35 Ill. Adm. Code 370.840
Aerobic Sludge Digestion
Section 370
Section 370.840 Aerobic
Sludge Digestion
a) General
The aerobic sludge digestion system shall include provisions
for digestion, supernatant separation, sludge concentration and any necessary
sludge storage. These may be accomplished with separate tanks or processes or
in digestion tanks.
b) Multiple Units
Multiple digestion units capable of independent operation are
recommended for all plants and shall be provided in those plants where the
design average flow exceeds 100,000 gallons per day. Plants without multiple
units shall provide alternate sludge handling and disposal methods.
c) Tank Capacity
1) The following digestion tank capacities are based on a solids
concentration of 2 percent with supernatant separation performed in a separate
tank. If supernatant separation is performed in the digestion tank, a minimum
of 25 percent additional volume is required. These capacities shall be
provided unless sludge thickening facilities (refer to Section 370.820) are
utilized to thicken the feed solids concentration to greater than 2 percent.
If such. thickening is provided, the digestion volumes may be decreased
proportionally.
(ft.(3)/Population
Sludge Source
Equivalent (P.E.))
Waste activated sludge-no
primary settling
4.5*
Primary plus waste activated
sludge
.0*
Waste activated sludge
exclusive of primary sludge
.0*
Extended aeration activated
sludge
.0
Primary plus fixed film
reactor sludges
.0
*These volumes apply to waste activated sludge from single
stage nitrification facilities with less than 24 hours detention time based on
design average flow.
2) These volumes are based on digester temperatures of 59~ F
(15~ C) and a solids retention time of 27 days. Aerobic digesters shall be
covered to minimize heat loss or these volumes shall be increased for colder
temperature applications. Refer to subsection (g) below for necessary sludge
storage. Additional volume may be required if the land application disposal
method is used in order to meet applicable Federal regulations.
d) Mixing
Aerobic digesters shall be equipped with devices which can
maintain solids in suspension and which provide complete mixing of the digester
contents.
e) Air Requirements
Sufficient air shall be provided to keep the solids in
suspension and maintain dissolved oxygen between 1 and 2 milligrams per liter
(mg/l). For minimum mixing and oxygen requirements, an air supply of 30 cfm
per 1000 cubic feet of tank volume shall be provided with the largest blower
out of service. If diffusers are used, the nonclog type is recommended, and
they should be designed to permit continuity of service. If mechanical turbine
aerators are utilized, at least two turbine aerators per tank shall be provided
to permit continuity of service. Mechanical aerators are not acceptable for use
in aerobic digesters due to freezing conditions experienced throughout
Illinois.
f) Supernatant Separation and Scum and Grease Removal
1) Supernatant Separation
Facilities shall be provided for effective separation or
decanting of supernatant. Separate facilities are recommended; however,
supernatant separation may be accomplished in the digestion tank if additional
volume is provided, in accordance with subsection (c) above. The supernatant
drawoff unit shall be designed to prevent the recycle of scum and grease back
to plant process units. Provision should be made to withdraw supernatant from
multiple levels of the supernatant withdrawl zone.
2) Scum and Grease Removal
Facilities shall be provided for the effective collection of
scum and grease for final disposal and to prevent recycle back to plant process
units and prevent long term accumulation and potential for discharge of scum
and grease in the effluent.
g) High Level Emergency Overflow
An unvalved high level overflow and any necessary piping
shall be provided to return digester overflow back to the head of the plant or
to the aeration process in case of accidental overfilling. The design of the
overflow shall take into account the length of time and rate at which sludge is
wasted during periods when the treatment plant is unattended, potential effects
of overflow on plant process units, location of the discharge from the emergency
overflow, and the potential for discharge of suspended solids in the plant
effluent.
h) Digested Sludge Storage Volume
1) Sludge storage must be provided in accordance with Section
370.870 to accommodate daily sludge production volumes and as an operational
buffer for unit outage and adverse weather conditions. Designs utilizing
increased sludge age in the activated sludge system as a means of storage are
not acceptable.
2) Liquid sludge storage capacity shall be based on the following
values unless digested sludge thickening facilities are utilized (refer to
Section 370.173) to provide solids concentrations to greater than 2 percent.
Sludge Source
Volume (ft.(3)/P.E./day)