8 Ill. Adm. Code 255.80
Secondary Containment
Section 255
Section 255.80 Secondary
Containment
a) All agrichemical non-mobile storage containers for liquid
pesticides and liquid fertilizer shall be located within a secondary
containment structure.
b) Secondary containment structures and systems shall provide the
following capacity:
1) When not protected from receiving precipitation, the
containment shall have a minimum containment volume of a 6-inch rain storm (a
25 year, 24 hour rain), plus the capacity of the largest tank, and the volume
displaced by the bases of the other tanks located within the secondary
containment structure.
2) When protected from receiving precipitation, the containment
shall have a minimum containment volume of 100% of the capacity of the largest
tank, plus the volume displaced by the bases of the other tanks located within
the secondary containment structure.
c) Structural materials and integrity shall provide secondary
containment that meets or exceeds the requirement of this Section. Materials
shall be compatible with the agrichemical to be contained.
1) General requirements include:
A) Clay, natural soil clay mixtures or clay/bentonite mixtures
shall not be used to contain any bulk pesticide.
B) Secondary containment for liquid agrichemicals storage at
facility sites should provide for separation between bulk pesticides and bulk
fertilizer to the extent that a common wall or curbing between the fertilizer
area and the pesticide area shall provide for the interception and recovery
including clean up of pesticide spills while the entire secondary containment
area shall meet or exceed the total capacity requirement specified in this
Section.
C) The secondary containment structure shall be constructed to a
water permeability rate of not greater than 1 x 10
-6
centimeters per
second and maintained so that liquid movement through the walls and base does
not exceed a rate of 1 x 10
-5
centimeters per second permeability
rate. The secondary containment structure shall be designed and maintained to
withstand a full hydrostatic head of any contained liquid. The containment
area shall not be equipped with a permanent pump unless the pump has only a
manual mode of operation.
D) The secondary containment structure shall not have a discharge
outlet or gravity drain through the wall or floor.
E) Synthetic materials or liners may be used with secondary
containment structures provided they are compatible with agrichemicals being
contained and it is installed according to manufacturer's written direction and
repaired and maintained according to manufacturer's recommendations. These
directions and recommendations shall become records maintained at the facility
site.
2) Walls: The walls of secondary containment structures shall
meet each of the following criteria:
A) Walls shall be constructed of materials, including but not
limited to, steel, reinforced concrete, solid masonry, or compatible synthetic
materials or synthetic liners as authorized in this Section.
B) No piping shall be installed through the wall except for
interconnections between multiple secondary containment structures authorized
in this Section.
C) Multiple basins connected to provide the containment capacity as
set forth in this Section shall be connected in a manner that assures an
unrestricted transfer of discharged liquid between basins.
D) Earthen walls used for secondary containment of fertilizer
shall be protected against erosion (e.g., sodding and seeding). Side slopes
shall not exceed a 3 to 1 ratio of horizontal to vertical. The top width of
earthen walls shall not be less than 2½ feet.
E) Provisions shall be made for safe and emergency access and exit
to and from the secondary containment structures.
3) Floor: The base of a secondary containment structure shall be
lined with materials, including but not limited to, reinforced concrete, steel,
or compatible synthetic liner or synthetic materials as authorized in this
Section, and the floor shall meet each of the following criteria:
A) Floors shall be constructed to allow the safe and expeditious
removal of precipitation water and any spilled liquid in a manner that does not
disrupt the ability of the containment structure to prevent the movement of
liquid as required in this Section (e.g., sloped to a collection sump well).
B) Liners used for secondary containment of fertilizer may be
constructed of suitable soil or of soil treated with bentonite clay or other
comparable material, with a minimum depth of 12 inches provided the other floor
requirements as stated in this Section are met. The liner shall be covered by
a soil or smooth aggregate layer not less than 6 inches thick and shall be
maintained to prevent cracking or puncture.
4) Prefabricated facilities: A prefabricated secondary
containment structure shall be composed of a rigid prefabricated basin having
both a base and walls constructed of steel, reinforced concrete or synthetic
liner or synthetic materials which are resistant to corrosion, puncture, or
cracking. A written confirmation of compatibility and a written estimate of
life expectancy from the basin manufacturer shall be kept on file at the
facility. Multiple basins connected to provide the capacity required in this
Section shall be connected in a manner which assures an unrestricted transfer
of discharged liquid between basins.
5) Drainage and basin facility: A drainage and basin facility
diverts uncontaminated storm water drainage and provides secondary containment
in accordance with this Section. The curb, base and drainage path shall be at
least 12 inches thick and shall be constructed in lifts not to exceed 6 inches
in thickness. Persons wishing to use a drainage and basin facility should
consider the overall facility plan, topography, subsoil type, water table
location, and surface water drainage patterns.
d) Facilities with mini-bulk containers filled and warehoused for
product distribution shall:
1) Provide warehousing area secondary containment structures or
systems equal in volume to the largest container stored; or
2) Provide a current immediate response action plan for leakage
or spillage and maintain necessary supplies and equipment to effect containment
recovery and residue clean-up, in order to be in compliance with secondary
containment provisions of this Part.