10 CSR 26-2.040
General Requirements for Release Detection for All In-Use Underground Storage Tank Systems
PURPOSE: This rule outlines the minimum
requirements for leak and spill detection systems.
(1) Owners and operators of underground
storage tank (UST) systems that are in-use
must use a method, or combination of methods, of release detection that—
(A) Can detect a release from any portion
of the tank and the connected underground
piping that routinely contains a regulated substance, except remote fills and gravity piping;
(B) Is installed, calibrated, operated, tested, and maintained in accordance with the
manufacturer’s instructions, including routine
maintenance and service checks for operability or running condition. If manufacturer’s
operability test procedures are not available,
the annual operability test may be conducted
in accordance with a code of practice developed by a nationally recognized association
or independent testing laboratory or a method
approved by the department. Operability test
reports must, at a minimum, include facility
name and address, components tested, model
and serial number (if legible), testing date,
test method, technician name and affiliation,
and a certification of results;
(C) The first operability test is due not
later than January 1, 2020 or immediately
upon installation if installed after July 1,
2017. Electronic and mechanical release
detection equipment must be tested annually
for proper operation, in accordance with subsection (B) of this section. A test of the proper operation must be performed at least annually and, at a minimum and as applicable to
the facility, cover the following components
and criteria:
1. Automatic tank gauge and other controllers: test alarm; verify system configuration; test battery backup unless records are
electronically stored at a remote location;
2. Probes and sensors: inspect for residual buildup; ensure floats move freely; ensure
shaft is not damaged; ensure cables are free
of kinks, bends, and breaks; test alarm operability and communication with controller;
and
3. Vacuum pumps and pressure gauges:
ensure proper communication with sensors
and controller;
(D) Meets the performance requirements
for tanks in 10 CSR 26-2.043 or 10 CSR 262.046 for field-constructed tanks, or for piping in 10 CSR 25-2.044 or 10 CSR 26-2.047
for bulk piping, with any performance claims
and their manner of determination described
in writing by the equipment manufacturer or
installer. In addition, all release detection
methods must be capable of detecting the leak
rate or quantity specified for the method in 10
CSR 26-2.043, 10 CSR 26-2.044, 10 CSR
26-2.046, or 10 CSR 26-2.047, as appropriate, with a probability of detection of ninetyfive percent (95%) and a probability of false
alarm of five percent (5%); and
(E) All release detection methods and
equipment must be conducted and operated in
accordance with the applicable National Work
Group on Leak Detection Evaluations listing,
unless otherwise approved by the department.
To obtain copies of equipment listings, contact
the National Work Group on Leak Detection
Evaluations, www.nwglde.org.
(2) When a release detection method for
tanks in 10 CSR 26-2.043 or 10 CSR 262.046 or for piping in 10 CSR 26-2.044 or 10
CSR 26-2.047 indicates a release may have
occurred, owners and operators must notify
the department in accordance with 10 CSR
26-2.050–10 CSR 26-2.053.
AUTHORITY: sections 319.105, 319.107,
319.111, and 319.137, RSMo 2016.* This rule
originally filed as 10 CSR 20-10.040.
Original rule filed April 2, 1990, effective
Sept. 28, 1990. Amended: Filed Aug. 3,
1993, effective April 9, 1994. Moved and
amended: Filed April 15, 2011, effective Dec.
30, 2011. Amended: Filed Aug. 15, 2016,
effective May 30, 2017.