10 CSR 26-2.042
Requirements for Hazardous Substance Underground Storage Tank Systems
PURPOSE: This rule outlines the standards
for leak detection on hazardous substance
underground storage tanks.
(1) Owners and operators of in-use hazardous
substance underground storage tank (UST)
systems must use a release detection method
that meets the requirements of 10 CSR 262.041 and 10 CSR 26-2.043 subsection
(1)(H), except for the electronic monitoring
requirement in 10 CSR 26-2.043 paragraph
(1)(H)2. with approval from the department.
(2) In addition, all in-use hazardous substance USTs must meet the following requirements:
(A) Secondary containment systems must
be designed, constructed, and installed to—
1. Contain regulated substances released
from the tank system until they are detected
and removed;
2. Prevent the release of regulated substances to the environment at any time during
the operational life of the UST system; and
3. Be checked for evidence of a release
at least every thirty (30) days;
(B) Double-walled tanks must be designed,
constructed, and installed to—
1. Contain a release from any portion of
the inner tank within the outer wall; and
2. Detect the failure of the inner wall;
(C) External liners (including vaults) must
be designed, constructed, and installed to—
1. Contain one hundred percent (100%)
of the capacity of the largest tank within its
boundary;
2. Prevent the interference of precipitation or groundwater intrusion with the ability
to contain or detect a release of regulated
substances; and
3. Surround the tank completely (that is,
it is capable of preventing lateral as well as
vertical migration of regulated substances);
(D) Underground piping must be equipped
with secondary containment that satisfies the
requirements of subsection (2)(A) of this rule
(for example, trench liners, jacketing of double-walled pipe). In addition, underground
piping that conveys regulated substances
under pressure must be equipped with an
automatic line leak detector in 10 CSR 262.044(1)(A); and
(E) Other methods of release detection
may be used if owners and operators—
1. Demonstrate to the department that
an alternative method can detect a release of
the stored substance as effectively as any of
the methods allowed in 10 CSR 262.043(1)(B)–(I) can detect a release of
petroleum;
2. Provide information to the department on effective corrective action technologies, health risks, and chemical and physical
properties of the stored substance and the
characteristics of the UST site; and
3. Obtain approval from the department
to use the alternate release detection method
before the installation and operation of the
new UST system.
(3) All new or replaced hazardous substance
UST systems installed after July 1, 2017,
must also comply with the containment sump
testing requirements in 10 CSR 26-2.035.
AUTHORITY: sections 319.105, 319.107, and
319.137, RSMo 2016.* This rule originally
filed as 10 CSR 20-10.042. Original rule filed
April 2, 1990, effective Sept. 28, 1990.
Moved and amended: Filed April 15, 2011,
effective Dec. 30, 2011. Amended: Filed Aug.
15, 2016, effective May 30, 2017.
*Original authority: 319.105, RSMo 1989; 319.107, RSMo
1989, amended 1994; and 319.137, RSMo 1989, amended
1993, 1995, 2004.