35 Ill. Adm. Code 370.430
Submersible Pump Stations - Special Considerations
Section 370
Section 370.430 Submersible
Pump Stations - Special Considerations
Submersible pump stations shall
meet the applicable requirements under Section 370.132, except as modified in
this Section.
a) Construction
Submersible pumps and motors shall be designed specifically
for raw sewage use, including totally submerged operation during a portion of
each pumping cycle, and shall meet the requirements of the National Electrical
Code (1996). An effective method to detect shaft seal failure or potential
seal failure shall be provided.
b) Pump Removal
Submersible pumps shall be readily removable and replaceable
without dewatering the wet well or disconnecting any piping in the wet well.
c) Electrical
1) Power Supply and Control
Electrical supply, control and alarm circuits shall be
designed to provide strain relief and to allow disconnection from outside the
wet well. Terminals and connectors shall be protected from corrosion by
location outside the wet well or through use of watertight seals. If located
outside, weatherproof equipment shall be used.
2) Controls
The motor control center shall be located outside the wet
well, readily accessible, and be protected by conduit seal or other appropriate
measures meeting the requirements of the National Electrical Code, to prevent
the atmosphere of the wet well from gaining access to the control center. The
seal shall be so located that the motor may be removed and electrically
disconnected without disturbing the seal.
3) Power Cord
Pump motor power cords shall be designed for flexibility and
serviceability under conditions of extra hard usage and shall meet the
requirements of the National Electric Code (1996) for flexible cords in sewage
pump stations. Ground fault interruption protection shall be used to
de-energize the circuit in the event of any failure in the electrical integrity
of the cable. Power cord terminal fittings shall be corrosion-resistant and
constructed in a manner to prevent the entry of moisture into the cable, shall
be provided with strain relief appurtenances, and shall be designed to
facilitate field connecting.
d) Valves
Valves required under Section 370.132(e) shall be located in
a separate valve pit. Provision shall be made to remove accumulated water from
the valve pit. Accumulated water in valve pits deeper than 4 feet shall be
pumped to the wet well or gravity drained to the ground surface. Valve pits 4
feet deep or less may be gravity drained to the wet well through a trapped and
vented drain that meets the applicable requirements found in 77 Ill. Adm. Code
890, "Illinois Plumbing Code". Such pits shall have entrances that
fully expose the pit to the atmosphere. Check valves that are integral to the
pump need not be located in a separate valve pit provided that the valve can be
removed from the wet well in accordance with subsection (b) above. Provision
shall be made for the use of portable ventiliation equipment during periods of
maintenance.