1220-04-04-.44
Voltage Surveys And Records
Cite as Tenn. Comp. R. & Regs. 1220-04-04-.44
(1)
Voltage measurements shall be made at the utility’s service terminals. For single-phase
service, the measurement shall be made between the grounded conductor and the
REGULATIONS FOR ELECTRIC COMPANIES
CHAPTER 1220-04-04
ungrounded conductors. For three (3) phase service, the measurement shall be made
between the phase wires.
(2)
Each utility shall make a sufficient number of voltage measurements, using recording
voltmeters, in order to determine if voltages are in compliance with the requirements as
stated in Rule 1220-04-04-.43.
(3)
All voltmeter records obtained under this Rule 1220-04-04-.44(2) shall be retained by the
utility for at least one (1) year and shall be available for inspection by the Commission’s
representatives. Notations on each chart shall indicate the following:
(a)
The location where the voltage was taken.
(b)
The time and date of the test.
(c)
The results of the comparison with an indicating voltmeter.