1220-04-04-.43
Voltage Limits
Cite as Tenn. Comp. R. & Regs. 1220-04-04-.43
(1)
Each utility shall adopt and file with the Commission standard nominal service voltages for
each of the several areas into which its distribution system or systems may be divided.
(a)
Secondary Voltages - Delivery Point
The variations of voltage shall be no more than 7½ or below the standard voltage at
any time. Where three (3) phase service is provided, the utility shall exercise
reasonable care to assure that the phase voltages are in balance.
(b)
Primary Voltages - Delivery Point
The variations of voltage shall be no more than five percent (5%) above or below the
standard voltage at that time.
(c)
Limitations
Limitations in subparagraphs (c) and (d) above do not apply to special contracts in
which the customer specifically agrees to accept service with unregulated voltage.
(d)
Exceptions to Voltage Requirements:
Voltage outside the limits specified will not be considered a violation when the
variations
1.
Arise from the action of the elements.
2.
Are infrequent fluctuations not exceeding five (5) minutes duration.
3.
Arise from service interruptions.
4.
Arise from temporary separation of parts of the system from the main system.
5.
Are from causes beyond the control of the utility.