35 Ill. Adm. Code 370.420
Suction-Lift Pump Stations
Section 370
Section 370.420 Suction-Lift
Pump Stations
a) Pump Priming and Lift Requirements
Suction lift pumps shall be of the self-priming or
vacuum-priming type and shall meet the applicable requirements of Section
370.132. Suction lift pump stations using dynamic suction lifts exceeding the
limits outlined in the following sections may be approved upon submission of
factory certification of pump performance and detail calculations indicating
satisfactory performance under the proposed operating conditions. Such
detailed calculations must include static suction lift as measured from
"lead pump off" elevation to center line of pump suction, friction
and other hydraulic losses of the suction piping, vapor pressure of the liquid,
altitude correction, required net positive suction head, and a safety factor of
at least 6 feet.
1) Self-priming Pumps
Self-priming pumps shall be capable of rapid priming and
repriming at the "lead pump on" elevation. Such self-priming and
repriming shall be accomplished automatically under design operating
conditions. Suction piping should not exceed the size of the pump suction and
shall not exceed 25 feet in total length. Priming lift at the "lead pump
on" elevation shall include a safety factor of at least 4 feet from the
maximum allowable priming lift for the specific equipment at design operating conditions.
The combined total of dynamic suction lift at the "pump off"
elevation and required net positive suction head at design operating conditions
shall not exceed 22 feet.
2) Vacuum-priming Pumps.
Vacuum-priming pump stations shall be equipped with dual vacuum
pumps capable of automatically and completely removing air from the suction
lift pump. The vacuum pumps shall be adequately protected from damage due to
sewage. The combined total of dynamic suction lift at the "pump off"
elevation and required net positive suction head at design operating conditions
shall not exceed 22 feet.
b) Equipment, Wet Well Access and Valve Location
The pump equipment compartment shall be above grade or offset
and shall be effectively isolated from the wet well to prevent the humid and
corrosive sewer atmosphere from entering the equipment compartment. Wet well
access shall not be through the equipment compartment. Wet well access may not
be through the equipment compartment and shall be at least 24 inches in diameter.
Gasketed replacements shall be provided to cover the opening to the wet well
for pump units removed for servicing. Valves shall not be located in the wet
well.