10 CSR 60-4.052
Source Water Monitoring and Enhanced Treatment Requirements
PURPOSE: This rule establishes source
water monitoring requirements and enhanced
treatment for Cryptosporidium for surface
water systems and systems under the direct
influence of surface water.
These requirements are in addition to requirements for filtration and disinfection in 10 CSR 60-4.050
and 10 CSR 60-4.055. This rule adopts the
requirements found in subpart W of 40 CFR
part 141.
(1) Enhanced Treatment for Cryptosporidium
General Requirements.
(A) The requirements of this rule are
national primary drinking water regulations.
The regulations in this rule establish or
extend treatment technique requirements in
lieu of maximum contaminant levels for
Cryptosporidium. These requirements are in
addition to requirements for filtration and
disinfection in 10 CSR 60-4.050 and 10 CSR
60-4.055.
(B) Applicability.
1. The requirements of this rule apply to
all public water systems supplied by a surface
water source and public water systems supplied by a ground water source under the
direct influence of surface water.
2. Wholesale systems, as defined in 10
CSR 60-2.015, must comply with the
requirements of this rule based on the population of the largest system in the combined
distribution system.
(C) Requirements. Systems subject to this
rule must comply with the following requirements:
1. Systems must conduct an initial and a
second round of source water monitoring for
each plant that treats a surface water or
ground water under the direct influence of
surface water (GWUDISW) source. This
monitoring may include sampling for
Cryptosporidium, E. coli, and turbidity as
described in sections (2)–(6) of this rule, to
determine what level, if any, of additional
Cryptosporidium treatment they must provide;
2. Systems that plan to make a significant change to their disinfection practice
must develop disinfection profiles and calculate disinfection benchmarks, as described in
sections (8) and (9) of this rule;
3. Filtered systems must determine their
Cryptosporidium treatment bin classification
as described in section (10) of this rule and
provide
additional
treatment
for
Cryptosporidium, if required, as described in
section (11) of this rule. Filtered systems must
implement
Cryptosporidium
treatment
according to the schedule in section (12) of
this rule;
4. Systems required to provide additional treatment for Cryptosporidium must implement microbial toolbox options that are
designed and operated as described in sections (13)–(18) of this rule; and
5. Systems must comply with the applicable record-keeping and reporting requirements described in 10 CSR 60-7.010 and 10
CSR 60-9.010.
(2) Source Water Monitoring Requirements.
(A) Initial Round of Source Water Monitoring. Systems must conduct the following
monitoring on the schedule in subsection
(2)(C) of this rule unless they meet the monitoring exemption criteria in subsection
(2)(D) of this rule.
1. Filtered systems serving at least ten
thousand (10,000) people must sample their
source water for Cryptosporidium, E. coli,
and turbidity at least monthly for twenty-four
(24) months.
2. Filtered systems serving fewer than
ten thousand (10,000) people must sample
their source water for E. coli at least once
every two (2) weeks for twelve (12) months.
3. A filtered system serving fewer than
ten thousand (10,000) people may avoid E.
coli monitoring if the system notifies the
department that it will monitor for
Cryptosporidium as described in paragraph
(2)(A)4. of this rule. The system must notify
the department no later than three (3) months
prior to the date the system is otherwise
required to start E. coli monitoring under
subsection (2)(C) of this rule.
4. Filtered systems serving fewer than
ten thousand (10,000) people must sample
their source water for Cryptosporidium at
least twice per month for twelve (12) months
or at least monthly for twenty-four (24)
months if they meet one (1) of the following,
based on monitoring conducted under paragraphs (2)(A)2. and 3. of this rule.
A. For systems using lake or reservoir
sources, the annual mean E. coli concentration is greater than 10 E. coli/100 mL.
B. For systems using flowing stream
sources, the annual mean E. coli concentration is greater than 50 E. coli/100 mL.
C. The system does not conduct E.
coli monitoring as described in paragraphs
(2)(A)2. and 3. of this rule.
D. Systems using ground water under
the direct influence of surface water
(GWUDISW) must comply with the requirements of paragraph (2)(A)4. of this rule
based on the E. coli level that applies to the
nearest surface water body. If no surface
water body is nearby, the system must comply based on the requirements that apply to
systems using lake/reservoir sources.
5. For filtered systems serving fewer
than ten thousand (10,000) people, the
department may approve monitoring for an
indicator other than E. coli under paragraph
(2)(A)2. of this rule. The department also
may approve an alternative to the E. coli concentration in subparagraph (2)(A)4.A., B., or
D. of this rule to trigger Cryptosporidium
monitoring. This approval by the department
must be provided to the system in writing and
must include the basis for the department’s
determination that the alternative indicator
and/or trigger level will provide a more accurate identification of whether a system will
exceed the Bin 1 Cryptosporidium level in
section (10) of this rule.
6. Systems may sample more frequently
than required under this section if the sampling frequency is evenly spaced throughout
the monitoring period.
(B) Second Round of Source Water Monitoring. Systems must conduct a second round
of source water monitoring that meets the
requirements for monitoring parameters, frequency, and duration described in subsection
(2)(A) of this rule, unless they meet the monitoring exemption criteria in subsection
(2)(D) of this rule. Systems must conduct this
monitoring on the schedule in subsection
(2)(C) of this rule.
(C) Monitoring Schedule. Systems must
begin the monitoring required in subsection
(2)(A) and subsection (2)(B) of this rule no
later than the month beginning with the date
listed in this table—
(D) Monitoring Avoidance.
1. Filtered systems are not required to
conduct source water monitoring under this
rule if the system will provide a total of at
least
5.5-log
of
treatment
for
Cryptosporidium, equivalent to meeting the
treatment requirements of Bin 4 in section
(11) of this rule.
2. If a system chooses to provide the
level of treatment in paragraph (2)(D)1. of
this rule as applicable, rather than start
source water monitoring, the system must
notify the department in writing no later than
the date the system is otherwise required to
submit a sampling schedule for monitoring
under section (3) of this rule. Alternatively,
a system may choose to stop sampling at any
point after it has initiated monitoring if it
notifies the department in writing that it will
provide this level of treatment. Systems must
install and operate technologies to provide
this level of treatment by the applicable treatment compliance date in section (12) of this
rule.
(E) Plants Operating Only Part of the Year.
Systems with plants that operate for only part
of the year must conduct source water monitoring in accordance with this rule, but with
the following modifications:
1. Systems must sample their source
water only during the months that the plant
operates unless the department specifies
another monitoring period based on plant
operating practices; and
2. Systems with plants that operate less
than six (6) months per year and that monitor
for Cryptosporidium must collect at least six
(6) Cryptosporidium samples per year during
each of two (2) years of monitoring. Samples
must be evenly spaced throughout the period
the plant operates.
(F) New Source Requirements.
1. A system that begins using a new
source of surface water or GWUDISW after
the system is required to begin monitoring
under subsection (2)(C) of this rule must
monitor the new source on a schedule the
department approves. Source water monitoring must meet the requirements of this rule.
The system must also meet the bin classification and Cryptosporidium treatment requirements of sections (10) and (11) of this rule, as
applicable, for the new source on a schedule
the department approves.
2. The requirements of subsection (2)(F)
of this rule apply to surface water systems
and ground water under the direct influence
of surface water systems that begin operation
after the monitoring start date applicable to
the system’s size under subsection (2)(C) of
this rule.
3. The system must begin a second
round of source water monitoring no later
than six (6) years following initial bin classification under section (10) of this rule.
(G) Failure to collect any source water
sample required under this section in accordance with the sampling schedule, sampling
location, analytical method, approved laboratory, and reporting requirements of sections
(3) through (6) of this rule is a monitoring
violation.
(H) Grandfathering Monitoring Data.
Systems may use (i.e., may “grandfather”)
monitoring data collected prior to the applicable monitoring start date in subsection
(2)(C) to meet the initial source water monitoring requirements in subsection (2)(A) of
this rule. Grandfathered data may substitute
for an equivalent number of months at the
end of the monitoring period. All data submitted under subsection (2)(H) must meet the
requirements in section (7) of this rule.
(3) Sampling Schedules.
(A) Systems required to conduct source
water monitoring under section (2) of this
rule must submit a sampling schedule that
specifies the calendar dates when the system
will collect each required sample.
1. Systems must submit sampling schedules no later than three (3) months prior to
the applicable date listed in subsection (2)(C)
of this rule for each round of required monitoring.
2. Systems serving at least ten thousand
(10,000) people must submit their sampling
schedule for the initial round of source water
monitoring under subsection (2)(A) of this
rule to the Environmental Protection Agency
(EPA) electronically at the web address specified by the EPA for this purpose. If a system
is unable to submit the sampling schedule
electronically, the system may use an alternative approach for submitting the sampling
schedule that the EPA approves.
3. Systems serving fewer than ten thousand (10,000) people must submit their sampling schedules for the initial round of source
water monitoring in subsection (2)(A) of this
rule to the department.
4. Systems must submit sampling schedules for the second round of source water
monitoring in subsection (2)(B) of this rule to
the department.
5. If the EPA or the department does not
respond to a system regarding its sampling
schedule, the system must sample at the
reported schedule.
(B) Systems must collect samples within
two (2) days before or two (2) days after the
dates indicated in their sampling schedule
(that is, within a five (5)-day period around
the schedule date) unless one (1) of the conditions of paragraph (3)(B)1. or 2. applies.
1. If an extreme condition or situation
exists that may pose danger to the sample collector, or that cannot be avoided and causes
the system to be unable to sample in the
Systems that serve:
Must begin the first round of
source water monitoring no later
than the month beginning:
And must begin the second round
of source water monitoring no
later than the month beginning:
At least 100,000 people
October 1, 2006
April 1, 2015
From 50,000 to 99,999
April 1, 2007
October 1, 2015
From 10,000 to 49,999
April 1, 2008
October 1, 2016
Fewer than 10,000 and monitor
for E. coli
October 1, 2008
October 1, 2017
Fewer than 10,000 and monitor
for Cryptosporidium (Applies to
filtered systems that meet the
conditions of paragraph (2)(A)3.
of this rule.)
April 1, 2010
April 1, 2019
Source Water Monitoring Starting Dates Table
scheduled five (5)-day period, the system
must sample as close to the scheduled date as
is feasible unless the department approves an
alternative sampling date. The system must
submit an explanation for the delayed sampling date to the department concurrent with
the shipment of the sample to the laboratory.
2. If a system is unable to report a valid
analytical result for a scheduled sampling
date due to equipment failure, loss of or damage to the sample, failure to comply with the
analytical method requirements, including the
quality control requirements in 10 CSR 605.010, or the failure of an approved laboratory to analyze the sample, then the system
must collect a replacement sample. The system must collect the replacement sample not
later than twenty-one (21) days after receiving
information that an analytical result cannot be
reported for the scheduled date unless the
system demonstrates that collecting a replacement sample within this time frame is not
feasible or the department approves an alternative resampling date. The system must submit an explanation for the delayed sampling
date to the department concurrent with the
shipment of the sample to the laboratory.
(C) Systems that fail to meet the criteria of
subsection (3)(B) of this rule for any source
water sample required under section (2) of
this rule must revise their sampling schedules
to add dates for collecting all missed samples.
Systems must submit the revised schedule to
the department for approval prior to when the
system begins collecting the missed samples.
(4) Sampling Locations.
(A) Systems required to conduct source
water monitoring under section (2) of this
rule must collect samples for each plant that
treats a surface water or GWUDISW source.
Where multiple plants draw water from the
same influent, such as the same pipe or
intake, the department may approve one (1)
set of monitoring results to be used to satisfy
the requirements of section (2) of this rule for
all plants.
(B) Systems must collect source water
samples prior to chemical treatment, such as
coagulants, oxidants, and disinfectants,
unless the system meets the condition of paragraph (4)(B)1. of this rule.
1. The department may approve a system
to collect a source water sample after chemical treatment. To grant this approval, the
department must determine that collecting a
sample prior to chemical treatment is not
feasible for the system and that the chemical
treatment is unlikely to have a significant
adverse effect on the analysis of the sample.
(C) Systems that recycle filter backwash
water must collect source water samples prior
to the point of filter backwash water addition.
(D) Bank Filtration Requirements.
1. Systems that receive Cryptosporidium
treatment credit for bank filtration under 10
CSR 60-4.050(2)(F) as applicable, must collect source water samples in the surface water
prior to bank filtration.
2. Systems that use bank filtration as
pretreatment to a filtration plant must collect
source water samples from the well (i.e.,
after bank filtration). Use of bank filtration
during monitoring must be consistent with
routine operational practice. Systems collecting samples after a bank filtration process
may not receive treatment credit for the bank
filtration under subsection (15)(C) of this
rule.
(E) Multiple Sources. Systems with plants
that use multiple water sources, including
multiple surface water sources and blended
surface water and ground water sources, must
collect samples as specified in paragraph
(4)(E)1. or 2. of this rule. The use of multiple sources during monitoring must be consistent with routine operational practice.
1. If a sampling tap is available where
the sources are combined prior to treatment,
systems must collect samples from the tap.
2. If a sampling tap where the sources
are combined prior to treatment is not available, systems must collect samples at each
source near the intake on the same day and
must follow either subparagraph (4)(E)2.A.
or B. of this rule for sample analysis.
A. Systems may take composite samples from each source into one (1) sample
prior to analysis. The volume of sample from
each source must be weighted according to
the proportion of the source in the total plant
flow at the time the sample is collected.
B. Systems may analyze samples from
each source separately and calculate a
weighted average of the analysis results for
each sampling date. The weighted average
must be calculated by multiplying the analysis result for each source by the fraction the
source contributed to total plant flow at the
time the sample was collected and then summing these values.
(F) Additional Requirements. Systems must
submit a description of their sampling location(s) to the department at the same time as
the sampling schedule required under section
(3) of this rule. This description must address
the position of the sampling location in relation to the system’s water source(s) and treatment processes, including pretreatment, points
of chemical treatment, and filter backwash
recycle. If the department does not respond to
a system regarding sampling location(s), the
system must sample at the reported
location(s).
(5) Approved Laboratories.
(A) Cryptosporidium. Systems must have
Cryptosporidium samples analyzed by a laboratory that is approved under the EPA’s
Laboratory Quality Assurance Evaluation
Program for Analysis of Cryptosporidium in
Water or a laboratory that has been certified
for Cryptosporidium analysis by an equivalent
state laboratory certification program.
(B) E. Coli. Any laboratory certified by the
EPA, the National Environmental Laboratory
Accreditation Conference, or the department
for total coliform or fecal coliform analysis
under 10 CSR 60-5.010(3) is approved for E.
coli analysis under this rule when the laboratory uses the same technique for E. coli that
the laboratory uses for 10 CSR 60-5.010(3).
(C) Turbidity. Measurements of turbidity
must be made by a party approved by the
department.
(6) Reporting Source Water Monitoring
Results.
(A) Systems must report results from the
source water monitoring required under section (2) of this rule no later than ten (10) days
after the end of the first month following the
month when the sample is collected.
(B) All systems serving at least ten thousand (10,000) people must report the results
from the initial source water monitoring
required under subsection (2)(A) of this rule
to the EPA electronically at the web address
specified by the EPA for this purpose. If a
system is unable to report monitoring results
electronically, the system may use an alternative approach for reporting monitoring results
that the EPA approves.
(C) Systems serving fewer than ten thousand (10,000) people must report results from
the initial source water monitoring required
under subsection (2)(A) of this rule to the
department.
(D) All systems must report results from
the second round of source water monitoring
required under subsection (2)(B) of this rule
to the department.
(E) Systems must report the following
applicable information for the source water
monitoring required under section (2) of this
rule:
1. For each Cryptosporidium analysis—
A. Systems must report the following
data elements:
(I) Public water system (PWS) ID;
(II) Facility ID;
(III) Sample collection date;
(IV) Sample type (field or matrix
spike);
(V) Sample volume filtered (L), to
nearest;
(VI) Was one hundred percent
(100%) of filtered volume examined; and
(VII) Number of oocysts counted;
B. For matrix spike samples, systems
must also report the sample volume spiked
and estimated number of oocysts spiked.
These data are not required for field samples;
C. For samples in which less than ten
(10) L is filtered or less than one hundred
percent (100%) of the sample volume is
examined, systems must also report the number of filters used and the packed pellet volume; and
D. For samples in which less than one
hundred percent (100%) of sample volume is
examined, systems must also report the volume of resuspended concentrate and volume
of this resuspension processed through
immunomagnetic separation; and
2. For each E. coli analysis, systems
must report the following data elements:
A. PWS ID;
B. Facility ID;
C. Sample collection date;
D. Analytical method number;
E. Method type;
F. Source type (flowing stream,
lake/reservoir, GWUDISW);
G. E. coli/100 mL; and
H. Turbidity. (Systems serving fewer
than ten thousand (10,000) people that are not
required to monitor for turbidity under section (2) of this rule are not required to report
turbidity with their E. coli results.)
(7) Grandfathering Previously Collected
Data.
(A) Systems may use previously collected
data to comply with the initial source water
monitoring requirements of subsection (2)(A)
by grandfathering sample results that were
collected before the system is required to
begin monitoring. To be grandfathered, the
sample results and analysis must meet the criteria in this section and must be approved by
the department. A filtered system may grandfather Cryptosporidium samples to meet the
requirements of subsection (2)(A) when the
system does not have corresponding E. coli
and turbidity samples. A system that grandfathers Cryptosporidium samples without E.
coli and turbidity samples is not required to
collect E. coli and turbidity samples when the
system completes the requirements for
Cryptosporidium monitoring under subsection (2)(A).
(B) E. Coli Sample Analysis. The analysis
of E. coli samples must meet the analytical
method and approved laboratory requirements of 10 CSR 60-5.010(3) and section (5)
of this rule.
(C) Cryptosporidium Sample Analysis.
The analysis of Cryptosporidium samples
must meet the criteria in this subsection.
1. Laboratories must have analyzed
Cryptosporidium samples using one (1) of
these analytical methods:
A. Method 1623: Cryptosporidium
and Giardia in Water by Filtration/IMS/FA,
2005, United States Environmental Protection Agency, EPA–815–R–05–002;
B. Method 1622: Cryptosporidium in
Water by Filtration/IMS/FA, 2005, United
States Environmental Protection Agency,
EPA–815–R–05–001;
C. Method 1623: Cryptosporidium
and Giardia in Water by Filtration/IMS/FA,
2001, United States Environmental Protection Agency, EPA–821–R–01–025;
D. Method 1622: Cryptosporidium in
Water by Filtration/IMS/FA, 2001, United
States Environmental Protection Agency,
EPA–821–R–01–026;
E. Method 1623: Cryptosporidium
and Giardia in Water by Filtration/IMS/FA,
1999, United States Environmental Protection Agency, EPA–821–R–99–006; and
F. Method 1622: Cryptosporidium in
Water by Filtration/IMS/FA, 1999, United
States Environmental Protection Agency,
EPA–821–R–99–001.
2. For each Cryptosporidium sample,
the laboratory analyzed at least ten (10) L of
sample or at least two (2) mL of packed pellet or as much volume as could be filtered by
two (2) filters that EPA approved for the
methods listed in paragraph (7)(C)1.
(D) Sampling Location. The sampling
location must meet the conditions in section
(4) of this rule.
(E) Sampling Frequency. Cryptosporidium
samples were collected no less frequently
than each calendar month on a regular schedule, beginning no earlier than January 1999.
Sample collection intervals may vary for the
conditions specified in paragraphs (3)(B)1.
and 2. of this rule if the system provides documentation of the condition when reporting
monitoring results.
1. The department may approve grandfathering of previously collected data where
there are time gaps in the sampling frequency if the system conducts additional monitoring the department specifies to ensure that the
data used to comply with the initial source
water monitoring requirements of subsection
(2)(A) of this rule are seasonally representative and unbiased.
2. Systems may grandfather previously
collected data where the sampling frequency
varied
within
each
month.
If
the
Cryptosporidium sampling frequency varied,
systems must follow the monthly averaging
procedure in paragraph (10)(B)5. of this rule,
as applicable, when calculating the bin classification for filtered systems.
(F) Reporting Monitoring Results for
Grandfathering. Systems that request to
grandfather previously collected monitoring
results must report the following information
by the applicable dates listed in this subsection. Systems serving at least ten thousand
(10,000) people must report this information
to the EPA unless the department approves
reporting to the department rather than the
EPA. Systems serving fewer than ten thousand (10,000) people must report this information to the department.
1. Systems must report that they intend
to submit previously collected monitoring
results for grandfathering. This report must
specify the number of previously collected
results the system will submit, the dates of
the first and last sample, and whether a system will conduct additional source water
monitoring to meet the requirements of subsection (2)(A) of this rule. Systems must
report this information no later than the date
the sampling schedule under section (3) of
this rule is required.
2. Systems must report previously collected monitoring results for grandfathering,
along with the associated documentation listed in the following subparagraphs no later
than two (2) months after the applicable date
listed in subsection (2)(C) of this rule:
A. For each sample result, systems
must report the applicable data elements in
section (6) of this rule;
B. Systems must certify that the
reported monitoring results include all results
the system generated during the time period
beginning with the first reported result and
ending with the final reported result. This
applies to samples that were collected from
the sampling location specified for source
water monitoring under this rule, not spiked,
and analyzed using the laboratory’s routine
process for the analytical methods listed in
this section;
C. Systems must certify that the samples were representative of a plant’s source
water(s) and the source water(s) have not
changed. Systems must report a description
of the sampling location(s), which must
address the position of the sampling location
in relation to the system’s water source(s) and
treatment processes, including points of
chemical addition and filter backwash recycle; and
D. For Cryptosporidium samples, the
laboratory or laboratories that analyzed the
samples must provide a letter certifying that
the quality control criteria specified in the
methods listed in paragraph (7)(C)1. were
met for each sample batch associated with the
reported results. Alternatively, the laboratory
may provide bench sheets and sample examination report forms for each field, matrix
spike, Initial Precision and Recovery (IPR),
Ongoing Precision and Recovery (OPR), and
method blank sample associated with the
reported results.
(G) If the department determines that a
previously collected data set submitted for
grandfathering was generated during source
water conditions that were not normal for the
system, such as a drought, the department
may disapprove the data. Alternatively, the
department may approve the previously collected data if the system reports additional
source water monitoring data, as determined
by the department, to ensure that the data set
used under section (10) of this rule represents
average source water conditions for the system.
(H) If a system submits previously collected data that fully meet the number of samples
required for initial source water monitoring
under subsection (2)(A) of this rule and some
of the data are rejected due to not meeting the
requirements of this section, systems must
conduct additional monitoring to replace
rejected data on a schedule the department
approves. Systems are not required to begin
this additional monitoring until two (2)
months after notification that data have been
rejected and additional monitoring is necessary.
(8) Disinfection Profiling and Benchmarking
Requirements.
(A) Following the completion of initial
source water monitoring, a system that plans
to make a significant change to its disinfection practice, as defined in this section, must
develop disinfection profiles and calculate
disinfection benchmarks for Giardia lamblia
and viruses as described in section (9) of this
rule. Prior to changing the disinfection practice, the system must notify the department
and must include in this notice the following
information:
1. A completed disinfection profile and
disinfection benchmark for Giardia lamblia
and viruses as described in section (9) of this
rule;
2. A description of the proposed change
in disinfection practice; and
3. An analysis of how the proposed
change will affect the current level of disinfection.
(B) Significant changes to disinfection
practice are defined as follows:
1. Changes to the point of disinfection;
2. Changes to the disinfectant(s) used in
the treatment plant;
3. Changes to the disinfection process;
or
4. Any other modification identified by
the department as a significant change to disinfection practice.
(9) Developing the Disinfection Profile and
Benchmark.
(A) Systems required to develop disinfection profiles under section (8) of this rule
must follow the requirements of this section.
Systems must monitor at least weekly for a
period of twelve (12) consecutive months to
determine the total log inactivation for
Giardia lamblia and viruses. If systems monitor more frequently, the monitoring frequency must be evenly spaced. Systems that operate for fewer than twelve (12) months per
year must monitor weekly during the period
of operation. Systems must determine log
inactivation for Giardia lamblia through the
entire plant, based on CT99.9 values in the
Guidance Manual for Surface Water System
Treatment Requirements, January 1992, as
applicable. Systems must determine log inactivation for viruses through the entire treatment plant based on a protocol approved by
the department.
(B) Systems with a single point of disinfectant application prior to the entrance to the
distribution system must conduct the monitoring specified here. Systems with more than
one (1) point of disinfectant application must
conduct this monitoring for each disinfection
segment. Systems must monitor the parameters necessary to determine the total inactivation ratio, using analytical methods in 10
CSR 60- 5.010.
1. For systems using a disinfectant other
than ultraviolet light (UV), the temperature of
the disinfected water must be measured at
each residual disinfectant concentration sampling point during peak hourly flow or at an
alternative location approved by the department.
2. For systems using chlorine, the pH of
the disinfected water must be measured at
each chlorine residual disinfectant concentration sampling point during peak hourly flow
or at an alternative location approved by the
department.
3. The disinfectant contact time(s), (t),
must be determined during peak hourly flow.
4. The residual disinfectant concentration(s), (C), of the water before or at the first
customer and prior to each additional point of
disinfectant application must be measured
during peak hourly flow.
(C) In lieu of conducting new monitoring
under subsection (9)(B), systems may elect to
meet the requirements of paragraph (9)(C)1.
or 2.
1. Systems that have at least one (1) year
of existing data that are substantially equivalent to data collected under the provisions of
subsection (9)(B) may use these data to develop disinfection profiles as specified in this
section if the system has neither made a significant change to its treatment practice nor
changed sources since the data were collected. Systems may develop disinfection profiles
using up to three (3) years of existing data.
2. Systems may use disinfection profile(s) developed under 10 CSR 604.055(6)(C) in lieu of developing a new profile if the system has neither made a significant change to its treatment practice nor
changed sources since the profile was developed. Systems that have not developed a
virus profile under 10 CSR 60-4.055(6)(C)
must develop a virus profile using the same
monitoring data on which the Giardia lamblia profile is based.
(D) Systems must calculate the total inactivation ratio for Giardia lamblia as specified
here.
1. Systems using only one (1) point of
disinfectant application may determine the
total inactivation ratio for the disinfection
segment based on either of the methods in
subparagraph (9)(D)1.A. or B.
A. Determine one (1) inactivation
ratio (CTcalc/CT99.9) before or at the first
customer during peak hourly flow.
B. Determine successive CTcalc/
CT99.9 values, representing sequential inactivation ratios, between the point of disinfectant application and a point before or at the
first customer during peak hourly flow. The
system must calculate the total inactivation
ratio by determining (CTcalc/CT99.9) for each
sequence and then adding the (CTcalc/
CT99.9) values together to determine (
(CTcalc/CT99.9)).
2. Systems using more than one (1)
point of disinfectant application before the
first customer must determine the CT value
of each disinfection segment immediately
prior to the next point of disinfectant application, or for the final segment, before or at the
first customer, during peak hourly flow. The
(CTcalc/CT99.9) value of each segment and (
(CTcalc/CT99.9)) must be calculated using the
method in subparagraph (9)(D)1.A. of this
section.
3. The system must determine the total
logs of inactivation by multiplying the value
calculated in paragraph (9)(D)1. or 2. by
three (3).
4. Systems must calculate the log of
inactivation for viruses using a protocol
approved by the department.
(E) Systems must use the procedures specified in paragraphs (9)(E)1. and 2. to calculate a disinfection benchmark.
1. For each year of profiling data collected and calculated under subsections
(9)(A)–(D) of this rule, systems must determine the lowest mean monthly level of both
Giardia lamblia and virus inactivation.
Systems must determine the mean Giardia
lamblia and virus inactivation for each calendar month for each year of profiling data by
dividing the sum of daily or weekly Giardia
lamblia and virus log inactivation by the
number of values calculated for that month.
2. The disinfection benchmark is the
lowest monthly mean value (for systems with
one (1) year of profiling data) or the mean of
the lowest monthly mean values (for systems
with more than one (1) year of profiling data)
of Giardia lamblia and virus log inactivation
in each year of profiling data.
(10) Bin Classification for Filtered Systems.
(A) Following completion of the initial
round of source water monitoring required
under subsection (2)(A) of this rule, filtered
systems
must
calculate
an
initial
Cryptosporidium bin concentration for each
plant for which monitoring was required.
Calculation of the bin concentration must use
the Cryptosporidium results reported under
subsection (2)(A) of this rule and must follow
the procedures in subsection (10)(B) of this
rule.
(B) Procedures for Bin Determination.
1. For systems that collect a total of at
least forty-eight (48) samples, the bin concentration is equal to the arithmetic mean of
all sample concentrations.
2. For systems that collect a total of at
least twenty-four (24) samples, but not more
than forty-seven (47) samples, the bin concentration is equal to the highest arithmetic
mean of all sample concentrations in any
twelve (12) consecutive months during which
Cryptosporidium samples were collected.
3. For systems that serve fewer than ten
thousand (10,000) people and monitor for
Cryptosporidium for only one (1) year (that
is, collect twenty-four (24) samples in twelve
(12) months), the bin concentration is equal
to the arithmetic mean of all sample concentrations.
4. For systems with plants operating
only part of the year that monitor fewer than
twelve (12) months per year under subsection
(2)(E) of this rule, the bin concentration is
equal to the highest arithmetic mean of all
sample concentrations during any year of
Cryptosporidium monitoring.
5. If the monthly Cryptosporidium sampling frequency varies, systems must first calculate a monthly average for each month of
monitoring. Systems must then use these
monthly average concentrations, rather than
individual sample concentrations, in the
applicable calculation for bin classification in
paragraphs (10)(B)1.–5. of this rule.
(C) Filtered systems must determine their
initial bin classification from the following
table and using the Cryptosporidium bin concentration calculated under subsections
(10)(A) and (B).
(D) Following completion of the second
round of source water monitoring required
under subsection (2)(B), filtered systems
must recalculate their Cryptosporidium bin
concentration using the Cryptosporidium
results reported under subsection (2)(B) and
following the procedures in paragraphs
(10)(B)1. through 4. Systems must then redetermine their bin classification using this bin
concentration and the table in subsection
(10)(C) of this rule.
(E) Reporting Bin Classification Requirements.
1. Filtered systems must report their initial bin classification under subsection
(10)(C) to the department for approval no
later than six (6) months after the system is
required to complete initial source water
monitoring based on the schedule in subsection (2)(C) of this rule.
2. Systems must report their bin classification under subsection (10)(D) to the
department for approval no later than six (6)
months after the system is required to complete the second round of source water monitoring based on the schedule in subsection
(2)(C) of this rule.
3. The bin classification report to the
department must include a summary of
source water monitoring data and the calculation procedure used to determine bin classification.
(F) Failure to comply with the conditions
of subsection (10)(E) of this rule is a violation
of the treatment technique requirement.
(11) Additional Cryptosporidium Treatment
Requirements.
(A) Filtered systems must provide the level
of additional treatment for Cryptosporidium
specified in this subsection based on their bin
classification as determined under section
(10) of this rule and according to the schedule
in section (12) of this rule.
For systems that are:
With a Cryptosporidium bin concentration
(based on calculations in subsection (10)(A)
or (10)(B) as applicable) of:
The bin classification
is:
Required to monitor for
Cryptosporidium under
section (2) of this rule.
Cryptosporidium < 0.075 oocyst/L
Bin 1
0.075 oocysts/L d Cryptosporidium < 1.0
oocysts/L
Bin 2
1.0 oocysts/L d Cryptosporidium < 3.0
oocysts/L
Bin 3
Cryptosporidium t 3.0 oocysts/L
Bin 4
Serving fewer than 10,000
people and NOT required to
monitor for Cryptosporidium
under paragraph (2)(A)3.
NA
Bin 1
Bin Classification Table for Filtered Systems
(B) Filtered systems must use one (1) or
more of the treatment and management
options listed in section (13) of this rule,
termed the Microbial Toolbox, to comply
with the additional Cryptosporidium treatment required in subsection (11)(A) of this
rule.
1. Systems classified in Bin 3 and Bin 4
must achieve at least 1-log of the additional
Cryptosporidium treatment required under
subsection (11)(A) of this rule using either
one (1) or a combination of the following:
bag filters, bank filtration, cartridge filters,
chlorine dioxide, membranes, ozone, or UV,
as described in sections (14) through (18) of
this rule.
(C) Failure by a system in any month to
achieve treatment credit by meeting criteria in
sections (14) through (18) of this rule for
microbial toolbox options that is at least
equal to the level of treatment required in
subsection (11)(A) of this rule is a violation of
the treatment technique requirement.
(D) If the department determines during a
sanitary survey or an equivalent source water
assessment that, after a system completed the
monitoring conducted under subsection
(2)(A) or (2)(B) of this rule, significant
changes occurred in the system’s watershed
that could lead to increased contamination of
the source water by Cryptosporidium, the system must take actions specified by the department to address the contamination. These
actions may include additional source water
monitoring and/or implementing microbial
toolbox options listed in section (13) of this
rule.
(12)
Schedule
for
Compliance
With
Cryptosporidium Treatment Requirements.
(A) Following initial bin classification
under subsection (10)(C), filtered systems
must provide the level of treatment for
Cryptosporidium required under section (11)
according to the following Cryptosporidium
treatment compliance dates.
If the system bin
classification is:
And the system uses the following filtration treatment in full compliance with 10 CSR 604.050, 10 CSR 60-4.055, and 10 CSR 60-7.010 (as applicable), then the additional
Cryptosporidium treatment requirements are:
Conventional
filtration treatment
(including softening)
Direct Filtration
Slow sand or
diatomaceous earth
filtration
Alternative filtration
technologies
Bin 1
No additional
treatment
No additional
treatment
No additional
treatment
No additional
treatment
Bin 2
1-log treatment
1.5-log treatment
1-log treatment
As determined by the
department such that
the total
Cryptosporidium
removal and
inactivation is at least
4.0-log.
Bin 3
2-log treatment
2.5-log treatment
2-log treatment
As determined by the
department such that
the total
Cryptosporidium
removal and
inactivation is at least
5.0-log.
Bin 4
2.5-log treatment
3-log treatment
2.5-log treatment
As determined by the
department such that
the total
Cryptosporidium
removal and
inactivation is at least
5.5-log.
(B) If the bin classification for a filtered
system changes following the second round of
source water monitoring, as determined
under subsection (10)(D) of this rule, the system must provide the level of treatment for
Cryptosporidium required under section (11)
of this rule on a schedule the department
approves.
(13) Microbial Toolbox Options for Meeting
Cryptosporidium Treatment Requirements.
(A) Systems receive the treatment credit
listed in the table in subsection (13)(B) of this
rule by meeting the conditions for microbial
toolbox options described in sections (14)
through (18) of this rule. Systems apply these
treatment credits to meet the treatment
requirements in section (11) of this rule, as
applicable.
(B) The following table summarizes
options in the microbial toolbox:
Cryptosporidium Treatment Compliance Dates Table
Systems that serve:
Must comply with Cryptosporidium treatment
requirements no later than the following dates, except
that the department may allow up to an additional two (2)
years for complying with the treatment requirement for
systems making capital improvements:
1. At least 100,000 people
April 1, 2012
2. From 50,000 to 99,999 people
October 1, 2012
3. From 10,000 to 49,999 people
October 1, 2013
4. Fewer than 10,000 people
October 1, 2014
0LFURELDO7RROER[6XPPDU\7DEOH2SWLRQV7UHDWPHQW&UHGLWDQG&ULWHULD
7RROER[2SWLRQ
&U\SWRVSRULGLXPWUHDWPHQWFUHGLWZLWKGHVLJQDQGLPSOHPHQWDWLRQFULWHULD
6RXUFH3URWHFWLRQDQG0DQDJHPHQW7RROER[2SWLRQV
:DWHUVKHGFRQWUROSURJUDP
ORJFUHGLWIRUGHSDUWPHQWDSSURYHGSURJUDPFRPSULVLQJUHTXLUHGHOHPHQWVDQQXDOSURJUDP
VWDWXVUHSRUWWRWKHGHSDUWPHQWDQGUHJXODUZDWHUVKHGVXUYH\6SHFLILFFULWHULDDUHLQVXEVHFWLRQ
$
$OWHUQDWLYHVRXUFHLQWDNH
PDQDJHPHQW
1RSUHVFULEHGFUHGLW6\VWHPVPD\FRQGXFWVLPXOWDQHRXVPRQLWRULQJIRUWUHDWPHQWELQ
FODVVLILFDWLRQDWDOWHUQDWLYHLQWDNHORFDWLRQVRUXQGHUDOWHUQDWLYHPDQDJHPHQWVWUDWHJLHV6SHFLILF
FULWHULDDUHLQVXEVHFWLRQ%
3UH)LOWUDWLRQ7RROER[2SWLRQV
3UHVHGLPHQWDWLRQEDVLQZLWK
FRDJXODWLRQ
ORJFUHGLWGXULQJDQ\PRQWKWKDWSUHVHGLPHQWDWLRQEDVLQVDFKLHYHDPRQWKO\PHDQUHGXFWLRQ
RIORJRUJUHDWHULQWXUELGLW\RUDOWHUQDWLYHGHSDUWPHQWDSSURYHGSHUIRUPDQFHFULWHULD7REH
HOLJLEOHEDVLQVPXVWEHRSHUDWHGFRQWLQXRXVO\ZLWKFRDJXODQWDGGLWLRQDQGDOOSODQWIORZPXVW
SDVVWKURXJKEDVLQV6SHFLILFFULWHULDDUHLQVXEVHFWLRQ$
7ZRVWDJHOLPHVRIWHQLQJ
ORJFUHGLWIRUWZRVWDJHVRIWHQLQJZKHUHFKHPLFDODGGLWLRQDQGKDUGQHVVSUHFLSLWDWLRQRFFXU
LQERWKVWDJHV$OOSODQWIORZPXVWSDVVWKURXJKERWKVWDJHV6LQJOHVWDJHVRIWHQLQJLVFUHGLWHGDV
HTXLYDOHQWWRFRQYHQWLRQDOWUHDWPHQW6SHFLILFFULWHULDDUHLQVXEVHFWLRQ%
%DQNILOWUDWLRQ
ORJFUHGLWIRUIRRWVHWEDFNORJFUHGLWIRUIRRWVHWEDFNDTXLIHUPXVWEH
XQFRQVROLGDWHGVDQGFRQWDLQLQJDWOHDVWWHQSHUFHQWILQHVDYHUDJHWXUELGLW\LQZHOOVPXVW
EHOHVVWKDQRQH1786\VWHPVXVLQJZHOOVIROORZHGE\ILOWUDWLRQZKHQFRQGXFWLQJVRXUFH
ZDWHUPRQLWRULQJPXVWVDPSOHWKHZHOOWRGHWHUPLQHELQFODVVLILFDWLRQDQGDUHQRWHOLJLEOHIRU
DGGLWLRQDOFUHGLW6SHFLILFFULWHULDDUHLQVXEVHFWLRQ&
7UHDWPHQW3HUIRUPDQFH7RROER[2SWLRQV
&RPELQHGILOWHUSHUIRUPDQFH
ORJFUHGLWIRUFRPELQHGILOWHUHIIOXHQWWXUELGLW\OHVVWKDQRUHTXDOWR178LQDWOHDVW
QLQHW\ILYHSHUFHQWRIPHDVXUHPHQWVHDFKPRQWK6SHFLILFFULWHULDDUHLQVXEVHFWLRQ
$
,QGLYLGXDOILOWHUSHUIRUPDQFH
ORJFUHGLWLQDGGLWLRQWRORJFRPELQHGILOWHUSHUIRUPDQFHFUHGLWLILQGLYLGXDOILOWHU
HIIOXHQWWXUELGLW\LVOHVVWKDQRUHTXDOWR178LQDWOHDVWQLQHW\ILYHSHUFHQWRI
VDPSOHVHDFKPRQWKLQHDFKILOWHUDQGLVQHYHUJUHDWHUWKDQ178LQWZRFRQVHFXWLYH
PHDVXUHPHQWVLQDQ\ILOWHU6SHFLILFFULWHULDDUHLQVXEVHFWLRQ%
'HPRQVWUDWLRQRISHUIRUPDQFH
&UHGLWDZDUGHGWRXQLWSURFHVVRUWUHDWPHQWWUDLQEDVHGRQDGHPRQVWUDWLRQWRWKHGHSDUWPHQW
ZLWKDGHSDUWPHQWDSSURYHGSURWRFRO6SHFLILFFULWHULDDUHLQVXEVHFWLRQ&
%DJRUFDUWULGJHILOWHUVLQGLYLGXDO
ILOWHUV
8SWRORJFUHGLWEDVHGRQWKHUHPRYDOHIILFLHQF\GHPRQVWUDWHGGXULQJFKDOOHQJHWHVWLQJZLWKD
ORJIDFWRURIVDIHW\6SHFLILFFULWHULDDUHLQVXEVHFWLRQ$
%DJRUFDUWULGJHILOWHUVLQVHULHV
8SWRORJFUHGLWEDVHGRQWKHUHPRYDOHIILFLHQF\GHPRQVWUDWHGGXULQJFKDOOHQJHWHVWLQJZLWK
DORJIDFWRURIVDIHW\6SHFLILFFULWHULDDUHLQVXEVHFWLRQ$
0HPEUDQHILOWUDWLRQ
/RJFUHGLWHTXLYDOHQWWRUHPRYDOHIILFLHQF\GHPRQVWUDWHGLQFKDOOHQJHWHVWIRUGHYLFHLI
VXSSRUWHGE\GLUHFWLQWHJULW\WHVWLQJ6SHFLILFFULWHULDDUHLQVXEVHFWLRQ%
6HFRQGVWDJHILOWUDWLRQ
ORJFUHGLWIRUVHFRQGVHSDUDWHJUDQXODUPHGLDILOWUDWLRQVWDJHLIWUHDWPHQWWUDLQLQFOXGHV
FRDJXODWLRQSULRUWRILUVWILOWHU6SHFLILFFULWHULDDUHLQVXEVHFWLRQ&
6ORZVDQGILOWUDWLRQ
ORJFUHGLWDVDVHFRQGDU\ILOWUDWLRQVWHSORJFUHGLWDVDSULPDU\ILOWUDWLRQSURFHVV1R
SULRUFKORULQDWLRQIRUHLWKHURSWLRQ6SHFLILFFULWHULDDUHLQVXEVHFWLRQ'
,QDFWLYDWLRQ7RROER[2SWLRQV
&KORULQHGLR[LGH
/RJFUHGLWEDVHGRQPHDVXUHG&7LQUHODWLRQWR&7WDEOH6SHFLILFFULWHULDLQVXEVHFWLRQ%
2]RQH
/RJFUHGLWEDVHGRQPHDVXUHG&7LQUHODWLRQWR&7WDEOH6SHFLILFFULWHULDLQVXEVHFWLRQ%
8OWUDYLROHW
/RJFUHGLWEDVHGRQYDOLGDWHG89GRVHLQUHODWLRQWR89GRVHWDEOHUHDFWRUYDOLGDWLRQWHVWLQJ
UHTXLUHGWRHVWDEOLVK89GRVHDQGDVVRFLDWHGRSHUDWLQJFRQGLWLRQV6SHFLILFFULWHULDLQVXEVHFWLRQ
'
(14) Source Toolbox Components.
(A) Watershed Control Program. Systems
receive 0.5-log Cryptosporidium treatment
credit for implementing a watershed control
program that meets the requirements of this
section.
1. Systems that intend to apply for the
watershed control program credit must notify
the department of this intent no later than two
(2) years prior to the treatment compliance
date applicable to the system in section (12)
of this rule.
2. Systems must submit to the department a proposed watershed control plan no
later than one (1) year before the applicable
treatment compliance date in section (12) of
this rule. The department must approve the
watershed control plan for the system to
receive watershed control program treatment
credit. The watershed control plan must
include the elements in subparagraphs
(14)(A)2.A.–D. of this rule.
A. Identification of an “area of influence” outside of which the likelihood of
Cryptosporidium or fecal contamination
affecting the treatment plant intake is not significant. This is the area to be evaluated in
future watershed surveys under subparagraph
(14)(A)5.B.
B. Identification of both potential and
actual sources of Cryptosporidium contamination and an assessment of the relative
impact of these sources on the system’s
source water quality.
C. An analysis of the effectiveness
and feasibility of control measures that could
reduce
Cryptosporidium
loading
from
sources of contamination to the system’s
source water.
D. A statement of goals and specific
actions the system will undertake to reduce
source water Cryptosporidium levels. The
plan must explain how the actions are expected to contribute to specific goals, identify
watershed partners and their roles, identify
resource requirements and commitments, and
include a schedule for plan implementation
with deadlines for completing specific actions
identified in the plan.
3. Systems with existing watershed control programs (that is, programs in place on
January 5, 2006) are eligible to seek this
credit. Their watershed control plans must
meet the criteria in paragraph (14)(A)2. of
this rule and must specify ongoing and future
actions that will reduce source water
Cryptosporidium levels.
4. If the department does not respond to
a system regarding approval of a watershed
control plan submitted under this section and
the system meets the other requirements of
this section, the watershed control program
will be considered approved and 0.5-log
Cryptosporidium treatment credit will be
awarded unless and until the department subsequently withdraws such approval.
5. Systems must complete the actions in
subparagraphs (14)(A)5.A.–C. of this rule to
maintain the 0.5-log credit.
A. Submit an annual watershed control program status report to the department.
The annual watershed control program status
report must describe the system’s implementation of the approved plan and assess the
adequacy of the plan to meet its goals. It must
explain how the system is addressing any
shortcomings in plan implementation, including those previously identified by the department or as the result of the watershed survey
conducted under subparagraph (14)(A)5.B. of
this rule. It must also describe any significant
changes that have occurred in the watershed
since the last watershed sanitary survey. If a
system determines during implementation
that making a significant change to its
approved watershed control program is necessary, the system must notify the department
prior to making any such changes. If any
change is likely to reduce the level of source
water protection, the system must also list in
its notification the actions the system will
take to mitigate this effect.
B. Undergo a watershed sanitary survey every three (3) years for community
water systems and every five (5) years for
noncommunity water systems and submit the
survey report to the department. The survey
must be conducted according to department
guidelines and by persons the department
approves.
(I) The watershed sanitary survey
must meet the following criteria: encompass
the region identified in the departmentapproved watershed control plan as the area
of influence; assess the implementation of
actions
to
reduce
source
water
Cryptosporidium levels; and identify any significant new sources of Cryptosporidium.
(II) If the department determines
that significant changes may have occurred in
the watershed since the previous watershed
sanitary survey, systems must undergo another watershed sanitary survey by a date the
department requires, which may be earlier
than the regular date in subparagraph
(14)(A)5.B. of this rule.
C. The system must make the watershed control plan, annual status reports, and
watershed sanitary survey reports available to
the public upon request. These documents
must be in a plain language style and include
criteria by which to evaluate the success of
the program in achieving plan goals. The
department may approve systems to withhold
from the public portions of the annual status
report, watershed control plan, and watershed
sanitary survey based on water supply security considerations.
6. If the department determines that a
system is not carrying out the approved
watershed control plan, the department may
withdraw the watershed control program
treatment credit.
(B) Alternative Source Requirements.
1. A system may conduct source water
monitoring that reflects a different intake
location (either in the same source or for an
alternate source) or a different procedure for
the timing or level of withdrawal from the
source (alternative source monitoring). If the
department approves, a system may determine its bin classification under section (10)
of this rule based on the alternative source
monitoring results.
2. If systems conduct alternative source
monitoring under paragraph (14)(B)1. of this
rule, systems must also monitor their current
plant intake concurrently as described in section (2) of this rule.
3. Alternative source monitoring under
paragraph (14)(B)1. of this rule must meet
the requirements for source monitoring to
determine bin classification, as described in
sections (2)–(6) of this rule. Systems must
report the alternative source monitoring
results to the department, along with supporting information documenting the operating conditions under which the samples were
collected.
4. If a system determines its bin classification under section (10) of this rule using
alternative source monitoring results that
reflect a different intake location or a different procedure for managing the timing or
level of withdrawal from the source, the system must relocate the intake or permanently
adopt the withdrawal procedure, as applicable, no later than the applicable treatment
compliance date in section (12) of this rule.
(15) Pre-Filtration Treatment Toolbox Components.
(A) Presedimentation. Systems receive
0.5-log Cryptosporidium treatment credit for
a presedimentation basin during any month
the process meets the criteria in this subsection.
1. The presedimentation basin must be
in continuous operation and must treat the
entire plant flow taken from a surface water
or GWUDISW source.
2. The system must continuously add a
coagulant to the presedimentation basin.
3. The presedimentation basin must
achieve the performance criteria in subparagraph (15)(A)3.A. or B. of this rule.
A. Demonstrates at least 0.5-log
mean reduction of influent turbidity. This
reduction must be determined using daily turbidity measurements in the presedimentation
process influent and effluent and must be calculated as follows: log10(monthly mean of
daily influent turbidity) − log10(monthly
mean of daily effluent turbidity).
B.
Complies
with
departmentapproved performance criteria that demonstrate at least 0.5-log mean removal of
micron-sized particulate material through the
presedimentation process.
(B) Two (2)-Stage Lime Softening.
Systems receive an additional 0.5-log
Cryptosporidium treatment credit for a two
(2)-stage lime softening plant if chemical
addition and hardness precipitation occur in
two (2) separate and sequential softening
stages prior to filtration. Both softening
stages must treat the entire plant flow taken
from a surface water or GWUDISW source.
(C) Bank Filtration. Systems receive
Cryptosporidium treatment credit for bank
filtration that serves as pretreatment to a filtration plant by meeting the criteria in this
subsection. Systems using bank filtration
when they begin source water monitoring
under subsection (2)(A) of this rule must collect samples as described in subsection
(4)(D) of this rule and are not eligible for this
credit.
1. Wells with a ground water flow path
of at least twenty-five feet (25') receive 0.5log treatment credit; wells with a ground
water flow path of at least fifty feet (50')
receive 1.0-log treatment credit. The ground
water flow path must be determined as specified in paragraph (15)(C)4. of this rule.
2. Only wells in granular aquifers are
eligible for treatment credit. Granular
aquifers are those comprised of sand, clay,
silt, rock fragments, pebbles or larger particles, and minor cement. A system must characterize the aquifer at the well site to determine aquifer properties. Systems must extract
a core from the aquifer and demonstrate that,
in at least ninety percent (90%) of the core
length, grains less than 1.0 mm in diameter
constitute at least ten percent (10%) of the
core material.
3. Only horizontal and vertical wells are
eligible for treatment credit.
4. For vertical wells, the ground water
flow path is the measured distance from the
edge of the surface water body under high
flow conditions (determined by the one hundred (100)-year floodplain elevation boundary
or by the floodway, as defined in Federal
Emergency Management Agency flood hazard maps) to the well screen. For horizontal
wells, the ground water flow path is the measured distance from the bed of the river under
normal flow conditions to the closest horizontal well lateral screen.
5. Systems must monitor each wellhead
for turbidity at least once every four (4) hours
while the bank filtration process is in operation. If monthly average turbidity levels,
based on daily maximum values in the well,
exceed one (1) nephelometric turbidity unit
(NTU), the system must report this result to
the department and conduct an assessment
within thirty (30) days to determine the cause
of the high turbidity levels in the well. If the
department
determines
that
microbial
removal has been compromised, the department may revoke treatment credit until the
system
implements
corrective
actions
approved by the department to remediate the
problem.
6. Springs and infiltration galleries are
not eligible for treatment credit under this
section but are eligible for credit under subsection (16)(C) of this rule.
7. Bank filtration demonstration of performance. The department may approve
Cryptosporidium treatment credit for bank
filtration based on a demonstration of performance study that meets the criteria in this
subsection. This treatment credit may be
greater than 1.0-log and may be awarded to
bank filtration that does not meet the criteria
in paragraphs (15)(C)1.–5. of this rule.
A. The study must follow a department-approved protocol and must involve the
collection of data on the removal of
Cryptosporidium
or
a
surrogate
for
Cryptosporidium and related hydrogeologic
and water quality parameters during the full
range of operating conditions.
B. The study must include sampling
both from the production well(s) and from
monitoring wells that are screened and located along the shortest flow path between the
surface water source and the production
well(s).
(16) Treatment Performance Toolbox Components.
(A) Combined Filter Performance. Systems
using conventional filtration treatment or
direct filtration treatment receive an additional 0.5-log Cryptosporidium treatment credit
during any month the system meets the criteria in this subsection. Combined filter effluent
(CFE) turbidity must be less than or equal to
0.15 NTU in at least ninety-five percent
(95%) of the measurements. Turbidity must be
measured as described in 10 CSR 60-4.050(2)
and 10 CSR 60-4.080(3).
(B) Individual Filter Performance. Systems
using conventional filtration treatment or
direct filtration treatment receive 0.5-log
Cryptosporidium treatment credit, which can
be in addition to the 0.5-log credit under subsection (16)(A) during any month the system
meets the criteria in this subsection.
Compliance with these criteria must be based
on individual filter turbidity monitoring as
described in 10 CSR 60-4.050(2)(D) and 10
CSR 60-7.010(6).
1. The filtered water turbidity for each
individual filter must be less than or equal to
0.15 NTU in at least ninety-five percent
(95%) of the measurements recorded each
month.
2. No individual filter may have a measured turbidity greater than 0.3 NTU in two
(2) consecutive measurements taken fifteen
(15) minutes apart.
3. Any system that has received treatment credit for individual filter performance
and fails to meet the requirements of paragraph (16)(B)1. or 2. of this rule during any
month does not receive a treatment technique
violation under subsection (11)(C) of this rule
if the department determines the following:
A. The failure was due to unusual and
short-term circumstances that could not reasonably be prevented through optimizing
treatment plant design, operation, and maintenance; and
B. The system has experienced no
more than two (2) such failures in any calendar year.
(C) Demonstration of Performance. The
department may approve Cryptosporidium
treatment credit for drinking water treatment
processes based on a demonstration of performance study that meets the criteria in this
subsection. This treatment credit may be
greater than or less than the prescribed treatment credits in section (11) or section (15)
through section (18) of this rule and may be
awarded to treatment processes that do not
meet the criteria for the prescribed credits.
1. Systems cannot receive the prescribed
treatment credit for any toolbox option in sections (15) through (18) if that toolbox option
is included in a demonstration of performance study for which treatment credit is
awarded under this paragraph.
2. The demonstration of performance
study must follow a department-approved
protocol and must demonstrate the level of
Cryptosporidium reduction the treatment process will achieve under the full range of
expected operating conditions for the system.
3. Approval by the department must be
in writing and may include monitoring and
treatment performance criteria that the system must demonstrate and report on an ongoing basis to remain eligible for the treatment
credit. The department may designate such
criteria, where necessary, to verify that the
conditions under which the demonstration of
performance credit was approved are maintained during routine operation.
(17) Additional Filtration Toolbox Components.
(A) Bag and Cartridge Filters. Systems
receive Cryptosporidium treatment credit of
up to 2.0-log for individual bag or cartridge
filters and up to 2.5-log for bag or cartridge
filters operated in series by meeting the criteria in paragraphs (17)(A)1. through 10. of
this section. To be eligible for this credit, systems must report the results of challenge testing that meets the requirements of paragraphs
(17)(A)2. through 9. to the department. The
filters must treat the entire plant flow taken
from a surface water or ground water under
the direct influence of surface water source.
1. The Cryptosporidium treatment credit awarded to bag or cartridge filters must be
based on the removal efficiency demonstrated
during challenge testing that is conducted
according to the criteria in paragraphs
(17)(A)2. through 9. A factor of safety equal
to 1-log for individual bag or cartridge filters
and 0.5-log for bag or cartridge filters in
series must be applied to challenge testing
results to determine removal credit. Systems
may use results from challenge testing conducted prior to January 5, 2006, if the prior
testing was consistent with the criteria specified in paragraphs (17)(A)2. through 9.
2. Challenge testing must be performed
on full-scale bag or cartridge filters, and the
associated filter housing or pressure vessel,
that are identical in material and construction
to the filters and housings the system will use
for removal of Cryptosporidium. Bag or cartridge filters must be challenge tested in the
same configuration that the system will use,
either as individual filters or as a series configuration of filters.
3. Challenge testing must be conducted
using Cryptosporidium or a surrogate that is
removed no more efficiently than Cryptosporidium. The microorganism or surrogate
used during challenge testing is referred to as
the challenge particulate. The concentration
of the challenge particulate must be determined using a method capable of discretely
quantifying the specific microorganism or
surrogate used in the test; gross measurements such as turbidity may not be used.
4. The maximum feed water concentration that can be used during a challenge test
must be based on the detection limit of the
challenge particulate in the filtrate (i.e., filtrate detection limit) and must be calculated
using the following equation:
Maximum Feed Concentration = 1 ×
104 × (Filtrate Detection Limit).
5. Challenge testing must be conducted
at the maximum design flow rate for the filter as specified by the manufacturer.
6. Each filter evaluated must be tested
for a duration sufficient to reach one hundred
percent (100%) of the terminal pressure drop,
which establishes the maximum pressure
drop under which the filter may be used to
comply with the requirements of this rule.
7. Removal efficiency of a filter must be
determined from the results of the challenge
test and expressed in terms of log removal
values using the following equation:
LRV = LOG10(Cf) − LOG10(Cp)
Where:
LRV = log removal value demonstrated
during challenge testing
Cf = the feed concentration measured during the challenge test
Cp = the filtrate concentration measured
during the challenge test
In applying this equation, the same units
must be used for the feed and filtrate concentrations. If the challenge particulate is not
detected in the filtrate, then the term Cp must
be set equal to the detection limit.
8. Each filter tested must be challenged
with the challenge particulate during three (3)
periods over the filtration cycle: within two
(2) hours of start-up of a new filter; when the
pressure drop is between forty-five percent
and fifty-five percent (45%–55%) of the terminal pressure drop; and at the end of the
cycle after the pressure drop has reached one
hundred percent (100%) of the terminal pressure drop. An LRV must be calculated for
each of these challenge periods for each filter
tested. The LRV for the filter (LRVfilter) must
be assigned the value of the minimum LRV
observed during the three (3) challenge periods for that filter.
9. If fewer than twenty (20) filters are
tested, the overall removal efficiency for the
filter product line must be set equal to the
lowest LRVfilter among the filters tested. If
twenty (20) or more filters are tested, the
overall removal efficiency for the filter product line must be set equal to the 10th percentile of the set of LRVfilter values for the
various filters tested. The percentile is
defined by (i/(n+1)) where i is the rank of n
individual data points ordered lowest to highest. If necessary, the 10th percentile may be
calculated using linear interpolation.
10. If a previously tested filter is modified in a manner that could change the
removal efficiency of the filter product line,
challenge testing to demonstrate the removal
efficiency of the modified filter must be conducted and submitted to the department.
(B) Membrane Filtration Requirements.
1. Systems receive Cryptosporidium
treatment credit for membrane filtration that
meets the criteria of this paragraph.
Membrane cartridge filters that meet the definition of membrane filtration in 10 CSR 602.015 are eligible for this credit. The level of
treatment credit a system receives is equal to
the lower of the values determined under subparagraphs (17)(B)1.A. and B.
A. The removal efficiency demonstrated during challenge testing conducted
under the conditions in paragraph (17)(B)2.
B. The maximum removal efficiency
that can be verified through direct integrity
testing used with the membrane filtration process under the conditions in paragraph
(17)(B)3.
2. Challenge testing. The membrane
used by the system must undergo challenge
testing to evaluate removal efficiency, and the
system must report the results of challenge
testing to the department. Challenge testing
must be conducted according to the criteria in
subparagraphs (17)(B)2.A. through H.
Systems may use data from challenge testing
conducted prior to January 5, 2006, if the
prior testing was consistent with the criteria
in subparagraphs (17)(B)2.A. through G.
A. Challenge testing must be conducted on either a full-scale membrane module, identical in material and construction to
the membrane modules used in the system’s
treatment facility, or a smaller-scale membrane module, identical in material and similar in construction to the full-scale module.
A module is defined as the smallest component of a membrane unit in which a specific
membrane surface area is housed in a device
with a filtrate outlet structure.
B. Challenge testing must be conducted using Cryptosporidium oocysts or a surrogate that is removed no more efficiently than
Cryptosporidium oocysts. The organism or
surrogate used during challenge testing is
referred to as the challenge particulate. The
concentration of the challenge particulate, in
both the feed and filtrate water, must be
determined using a method capable of discretely quantifying the specific challenge particulate used in the test; gross measurements
such as turbidity may not be used.
C. The maximum feed water concentration that can be used during a challenge
test is based on the detection limit of the challenge particulate in the filtrate and must be
determined according to the following equation:
Maximum Feed Concentration = 3.16 ×
106 × (Filtrate Detection Limit)
D. Challenge testing must be conducted under representative hydraulic conditions at the maximum design flux and maximum design process recovery specified by the
manufacturer for the membrane module.
Flux is defined as the throughput of a pressure-driven membrane process expressed as
flow per unit of membrane area. Recovery is
defined as the volumetric percent of feed
water that is converted to filtrate over the
course of an operating cycle uninterrupted by
events such as chemical cleaning or a solids
removal process (i.e., backwashing).
E. Removal efficiency of a membrane
module must be calculated from the challenge
test results and expressed as a log removal
value according to the following equation:
LRV = LOG10(Cf) − LOG10(Cp)
Where:
LRV = log removal value demonstrated
during the challenge test
Cf = the feed concentration measured during the challenge test
Cp = the filtrate concentration measured
during the challenge test
Equivalent units must be used for the feed
and filtrate concentrations. If the challenge
particulate is not detected in the filtrate, the
term Cp is set equal to the detection limit for
the purpose of calculating the LRV. An LRV
must be calculated for each membrane module evaluated during the challenge test.
F. The removal efficiency of a membrane filtration process demonstrated during
challenge testing must be expressed as a log
removal value (LRVC-Test). If fewer than twenty (20) modules are tested, then LRVC-Test is
equal to the lowest of the representative LRVs
among the modules tested. If twenty (20) or
more modules are tested, then LRVC-Test is
equal to the 10th percentile of the representative LRVs among the modules tested. The
percentile is defined by (i/(n+1)) where i is
the rank of n individual data points ordered
lowest to highest. If necessary, the 10th percentile may be calculated using linear interpolation.
G. The challenge test must establish a
quality control release value (QCRV) for a
non-destructive performance test that demonstrates the Cryptosporidium removal capability of the membrane filtration module. This
performance test must be applied to each production membrane module used by the system that was not directly challenge tested in
order to verify Cryptosporidium removal
capability. Production modules that do not
meet the established QCRV are not eligible
for the treatment credit demonstrated during
the challenge test.
H. If a previously tested membrane is
modified in a manner that could change the
removal efficiency of the membrane or the
applicability of the non-destructive performance test and associated QCRV, additional
challenge testing to demonstrate the removal
efficiency of, and determine a new QCRV
for, the modified membrane must be conducted and submitted to the department.
3. Direct integrity testing. Systems
must conduct direct integrity testing in a
manner that demonstrates a removal efficiency equal to or greater than the removal credit awarded to the membrane filtration process
and meets the requirements described in subparagraphs (17)(B)3.A.–G. of this rule. A
direct integrity test is defined as a physical
test applied to a membrane unit in order to
identify and isolate integrity breaches (that is,
one (1) or more leaks that could result in contamination of the filtrate).
A. The direct integrity test must be
independently applied to each membrane unit
in service. A membrane unit is defined as a
group of membrane modules that share common valving that allows the unit to be isolated from the rest of the system for the purpose
of integrity testing or other maintenance.
B. The direct integrity method must
have a resolution of three (3) micrometers or
less, where resolution is defined as the size of
the smallest integrity breach that contributes
to a response from the direct integrity test.
C. The direct integrity test must have
a sensitivity sufficient to verify the log treatment credit awarded to the membrane filtration process by the department, where sensitivity is defined as the maximum log removal
value that can be reliably verified by a direct
integrity test. Sensitivity must be determined
using
the
approach
in
either
part
(17)(B)3.C.(I) or (II) of this section as applicable to the type of direct integrity test the
system uses.
(I) For direct integrity tests that use
an applied pressure or vacuum, the direct
integrity test sensitivity must be calculated
according to the following equation:
LRVDIT = LOG10 (Qp /(VCF × Qbreach))
Where:
LRVDIT = the sensitivity of the direct
integrity test
Qp = total design filtrate flow from the
membrane unit
Qbreach = flow of water from an integrity
breach associated with the smallest integrity test response that
can be reliably measured
VCF = volumetric concentration factor
The volumetric concentration factor is the
ratio of the suspended solids concentration on
the high pressure side of the membrane relative to that in the feed water.
(II) For direct integrity tests that
use a particulate or molecular marker, the
direct integrity test sensitivity must be calculated according to the following equation:
LRVDIT = LOG10(Cf) − LOG10(Cp)
Where:
LRVDIT = the sensitivity of the direct
integrity test
Cf = the typical feed concentration of the
marker used in the test
Cp = the filtrate concentration of the
marker from an integral membrane
unit
D. Systems must establish a control
limit within the sensitivity limits of the direct
integrity test that is indicative of an integral
membrane unit capable of meeting the
removal credit awarded by the department.
E. If the result of a direct integrity
test exceeds the control limit established
under subparagraph (17)(B)3.D., the system
must remove the membrane unit from service. Systems must conduct a direct integrity
test to verify any repairs and may return the
membrane unit to service only if the direct
integrity test is within the established control
limit.
F. Systems must conduct direct
integrity testing on each membrane unit at a
frequency of not less than once each day that
the membrane unit is in operation. The
department may approve less frequent testing,
based on demonstrated process reliability, the
use of multiple barriers effective for
Cryptosporidium, or reliable process safeguards.
4.
Indirect
integrity
monitoring.
Systems must conduct continuous indirect
integrity monitoring on each membrane unit
according to the criteria in subparagraphs
(17)(B)4.A. through E. Indirect integrity
monitoring is defined as monitoring some
aspect of filtrate water quality that is indicative of the removal of particulate matter. A
system that implements continuous direct
integrity testing of membrane units in accordance with the criteria in subparagraphs
(17)(B)3.A. through E. of this section is not
subject to the requirements for continuous
indirect integrity monitoring. Systems must
submit a monthly report to the department
summarizing all continuous indirect integrity
monitoring results triggering direct integrity
testing and the corrective action that was
taken in each case.
A. Unless the department approves an
alternative parameter, continuous indirect
integrity monitoring must include continuous
filtrate turbidity monitoring.
B. Continuous monitoring must be
conducted at a frequency of no less than once
every fifteen (15) minutes.
C. Continuous monitoring must be
separately conducted on each membrane unit.
D. If indirect integrity monitoring
includes turbidity and if the filtrate turbidity
readings are above 0.15 NTU for a period
greater than fifteen (15) minutes (i.e., two (2)
consecutive fifteen (15)-minute readings
above 0.15 NTU), direct integrity testing
must immediately be performed on the associated membrane unit as specified in subparagraphs (17)(B)3.A. through E.
E. If indirect integrity monitoring
includes a department-approved alternative
parameter and if the alternative parameter
exceeds a department-approved control limit
for a period greater than fifteen (15) minutes,
direct integrity testing must immediately be
performed on the associated membrane units
as specified in subparagraphs (17)(B)3.A.
through E.
(C) Second Stage Filtration. Systems
receive 0.5-log Cryptosporidium treatment
credit for a separate second stage of filtration
that consists of sand, dual media, granular
activated carbon (GAC), or other fine grain
media following granular media filtration if
the department approves. To be eligible for
this credit, the first stage of filtration must be
preceded by a coagulation step, and both filtration stages must treat the entire plant flow
taken from a surface water or GWUDISW
source. A cap, such as GAC, on a single
stage of filtration is not eligible for this credit. The department must approve the treatment credit based on an assessment of the
design characteristics of the filtration process.
(D) Slow Sand Filtration (as Secondary
Filter). Systems are eligible to receive 2.5log Cryptosporidium treatment credit for a
slow sand filtration process that follows a separate stage of filtration if both filtration stages
treat entire plant flow taken from a surface
water or GWUDISW source and no disinfectant residual is present in the influent water to
the slow sand filtration process. The department must approve the treatment credit based
on an assessment of the design characteristics
of the filtration process. This subsection
does not apply to treatment credit awarded to
slow sand filtration used as a primary filtration process.
(18) Inactivation Toolbox Components.
(A) Calculation of CT Values.
1. CT is the product of the disinfectant
contact time (T, in minutes) and disinfectant
concentration (C, in milligrams per liter).
Systems with treatment credit for chlorine
dioxide or ozone under subsection (18)(B) or
(C) must calculate CT at least once each day,
with both C and T measured during peak
hourly flow as specified in 10 CSR 60-5.010,
10 CSR 60-5.020, and the Missouri Guidance
Manual for Surface Water System Treatment
Requirements, 1992.
2. Systems with several disinfection segments in sequence may calculate CT for each
segment, where a disinfection segment is
defined as a treatment unit process with a
measurable disinfectant residual level and a
liquid volume. Under this approach, systems
must add the Cryptosporidium CT values in
each segment to determine the total CT for
the treatment plant.
(B) CT Values for Chlorine Dioxide and
Ozone.
1. Systems receive the Cryptosporidium
treatment credit listed in this table by meeting
the corresponding chlorine dioxide CT value
for the applicable water temperature, as
described in subsection (18)(A). Systems
may use this equation to determine log credit
between the indicated values:
Log credit = (0.001506 ×
(1.09116)Temp) × CT
2. Systems receive the Cryptosporidium
treatment credit listed in this table by meeting
the corresponding ozone CT values for the
applicable water temperature, as described in
subsection (18)(A) of this rule.
Log credit
Water temperature, qC
<
0.5
1
2
3
5
7
10
15
20
25
30
0.25
159
153
140
128
107
90
69
45
29
19
12
0.5
319
305
279
256
214
180
138
89
58
38
24
1.0
637
610
558
511
429
360
277
179
116
75
49
1.5
956
915
838
767
643
539
415
268
174
113
73
2.0
1275
1220 1117 1023 858
719
553
357
232
150
98
2.5
1594
1525 1396 1278 1072 899
691
447
289
188
122
3.0
1912
1830 1675 1534 1286 1079 830
536
347
226
147
CT Values (MG-MIN/L) for Cryptosporidium Inactivation By Chlorine Dioxide
CT Values (MG-MIN/L) for Cryptosporidium Inactivation by Ozone
Systems may use this equation to determine log credit between the indicated values: Log credit = (0.0397 ×
(1.09757) temp) × CT
Log credit
Water Temperature, qC
<
0.5
1
2
3
5
7
10
15
20
25
30
0.25
6.0
5.8 5.2
4.8
4.0
3.3
2.5
1.6
1.0
0.6
0.39
0.5
12
12
10
9.5
7.9
6.5
4.9
3.1
2.0
1.2
0.78
1.0
24
23
21
19
16
13
9.9
6.2
3.9
2.5
1.6
1.5
36
35
31
29
24
20
15
9.3
5.9
3.7
2.4
2.0
48
46
42
38
32
26
20
12
7.8
4.9
3.1
2.5
60
58
52
48
40
33
25
16
9.8
6.2
3.9
3.0
72
69
63
57
47
39
30
19
12
7.4
4.7
(C) Site-Specific Study. The department
may approve alternative chlorine dioxide or
ozone CT values to those listed in subsection
(18)(B) on a site-specific basis. The department must base this approval on a site-specific study a system conducts that follows a
department-approved protocol.
(D) Ultraviolet Light. Systems receive
Cryptosporidium, Giardia lamblia, and
virus-treatment credits for ultraviolet (UV)
light reactors by achieving the corresponding
UV dose values shown in paragraph
(18)(D)1. Systems must validate and monitor
UV reactors as described in paragraphs
(18)(D)2. and 3. to demonstrate that they are
achieving a particular UV dose value for
treatment credit.
1. UV dose table. The treatment credits
listed in this table are for UV light at a wavelength of two hundred fifty-four nanometers
(254 nm) as produced by a low pressure mercury vapor lamp. To receive treatment credit
for other lamp types, systems must demonstrate an equivalent germicidal dose through
reactor validation testing, as described in
paragraph (18)(D)2. of this rule. The UV
dose values in this table are applicable only to
post-filter applications of UV in filtered systems.
UV Dose Table for Cryptosporidium, Giardia lamblia, and Virus Inactivation Credit
Log credit
Cryptosporidium UV
dose (mJ/cm2)
Giardia lamblia UV
dose (mJ/cm2)
Virus
UV dose (mJ/cm2)
0.5
1.6
1.5
39
1.0
2.5
2.1
58
1.5
3.9
3.0
79
2.0
5.8
5.2
100
2.5
8.5
7.7
121
3.0
12
11
143
3.5
15
15
163
4.0
22
22
186
2. Reactor validation testing. Systems
must use UV reactors that have undergone
validation testing to determine the operating
conditions under which the reactor delivers
the UV dose required in paragraph (18)(D)1.
(i.e., validated operating conditions). These
operating conditions must include flow rate,
UV intensity as measured by a UV sensor,
and UV lamp status.
A. When determining validated operating conditions, systems must account for
the following factors: UV absorbance of the
water; lamp fouling and aging; measurement
uncertainty of online sensors; UV dose distributions arising from the velocity profiles
through the reactor; failure of UV lamps or
other critical system components; and inlet
and outlet piping or channel configurations of
the UV reactor.
B. Validation testing must include the
following: Full-scale testing of a reactor that
conforms uniformly to the UV reactors used
by the system and inactivation of a test
microorganism whose dose response characteristics have been quantified with a low pressure mercury vapor lamp.
C. The department may approve an
alternative approach to validation testing.
3. Reactor monitoring requirements.
A. Systems must monitor their UV
reactors to determine if the reactors are operating within validated conditions, as determined under paragraph (18)(D)2. This monitoring must include UV intensity as measured by a UV sensor, flow rate, lamp status,
and other parameters the department designates based on UV reactor operation.
Systems must verify the calibration of UV
sensors and must recalibrate sensors in accordance with a protocol the department
approves.
B. To receive treatment credit for UV
light, systems must treat at least ninety-five
percent (95%) of the water delivered to the
public during each month by UV reactors
operating within validated conditions for the
required UV dose, as described in paragraphs
(18)(D)1. and 2. Systems must demonstrate
compliance with this condition by the monitoring
required
under
subparagraph
(18)(D)3.A. of this rule.
(19) Reporting Requirements.
(A) Systems must report sampling schedules under section (3) of this rule and source
water monitoring results under section (6) of
this rule unless they notify the department
that they will not conduct source water monitoring due to meeting the criteria of subsection (2)(D) of this rule.
(B) Filtered systems must report their
Cryptosporidium
bin
classification
as
described in section (10) of this rule.
(C) Systems must report disinfection profiles and benchmarks to the department as
described in sections (8) through (9) of this
rule prior to making a significant change in
disinfection practice.
(D) Systems must report to the department
in accordance with the following table for any
microbial toolbox options used to comply
with treatment requirements under section
(11) of this rule. Alternatively, the department
may approve a system to certify operation
within required parameters for treatment
credit rather than reporting monthly operational data for toolbox options.
Microbial Toolbox Reporting Requirements
Toolbox option
Systems must submit the
following information
On the following schedule
Watershed control
program (WCP)
(I) Notice of intention to develop
a new or continue an existing
watershed control program
No later than two years before the
applicable treatment compliance date in
section (12) of this rule
(II) Watershed control plan
No later than one year before the
applicable treatment compliance date in
section (12) of this rule
(III) Annual watershed control
program status report
Every 12 months, beginning one year
after the applicable treatment
compliance date in section (12) of this
rule
(IV) Watershed sanitary survey
report
For community water systems, every
three years beginning three years after
the applicable treatment compliance
date in section (12) of this rule. For
noncommunity water systems, every
five years beginning five years after the
applicable treatment compliance date in
section (12) of this rule
Alternative source/intake
management
Verification that system has
relocated the intake or adopted
the intake withdrawal procedure
reflected in monitoring results
No later than the applicable treatment
compliance date in section (12) of this
rule
Presedimentation
Monthly verification of the
following:
(I) Continuous basin operation;
(II) Treatment of 100% of the
flow;
(III) Continuous addition of a
coagulate; and
(IV) At least 0.5-log mean
reduction of influent turbidity or
compliance with alternative
department-approved
performance criteria
Monthly reporting within 10 days
following the month in which the
monitoring was conducted, beginning
on the applicable treatment compliance
date in section (12) of this rule
Two-stage lime softening
Monthly verification of the
following:
(I) Chemical addition and
hardness precipitation occurred
in two separate and sequential
softening stages prior to
filtration; and
(II) Both stages treated 100% of
the plant flow
Monthly reporting within 10 days
following the month in which the
monitoring was conducted beginning on
the applicable treatment compliance
date in section (12) of this rule
Bank filtration
(I) Initial demonstration of the
following:
(A) Unconsolidated,
predominantly sandy aquifer;
and
(B) Setback distance of at least
25 ft. (0.5-log credit) or 50 ft.
(1.0-log credit)
No later than the applicable treatment
compliance date in section (12) of this
rule
(II) If monthly average of daily
max turbidity is greater than
1 NTU, then the system must
report result and submit an
assessment of the cause
Report within 30 days following the
month in which the monitoring was
conducted, beginning on the applicable
treatment compliance date in section
(12) of this rule
Combined filter
performance
Monthly verification of
combined filter effluent (CFE)
turbidity levels less than or equal
to 0.15 NTU in at least 95% of
the 4 hour CFE measurements
taken each month
Monthly reporting within 10 days
following the month in which the
monitoring was conducted beginning on
the applicable treatment compliance
date in section (12) of this rule
Individual filter
performance
Monthly verification of the
following:
(I) Individual filter effluent
(IFE) turbidity levels less than or
equal to 0.15 NTU in at least
95% of samples each month in
each filter; and
(II) No individual filter greater
than 0.3 NTU in two consecutive
readings 15 minutes apart
Monthly reporting within 10 days
following the month in which the
monitoring was conducted, beginning
on the applicable treatment compliance
date in section (12) of this rule
Demonstration of
performance
(I) Results from testing
following a department approved
protocol
No later than the applicable treatment
compliance date in section (12) of this
rule
(II) As required by the
department, monthly verification
of operation within conditions of
department approval for
demonstration of performance
credit
Within 10 days following the month in
which monitoring was conducted,
beginning on the applicable treatment
compliance date in section (12) of this
rule
Bag filters and cartridge
filters
(I) Demonstration that the
following criteria are met:
(A) Process meets the definition
of bag or cartridge filtration; and
(B) Removal efficiency
established through challenge
testing that meets criteria in this
rule
No later than the applicable treatment
compliance date in section (12) of this
rule
(II) Monthly verification that
100% of plant flow was filtered
Within 10 days following the month in
which monitoring was conducted,
beginning on the applicable treatment
compliance date in section (12) of this
rule
Membrane filtration
(I) Results of verification testing
demonstrating the following:
(A) Removal efficiency
established through challenge
testing that meets criteria in this
rule; and
(B) Integrity test method and
parameters, including resolution,
sensitivity, test frequency,
control limits, and associated
baseline
No later than the applicable treatment
compliance date in section (12) of this
rule
(II) Monthly report summarizing
the following:
(A) All direct integrity tests
above the control limit; and
(B) If applicable, any turbidity
or alternative department
approved indirect integrity
monitoring results triggering
direct integrity testing and the
corrective action that was taken
Within 10 days following the month in
which monitoring was conducted,
beginning on the applicable treatment
compliance date in section (12) of this
rule
AUTHORITY: section 640.100, RSMo 2016.*
Original rule filed Feb. 27, 2009, effective
Oct. 30, 2009. Amended: Filed June 13,
2018, effective Feb. 28, 2019.
*Original authority: 640.100, RSMo 1939, amended 1978,
1981, 1982, 1988, 1989, 1992, 1993, 1995, 1996, 1998,
1999, 2002, 2006, 2012, 2014.