77 Ill. Adm. Code 905.125
Pumps, Pumping/Dosing Chambers, and Ancillary Equipment
Section 905
Section 905.125Â Pumps,
Pumping/Dosing Chambers, and Ancillary Equipment
a)Â Â Â Â Â Â Â Â Pumps shall meet the following requirements:
1)Â Â Â Â Â Â Â Â The pump shall be submersible.
2)Â Â Â Â Â Â Â Â The pump shall be designed to handle wastewater and a minimum
of ½- inch diameter solids.
3)Â Â Â Â Â Â Â Â The pump shall be capable of delivering the required flow at
the design total dynamic head. The discharge pipe shall be the same size or
larger than the discharge of the pump.
4)Â Â Â Â Â Â Â Â The pump shall be constructed of corrosion-resistant
materials.
5)Â Â Â Â Â Â Â Â Performance curves and specification sheets indicating that the
criteria of this subsection (a) have been met shall be submitted with the plan
review application when pumps are to be used in a system.
b)Â Â Â Â Â Â Â Â Pumping Chambers
1)Â Â Â Â Â Â Â Â The pumping chamber shall be watertight, meaning that all
joints shall be sealed. The pumping chamber shall be filled with water after
being installed and backfilled to prevent the pumping chamber from floating out
of position because of hydrostatic pressures, unless the tank is installed in
dry soil.
2)Â Â Â Â Â Â Â Â The volume of the pumping chamber shall be sufficient to
provide the desired dosing volume, space for controls, space for setting the
pump, reserve capacity malfunction and flow-back after the pump shuts off
(volume of manifold and laterals).
3)        A reserve capacity above the active pumping volume equal to ½
day's design flow shall be provided if single pumps are used. A reserve volume
is not needed if siphons or dual pumps are used.
4)Â Â Â Â Â Â Â Â An access riser shall extend at least 6 inches above the
ground surface.
5)Â Â Â Â Â Â Â Â The dosing volume shall be at least 5 times the pipe volume of
the dosing network and provide for filling and drainback of the network. The
average flow shall be used to determine the dosing volume.
6)Â Â Â Â Â Â Â Â The pump control device shall be adjustable so that the
required dosing volume is discharged during each pumping cycle. The control
system for the pumping chamber shall consist of a control for operating the
pump and an alarm system to detect when the system is malfunctioning. Pump
controls shall allow flexibility in adjusting the on-off depth. An example of
acceptable controls is shown in Appendix A, Illustration Q.
7)Â Â Â Â Â Â Â Â A high water alarm shall be provided with audible and visual
signals and a test function. The alarm shall be on a separate circuit. The
alarm control device shall be a sealed float or diaphragm switch and shall be
located to activate 2 to 3 inches above the pump turn-on level or siphon
activation level. After January 1, 2014, all electrical devices for new and
repaired private sewage disposal systems shall comply with Section 905.20(k).
c)Â Â Â Â Â Â Â Â Ancillary Equipment
1)Â Â Â Â Â Â Â Â A quick disconnect device shall be included in the discharge
piping to facilitate removal of the pump for inspection, repair or
replacement. The disconnect device shall be a threaded union, pitless adapter
or lift-out rail system.
2)Â Â Â Â Â Â Â Â A corrosion-resistant rope or cable of adequate strength shall
be affixed to the pump to facilitate installation and removal so that personnel
need not enter the chamber to disconnect the pump.
3)Â Â Â Â Â Â Â Â A pump control device shall be adjustable so that the desired
dosing volume can be discharged during each pumping cycle. The control device
may consist of one or more sealed float or diaphragm switches that may
cooperate with a relay or contact. Separate control panels located outside the
chamber shall be protected from the weather and shall provide no air path
between the panel and the pumping chamber.
4)Â Â Â Â Â Â Â Â A check valve between the pump and the piping network shall
not be allowed unless this piping system is below the frost line.