675 IAC 15-2-57
675 IAC 15-2-57 Wet-vented drainage system
Cite as Ind. Admin. Code tit. 675, r. 15-2-57
Sec. 57. (a) A common vent may be used for two (2) fixtures set on the same floor level but connecting at different levels in the stack,
provided the vertical drain is one pipe diameter larger than the upper fixture drain but in no case smaller than the lower fixture drain, whichever is
the larger.
(b) Length of Trap Arm. Fixture traps shall be located within the distance given in Table 2B, in 675 IAC 15-2-62. Not more
than one (1) trap shall connect to a trap arm.