Regl. 2345
Enmienda al Reglamento Núm. 4, Parte 1910 (OSHA) Sección 1910.309 "National Electric Code". No incluido en el índice bajo Ley 149 de 12 dic, 2005
Cite as Reglamento Núm. 2345
No. 2345
Date: February
Approved: Reinaldo Paniagua Diez
Secretary of State
Commonwealth of Puerto Byco) Laurder
Department of Labor and Health Offices
Occupational Safety and
of
State
Barbosa Avenue 414
Hato Rey, Puerto Rico
RESOLUTION
I, Carlos S. Quirós, Puerto Rico Secretary of Labor and
Human Resources pursuant to the authority conferred by Section 8
of the Puerto Rico Occupational Safety and Health Act, Act
Number 16 of August 5, 1975 (LPRA) as amended, hereby amend the
Puerto Rico Occupational Safety and Health Regulation Number
Four (Part 1910) approved on February 1st, 1978 by adopting the
revision to Section 1910.309 "National Electric Code" which
appears in the Federal Register, Volume 41 Number 246 of
December 21, 1976.
This adoption shall be effective immediately after its
approval.
Given on this 21 day of February of 1978.
Carlos S. Quirós
Secretary of Labor and Human Resources
55703
(iv) The following tests shall be performed on all cord sets, receptacles which
are not a part of the permanent wiring
of the building or structure, and cordand plug-connected equipment required
§ 1910.309 National ode.
to be grounded:
(A) All equipment grounding conductors shall be tested for continuity and
(c) Ground-funlt protection-(1)
shall be electrically continuous.
General. Notwithstanding the provisions
(B) Each receptacle and attachment
of paragraphs (a) and (b) of this seccap or plug shall be tested for correct
tion, the requirement in section 210-7 of
attachment of the equipment grounding
the 1971 National Electrical Code (NFPA
conductor. The equipment grounding
70-1971: ANSI C1-1971) that all 15- and
conductor shall be connected to its prop-
20-ampere receptacle outlets on singleer terminal.
phase circuits for construction sites have
(V) All required tests shall be perapproved ground-fault circuit protecformed:
tion for personnel does not apply. In lieu
(A) Before first use;
thereof, the employer shall use either
(B) Before equipment is returned to
ground-fault circuit interrupters as
service following any repairs;
specified in paragraph of this sec-
(C) Before equipment is used after
tion or an assured equipment grounding
any incident which can be reasonably
conductor program as specified in parasuspected to have caused damage (for
graph (c) (3) of this section, to protect
example, when a cord set is run over);
employees on construction sites. These
and
requirements are in addition to any other
(D) At intervals not to exceed 3
requirements for equipment grounding
months, except that cord sets and recepconductors.
tacles which are fixed and not exposed
(2) Ground-fault circuit interrupters.
to damage shall be tested at intervals
All 120-volt, single-phase, 15- and 20-
not exceeding 6 months.
ampere receptacle outlets on construe-
(vi) The employer may not make availtion sites, which are not a part of the
able or permit the use by employees of
permanent wiring of the building or
any equipment which has not met the
structure and which are in use by emrequirements of this paragraph (c) (3) of
ployees, shall have approved groundthis section.
fault circuit interrupters for personnel
(vii) Tests performed as required in
protection. Receptacles on a two-wire,
this paragraph shall be recorded. This
single-phase portable or vehicletest record shall identify each receptacle,
mounted generator rated not more than
cord set, and cord- and plug-connected
5kW, where the circuit conductors of
equipment that passed the test, and shall
the generator are insulated from the
indicate the last date it was tested or the
generator frame and all other grounded
interval for which it was tested. This recsurfaces, need not be protected with
ord shall be kept by means of logs, color
ground-fault circuit interrupters.
coding, or other effective means, and
(3) Assured equipment grounding conshall be maintained until replaced by a
ductor program. The employer shall esmore current record. The record shall be
tablish and implement an assured equipmade available on the jobsite for inspecment grounding conductor program on
tion by the Assistant Secretary and any
construction sites covering all cord sets,
affected employee.
receptacles which are not a part of the
permanent wiring of the building or
structure, and equipment connected by
cord and plug, which are available for
use or used by employees. This program
shall comply with the following minimum requirements:
(i) A written description of the program, including the specific procedures
adopted by the employer, shall be available at the jobsite for inspection and
copying by the Assistant Secretary and
any affected employee.
(ii) The employer shall designate one
or more competent persons (as defined
in 29 CFR 1926.32(f) ) to implement the
program.
(iii) Each cord set, attachment cap,
plug and receptacle of cord sets, and any
equipment connected by. cord and plug,
except cord sets and receptacles which
are fixed and not exposed to damage,
shall be visually inspected before each
day's use for external defects, such as
deformed or missing pins or insulation
damage, and for indication of possible
internal damage. Equipment found damaged or defective may not be used until
repaired.
FEDERAL REGISTER, VOL. 41, NO. 246-TUESDAY, DECEMBER 21, 1976