32 Ill. Adm. Code 346.270
Fire Protection
Section 346.270 Fire Protection
a) The
radiation room at a panoramic irradiator shall have heat and smoke detectors.
The detectors shall activate an audible alarm. The alarm shall be capable of
alerting personnel prepared to summon assistance promptly. The sources shall
automatically become fully shielded if a fire is detected.
b) The
radiation room at a panoramic irradiator shall be equipped with a fire
extinguishing system capable of extinguishing a fire without the entry of personnel
into the room. The system for the radiation room shall have a shut-off valve
to control flooding into unrestricted areas.
c) For
fire suppression systems using an extinguishing gas, the radiation room
ventilation system shall automatically shut down when the suppression system is
activated.