WAC 51-11C-403328. Table C403.3.2(8) — Electrically operated variable refrigerant flow air conditioners — Minimum efficiency requirements
Table C403.3.2(8)
Electrically Operated Variable Refrigerant Flow Air Conditioners — Minimum Efficiency Requirements b
Equipment Type Size Category Heating Section Type Subcategory or Rating Condition Minimum Efficiency Test Procedure a < 65,000 Btu/h All VRF Multi-Split System 13.0 SEER VRF Air Conditioners, Air Cooled ≥ 65,000 Btu/h and < 135,000 Btu/h Electric Resistance (or none) VRF Multi-Split System 11.2 EER 15.5 IEER AHRI 1230 ≥ 135,000 Btu/h and < 240,000 Btu/h Electric Resistance (or none) VRF Multi-Split System 11.0 EER 14.9 IEER ≥ 240,000 Btu/h Electric Resistance (or none) VRF Multi-Split System 10.0 EER 13.9 IEER
Equipment Type
Size Category
Heating Section Type
Subcategory or Rating Condition
Minimum Efficiency
Test Procedure a
< 65,000 Btu/h
All
VRF Multi-Split System
13.0 SEER
VRF Air Conditioners, Air Cooled
≥ 65,000 Btu/h and
< 135,000 Btu/h
Electric Resistance
(or none)
VRF Multi-Split System
11.2 EER
15.5 IEER
AHRI 1230
≥ 135,000 Btu/h and
< 240,000 Btu/h
Electric Resistance
(or none)
VRF Multi-Split System
11.0 EER
14.9 IEER
≥ 240,000 Btu/h
Electric Resistance
(or none)
VRF Multi-Split System
10.0 EER
13.9 IEER
For SI: 1 British thermal unit per hour = 0.2931 W.
a
Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
b
This table is a replica of ASHRAE 90.1 Table 6.8.1-8 Electrically Operated Variable-Refrigerant-Flow Air Conditioners — Minimum Efficiency Requirements.