675 IAC 15-2-102
675 IAC 15-2-102 Outdoor fixtures, outlets, and appliances
Cite as Ind. Admin. Code tit. 675, r. 15-2-102
Sec. 102. (a) Outdoor fixtures and equipment shall be approved for outdoor use. Outdoor receptacles or convenience outlets shall be of
a gasketed-cover type, for use in wet locations.
(b) Outside Heating and/or Air-Conditioning Equipment. A mobile structure provided with a branch circuit designed to energize heating
and/or air-conditioning equipment located outside and mobile structure, other than room air-conditioners, shall have branch-circuit conductors
terminate in a listed outlet box, or disconnecting means, located on the otside [sic.] of the mobile structure. A label shall be permanently
affixed adjacent to the outlet box and contain the following information:
"This connection is for heating and/or air-conditioning equipment. The branch-circuit is rated at not more than _____ amperes, at
_____ volts, 60-Hertz, _____ conductor ampacity. A disconnecting means shall be located within sight of the equipment.
The correct voltage and ampere rating shall be given. The tag shall be not less than 0.020 inch, etched brass, stainless steel, anodized or
alcald aluminum or equivalent. The tag shall not be less than three inches (3") by one and three-fourths inches (1 3/4") minimum size.