ARSD 61:08:09:06
ARSD 61:08:09:06. Preparation of boiler for internal inspection
Cite as S.D. Admin. R. 61:08:09:06
The owner or user shall prepare a boiler for internal inspection by:
(1) Removing all handhold plates, washout plugs, and inspection plugs;
(2) Thoroughly washing the water side of the boiler;
(3) Cleaning the fire side of boiler parts, including the flues, of all loose soot and ashes; and
(4) Removing excessive scale or other deposits by chemical or mechanical means.
If a boiler has not been prepared in accordance with this section, the inspector may refuse to conduct the inspection.