAQUE
THERMAL ENVELOPE ASSEMBLY REQUIREMENTS
CLIMATE ZONE
5
All other
Group R
Roofs
Insulation entirely
above deck
U-0.039
U-0.039
Metal buildings
U-0.035
U-0.035
Attic and other
U-0.027
U-00021
Walls, Above Grade
Mass
U-0.078
U-0.78
Metal building
U-0.052
U-0.052
Metal framed
U-0.064
U-0.064
Wood framed and other
U-0.064
U-0.064
Walls, Below Grade
Below-grade walls
C-0.119
C-0.119
Floors
Mass
U-0.074
U-0.064
Joist/Framing
U-0.033
U-0.033
Slab-on Grade Floors
Unheated slabs
F-0.54
F-0.54
Heated slabs
F-0.58
F0.58
a. Use
opaque assembly U-factors, C-factors, and F-factors from
ANSI/ASHRAE/IESNA 90.1 Appendix A shall be permitted, provided the
construction complies with the applicable construction details from
ANSI/ASHRAE/IESNA 90.1 Appendix A.
b. When
heated slabs are placed below-grade, below grade walls must meet the
F-factor requirements for heated slabs.
Delete Table C402.1.3 and
substitute the following
TABLE C402.1.3
OPAQUE
THERMAL ENVELOPE REQUIREMENTS
CLIMATE ZONE
5
ALL OTHERS
GROUP R
Roofs
Insulation entirely
Above deck
R-25ci
R-25ci
Metal buildings (with
R-5 thermal blocks a,b )
(Assembly descriptions
can be found in ANSI/ASHRAE/IESNA Appendix A.)
(When using R-value
compliance method, a thermal spacer block shall be provided,
otherwise use the U-factor compliance method in Table C402.1.2.)
R-19 + R-11LS
R-19
R-11LS
Attic and other
R-38
R-49
Walls,
Above Grade
Mass
R-11.4ci
R-13.3 ci
Metal building c
(When using R-value compliance method, a thermal spacer block
shall be provided, otherwise use the U-factor compliance method in
Table C402.1.2.)
R-13 +
R-13ci
R-13 +
R-13ci
Metal framed
R-13 + R-7.5ci
R-13 + R-7.5ci
Wood framed and other
R-13 +
R-3.8ci or R-20
R-13 + R-7.5ci or R-20 +
R-3.8ci
Walls,
Below Grade
Below grade wall c
(R-5.7ci is allowed to
be substituted with concrete block walls complying with ASTM C 90,
un-grouted or partially grouted at 32 inches or less on center
vertically and 48 inches or less on center horizontally, with
un-grouted cores filled with materials having a maximum thermal
conductivity of 0.44 Btu-in/h-f2 F.)
R-7.5ci
R-7.5ci
Floors
Mass
R-10ci
R-12.5ci
Joist/framing
Steel/(wood)
R-30
R-30
Slab-on-Grade
Floors
Unheated Slabs
R-10 for 24” below
R-10 for 24” below
Heated slabs
R-15 for 36” below
R-15 for 36” below
Opaque doors
Swinging
U –0.37
U –0.37
Roll-up or sliding
R -4.75
R -4.75
For
SI: 1 inch = 25.4mm.
Ci
= Continuous insulation. NR = No requirement.
a. Assembly
descriptions can be found in ANSI/ASHRAE/IESNA Appendix A.
b. When
using R-value compliance method, a thermal spacer block shall be
provided, otherwise use the U-factor compliance method in Table
C402.1.2.
c. R-5.7ci
is allowed to be substituted with concrete block walls complying with
ASTM C 90, ungrouted or partially grouted at 32 inches or less on
center vertically and 48 inches or less on center horizontally, with
ungrouted cores filled with materials having a maximum thermal
conductivity of 0.44 Btu-in/h-f2 F.
d. Where
heated slabs are below grade, below-grade walls shall comply with the
exterior insulation requirements for heated slabs.
e. Steel
floor joist systems shall be insulated to R-38.
Delete Table C402.4 and
substitute the following
TABLE C402.4
BUILDING
ENVELOPE REQUIREMENTS: FENESTRATION
CLIMATE ZONE
5
Vertical
fenestration
U-factor
Fixed fenestration
0.38
Operable
fenestration 0.45
Entrance door
0.77
SHGC
SHGC
0.40
Skylights
U-factor
0.50
SHGC
0.40
Add Exception: #8
C402.5.7: Exception: #8 Where
a compliant main entrance is already required such as patio doors
intended for seasonal use.
C403.2.1 Delete and
Substitute
C403.2.1 Calculation of
heating and cooling loads. Design loads shall be determined in
accordance with the procedures described in the ANSI/ASHRAE/ACCA
Standard 183.
The
design loads shall account for the building envelope, lighting,
ventilation and occupancy loads based on the projected design.
Heating
and cooling loads shall be adjusted to account for load reductions
that are achieved when energy recovery systems are utilized in the
HVAC system.
Alternatively,
design loads shall be determined by an approved equivalent
computation procedure, using the design parameters specified in
Chapter 3.
C403.2.4.3 Delete and
substitute the following exceptions.
1. Gravity
exhaust dampers shall be permitted in buildings less than three
stories in height.
2. Gravity
dampers shall be permitted for exhaust airflows of 300 CFM (.14 m 3 /s)
when serving a single space.
C403.2.4.5 Delete and
substitute
C403.2.4.5 Snow melt system
controls. Snow and ice-melting system are allowed only when there is
no increase in supplied energy consumption above a base code
compliant level. As certified by Registered Design Professional.
Snow- and ice- melting systems, supplied through energy service to
the building, shall include automatic controls capable of shutting
off the system when the pavement temperature is above 50°F (10°C)
and no precipitation is falling and an automatic or manual control
that will allow shutoff when the outdoor temperature is above 40°F
(4°C) so that the potential for snow or ice accumulation is
negligible.
C403.2.6.1 Demand controlled
ventilation. Demand control ventilation (DCV) shall be provided for
spaces larger than 500 square feet (46.5 m2) and with an average
occupant load of 25 or more people per 1,000 square feet (93 m2) of
floor area and served by systems with one or more of the following:
TABLE C403.2.7
ENERGY RECOVERY REQUIREMENT
CLIMATE ZONE
PERCENT (%) OUTDOOR AIR
AT FULL DESIGN AIRFLOW RATE
>30% AND <40%
>40% AND <50%
>50% AND <60%
>60% AND <70%
>70% AND <80%
> 80%
DESIGN SUPPLY FAN
AIRFLOW RATE (cfm)
5
> 5500
>4500
> 3500
> 2000
> 1000
> 0
C403.2.9 Delete and
substitute
C403.2.9 Duct and plenum
insulation and sealing. All supply and return air ducts and plenums
shall be insulated with a minimum of R-8 insulation when located in
unconditioned spaces and a minimum of R-12 insulation when located
outside the building. When located within a building envelope
assembly, the duct or plenum shall be separated from the building
exterior or unconditioned or exempt spaces by a minimum of R-8
insulation.
Exceptions:
1. When
located within equipment.
2. When
the design temperature difference between the interior and exterior
of the duct or plenum does not exceed 15°F (8°C).
All
ducts, air handlers and filter boxes shall be sealed. Joints and
seams shall comply with section 603.9 of the International Mechanical
Code.
Delete Table C403.3.3.3 and
replace with the following
Table
C403.3.3.3
High-Limit
Shutoff Control Setting for Air Economizers b
Device
Type
Climate
Zone
Required
High Limit
(Economizer
Off When):
Equation
Description
Fixed dry bulb
T OA >70°F
Outdoor air temperature
exceeds 70°F
5A, 6A
Differential dry bulb
1B, 2B,
3B, 3C, 4B, 4C, 5A, 5B, 5C, 6A, 6B, 7, 8
T OA >
T RA
Outdoor air temperature
exceeds return air temperature
Fixed enthalpy with
fixed dry-bulb temperatures
All
h OA >28Btu/lb a
or
T OA >75°F
Outdoor air temperature
exceeds 28 Btu/lb of dry air a or Outdoor air
temperature exceeds 75°F
Differential enthalpy
with fixed dry-bulb temperature
All
h OA >
h RA
or
T OA >75°F
Outdoor air temperature
exceeds return air enthalpy or Outdoor air temperature exceeds
75°F
For SI: 1 foot = 305mm,
°C = (°F – 32)/1.8, 1 Btu/lb = 2.33 kJ/kg.
a. At altitudes
substantially different than sea level, the fixed enthalpy limit
shall be set to the enthalpy value at 75°F and 50-percent
relative humidity. As an example, at approximately 6,000 feet
elevation, the fixed enthalpy limit is approximately 30.7 Btu/lb.
b. Devices with
selectable setpoints shall be capable of being set to within 2°F
and 2 Btu/lb of the setpoint listed.
Deleted without substitute
Section C407
8.6 Chapter 5[CE]
Reference Standards
Delete without substitute
ASHRAE – 2012 ASHRAE
HVAC Systems and Equipment Hand Book –2012.
8.7 Chapter 1[RE]
8.7.1 ADMINISTRATION
Revise IECC section R101.1,
Title, to read as follows:
R101.1 Title: These
regulations shall be known as the State Energy Conservation Code
Regulation SBC-8-2019 hereafter referred to as "this code”.
Add the following new
section R101.1.1 referenced codes.
R101.1.1 Referenced Codes.
The other codes listed in Sections R101.4.1 through R101.4.7 and
referenced elsewhere in this code shall be considered part of the
requirements of this code to the prescribed extent of each such
reference.
(1) Electrical.
The provisions of Rhode Island State Electrical Code SBC-5-2019 ( Part
5 of this Subchapter ) shall apply wherever referenced in this
code as the ICC Electrical Code, and shall apply to the installation
of electrical systems, including alterations, repairs, replacement,
equipment, appliances, fixtures, fittings, and appurtenances thereto.
(2) Gas.
The provisions of the Rhode Island State Fuel Gas Code SBC-19-2019
( Part
19 of this Subchapter ) shall apply wherever referenced in this
code as the International Fuel Gas Code, and shall apply to the
installation of gas piping from the point of delivery, gas appliances
and related accessories as covered in this code. These requirements
apply to gas piping systems extending from the point of delivery to
the inlet connections of appliances and the installation and
operation of residential and commercial gas appliances and related
accessories.
(3) Mechanical.
The provisions of the Rhode Island State Mechanical Code SBC-4-2019
( Part
4 of this Subchapter ) shall apply wherever referenced in this
code as the International Mechanical Code and shall apply to the
installation, alterations, repairs and replacement of the mechanical
systems, including equipment, appliances, fixtures, fittings and/or
appurtenances, including ventilating, heating, cooling,
air-conditioning and refrigeration systems, incinerators and other
energy-related systems.
(4) Plumbing.
The provisions of Rhode Island State Plumbing Code SBC-3-2019 ( Part
3 of this Subchapter ) shall apply wherever referenced in this
code as the International Plumbing Code, and shall apply to the
installation, alteration, repair and replacement of plumbing systems,
including equipment, appliances, fixtures, fittings and
appurtenances, and where connected to a water or sewage system and
all aspects of a medical gas system.
(5) Property
Maintenance. The provisions of the Rhode Island State Property
Maintenance Code SBC-6-2019 ( Part
6 of this Subchapter ) Provides requirements for
continued use and maintenance buildings and property, and of related
plumbing, mechanical, electrical and fire protection systems in
existing residential nonresidential structures.
(6) Fire
Prevention Code. Wherever and whenever provisions of the
International Fire Code 2019 editions are referenced, the appropriate
Rhode Island Fire Safety Code ( 450-RICR-00-00-1
through 10 ) requirements shall apply.
(7) Building
Code. The provisions of the Rhode Island State Building Code
SBC-1-2019 ( Part
1 of this Subchapter ) shall apply wherever
referenced in this code as the International Building Code, and shall
apply to all matters governing the design and construction of
buildings.
(8) Existing
Building Code. The provisions of the State Building Codes SBC-1-2019
( Part
1 of this Subchapter ) in conjunction with the State
Rehabilitation Code SRC-1 ( Part
20 of this Subchapter ) and the Rhode Island Fire
Safety Code ( 450-RICR-00-00-1
through 10 ) shall apply wherever referenced in this
code as the International Existing Building Code.
(9) Any
and all such references to the various International Code Council
family of code shall be substituted for the appropriate state code as
indicated above.
8.8 Chapter 3[RE] Climate Zones
Delete section R301 in its
entirety and substitute the following.
Section C301 Climate Zones
R301.1 General Rhode Island
shall be considered as climate zone 5 with the following design
conditions.
Table
R301.1 Delete and substitute the following:
Table R301.1
Exterior Design
Conditions.
Value
Value
Climate zone
Providence County
All others
Winter, design dry-bulb
(degree F)
0
5
Summer, design dry-bulb
87
89
Summer design wet-bulb
71
73
Degree days heating
6831
5950
Degree days cooling
371
811
Delete without substitute
section R301.2 and R301.3
Delete Table R301.3(1) without
substitute
Delete Table R301.3(2) without
substitute
Delete Figure R301.1 and
Substitute the following: Figure R301.1
8.9 Chapter
4 [RE]
R401.2 Delete R401.2 and
substitute the following:
R401.2 Compliance Methods
Compliance shall be
demonstrated by either:
1. Meeting
the requirements of the Rhode Island Energy Conservation Code
SBC-8-2019 (this Part).
2. Meeting
the requirements of this chapter using the criteria for climate zone
5 from Figure N 1102A or table 1102.1.2.
3. Compliance
submission of Res-Check for Zone 5 & R.I. Energy Conservation
Code Residential Provisions.
Add the following to R401.3
Certificate:
Figure R401.3
A certificate similar to
this shall be attached to or near the electrical panel board
ENERGY CERTIFICATE
Street Address
City / Town
Predominant Values
R-Value Ceiling / Roof
R- Value Walls
R- Value Ducts (outside
conditioned space)
U Factor Fenestration
SHGC Fenestration
Gas Fired Un-Vented Room
Heater
Baseboard Electric
Heater
Electric Furnace
U Factor Skylight / SHGC
AFUE Value Boiler /
Furnace
Efficiency and type of
heating equipment
Efficiency and type of
cooling equipment
Efficiency and type of
service water heater
Contractor or Design
Professional
Address
Registration
Signature
Delete and substitute Table
R402.1.2
TABLE R402.1.2
INSULATION AND
FENESTRATION REQUIREMENTS BY COMPONENT a
CLIMATE ZONE
FENESTRATION
U-FACTOR b
SKYLIGHT b
U-FACTOR
GLAZED FERNESTRATION
SHGC b
CEILING
R-VALUE i
WOOD FRAME WALL R-VALUE
g
MASS WALL
R-VALUE
FLOOR
R-VALUE
BASEMENT C
WALL R-VALUE
SLAB d
R-VALUE & DEPTH
CRAWL SPACE c WALL
R-VALUE
5
0.35
0.60
NR
38
20 or
13+5 f
13/17
30 e
10/13
R-10
for 2 ft.
10/13
For SI: 1 foot = 304.8 mm.
a. R-values
are minimums U-factors and SHGC are maximums. R-19 batts compressed
into a nominal 2 × 6 framing cavity such that the R- value is
reduced by R-1 or more shall be marked with the compressed batt
R-value in addition to the full thickness R-value.
b. The
fenestration U-factor column excludes skylights. The SHGC column
applies to all glazed fenestration.
c. “10/13”
means R-10 continuous insulated sheathing on the interior or exterior
of the home or R-13 cavity insulation at the interior of the basement
wall.
d. R-5
shall be added to the entire slab and the required slab edge R-values
for heated slabs
e. Or
insulation sufficient to fill the framing cavity, R-19 minimum.
f. “13+5”
means R-13 cavity insulation plus R-5 insulated sheathing. If
structural sheathing covers 25 percent or less of the exterior,
insulating sheathing is not required where structural sheathing is
used. If structural sheathing covers more than 25 percent of
exterior, structural sheathing shall be supplemented with insulated
sheathing of at least R-2.
g. The second R-value applies
when more than half the insulation is on the interior of the mass
wall.
TABLE R402.1.4 EQUIVALENT
U-FACTORS, a
CLIMATE ZONE
FENESTRATION U-FACTOR
SKYLIGHT U-FACTOR
CEILING U-FACTOR
FRAME WALL U-FACTOR
MASS WALL U-FACTORb
FLOOR U-FACTOR
BASEMENT WALL U-FACTOR
CRAWL SPACE WALL
U-FACTOR
5
0.32
0.55
0.026
0.057
0.082
0.033
0.050
0.055
R402.1.5 Total UA
alternative Delete and substitute
R402.1.5 Total UA
alternative. If the total building thermal envelope UA (sum of
U-factor times assembly area) is less than or equal to the total UA
resulting from using the U-factors in Table R402.1.3 (multiplied by
the same assembly area as in the proposed building), the building
shall be considered in compliance with Table R402.1.1. The UA
calculation shall include the thermal bridge effects of framing
materials. The UA calculation shall include the thermal bridging
effects of framing materials. The SHGC requirements shall be met in
addition to UA compliance
R402.4.1.2 Delete and
substitute the following
R402.4.1.2 Testing. The
building or dwelling unit shall be tested, and the air leakage rate
shall be verified. Testing shall be conducted with a blower door at
a pressure of 0.2 inches (50 Pascals). Maximum air change rates per
hour: in 2019 = 8; in 2020 = 7; in 2021 = 6; and in 2022 and
subsequent years = 5. Testing shall be conducted by an approved third
party, where required by the building official. A written report of
the results of the test shall be signed by the party conducting the
test and provided to the building official. Testing shall be
performed at any time after creation of all penetrations of the
building thermal envelope.
During testing:
1. Exterior
windows and doors, fireplace and stove doors shall be closed, but not
sealed, beyond the intended weather-stripping or other infiltration
control measures;
2. Dampers
including exhaust, intake, makeup air, backdraft and flue dampers
shall be closed, but not sealed beyond intended infiltration control
measures;
3. Interior
doors, if installed at the time of the test, shall be open.
4. Exterior
doors for continuous ventilation systems and heat recovery
ventilators shall be closed and sealed;
5. Heating
and cooling systems, if installed at the time of the test, shall be
turned off; and
6. Supply
and return registers, if installed at the time of the test, shall be
fully open.
R403.3.3 Sealing (Mandatory)
Delete From sections 403.3.3
1) Post construction test
2) Rough-in test
Substitute the following:
1. Post construction test:
Total leakage shall be less than or equal to 8 cfm (113.3 L/min) per
100 square feet (9.29 m 2 ) of conditioned floor area when
tested at a pressure differential of 0.1 inches w.g. (25 Pa) across
the entire system, including the manufacturer’s air handler
enclosure. All register boots shall be taped or otherwise sealed
during the test.
2. Rough-in
test: Total leakage shall be less than or equal to 6 cfm (113.3
L/min) per 100 square feet (9.29 m 2 ) of conditioned floor
area when tested at a pressure differential of 0.1 inches w.g. (25
Pa) across the system, including the manufacturer air handler
enclosure. All registers shall be taped or otherwise sealed during
the test. If the air handler is not installed at the time of the
test, total leakage shall be less than or equal to 4 cfm (85 L/min)
per 100 square feet (9.29 m 2 ) of conditioned floor area.
Delete
R403.3.5 and substitute the following:
R403.3.5 Building cavities
(Mandatory). Interior building framing cavities shall be permitted to
be used as return ducts or plenums. (BP)
8.10 Chapter 5[RE]
Reference Standards
Delete without substitute
ASHRAE
– 2013 ASHRAE Handbook of Fundamentals.