77 Ill. Adm. Code 890.350
Unions
Section 890
Section 890.350Â Unions
Unions may be used in the
drainage and venting system when accessibly located above ground. Unions shall
be installed in a water supply system within 5 feet of regulating equipment,
water heaters, water conditioning tanks, water conditioning equipment, pumps,
and similar equipment which may require service by removal or replacement.Â
Where small equipment may be unscrewed, only one union shall be required.
a)        Drainage System. Unions may be used in the trap seal and on
the inlet and outlet side of the trap. Unions shall have metal to metal seats
except that plastic unions may have plastic to plastic seats.
b)        Water Supply System. Unions in the water supply system shall
be metal to metal with ground seats, except that plastic to metal unions may
utilize durable, non-toxic, impervious gaskets. Unions between copper
pipe/tubing and dissimilar metals shall either be made with a brass converter
fitting or be a dielectric type union.